Cable Trays · NEC 392 · 2026-05-29

Cable Tray Fill Ratio & Width: NEC 392.22 Worked Example

NEC 392.22 does not set a flat 40% fill. For power and lighting cables in a ladder or ventilated trough tray it points to Table 392.22(A) Column 1 — an absolute fill area running from 1,500 mm² at 50 mm width to 27,000 mm² at 900 mm — while control-or-signal-only trays are capped at 50% (ladder, ventilated) or 40% (solid bottom). Single-conductor cables follow a third test entirely: the sum of their outside diameters must fit the tray width. This guide gives the clause-by-clause method, two worked examples with every figure shown, and the 392.80 derating that follows once the tray is sized.

Published 2026-05-29Updated 2026-09-22 Reading ~15 minLevel: Intermediate
Ladder-type cable tray carrying power and control cables in an industrial installation
Figure 1 — Mixed power and control cables in a ladder tray. Fill is checked per cable class, not once for the whole tray, and the governing test differs between multiconductor and single-conductor cables.

01What NEC 392.22 actually requires

Fail here and the tray either jams during the pull or fails the inspector's fill check at submittal stage. The section is short but it does not work the way most summaries describe it, because it splits into three separate tests by cable type and tray type — and only one of those three tests is a percentage.

The three tests, in one line each

Power and lighting cables (multiconductor, ≤2000 V): an absolute area limit from Table 392.22(A), not a percentage. Ladder, ventilated trough and wire mesh take Column 1; solid bottom takes the smaller Column 3.

Control and signal cables on their own: 50% of the interior cross-sectional area in a ladder or ventilated trough tray, 40% in a solid bottom tray — both calculated on the tray's inside depth capped at 150 mm.

Single-conductor cables: no area table at all for 1/0–4/0 AWG — the sum of the cable outside diameters simply has to fit inside the tray width.

Power and lighting cables: a table of areas, not a percentage

Where a ladder or ventilated trough tray carries multiconductor power or lighting cables, or any mixture of power, lighting, control and signal cables, 392.22(A)(1) sends you to one of three sub-rules depending on conductor size:

  • All cables 4/0 AWG or larger — the sum of the cable outside diameters must not exceed the tray width, and the cables sit in a single layer. No area calculation at all.
  • All cables smaller than 4/0 AWG — the sum of the cable cross-sectional areas must not exceed Column 1 of Table 392.22(A).
  • A mixture of the two — the cables smaller than 4/0 AWG must fit within Column 2, which is Column 1 minus 30 mm multiplied by the sum of the diameters of the 4/0-and-larger cables. Those larger cables go in a single layer, and nothing may be laid on top of them.

Solid bottom trays repeat the same three-way split in 392.22(A)(3), with one material difference: the 4/0-and-larger diameter sum is capped at 90% of the tray width rather than 100%, and the area columns are the smaller Column 3 and Column 4.

Notice what is absent. There is no line in 392.22(A)(1) or (A)(3) that says "power cables are limited to 40% of the tray." The limit is a number of square millimetres read off a table against your tray width — 3,000 mm² at 100 mm wide, 6,000 mm² at 200 mm, 9,000 mm² at 300 mm — and it does not change with tray depth.

Control and signal only: where 50% and 40% come from

The two percentages everyone quotes do exist in 392.22, but they belong to a narrower case than most summaries imply. They apply to a tray whose contents are only multiconductor control and/or signal cables:

  • 392.22(A)(2) — ladder or ventilated trough, usable inside depth 150 mm (6 in) or less: total cable area ≤ 50% of the interior cross-sectional area.
  • 392.22(A)(4) — solid bottom, usable inside depth 150 mm or less: total cable area ≤ 40% of the interior cross-sectional area.

The 150 mm cap matters on deep trays. Where the usable inside depth exceeds 150 mm, both clauses direct you to compute the allowable interior area using a depth of 150 mm — extra depth buys you nothing for fill purposes when the tray carries only control and signal cable.

Single-conductor cables: a diameter sum for the small sizes

Single-conductor cables do not use the multiconductor area table. 392.22(B)(1) splits them by size:

  • 1/0 through 4/0 AWG — the sum of the diameters of all single conductors must not exceed the tray width. That is the whole test. 392.22(D) adds that these conductors are installed in a single layer unless they are bound into circuit groups such as triplexed assemblies.
  • 250 kcmil through 900 kcmil — the sum of the cross-sectional areas must fit Column 1 of Table 392.22(B)(1); mixed with 1000 kcmil and larger, the smaller conductors fit Column 2.
  • 1000 kcmil and larger — sum of diameters must not exceed the tray width, single layer.

This is the single most common sizing error we see on submittals: a 4/0 single-conductor feeder run checked against a percentage of the tray area, when the governing clause is a diameter sum that will reject or accept the tray long before any area figure does.

Correction — this article's earlier method

An earlier version of this page stated that NEC 392.22 limits power and lighting cables to 40% fill, solid-bottom trays to 35%, and that a mixed power-and-control tray is checked at 40% for the power portion and 50% for the control portion. Checked against the clause text, that is not how 392.22 works:

  • The 40% figure belongs to 392.22(A)(4) — control and/or signal cables only, in a solid bottom tray. Not power cables.
  • The 50% figure belongs to 392.22(A)(2) — the same control-and-signal-only case, in a ladder or ventilated trough tray.
  • Power and lighting cables are limited by the absolute areas of Table 392.22(A) Column 1, and mixed trays by Column 2 (Column 1 minus a deduction for the large cables).
  • A 35% limit for solid bottom trays does not appear in 392.22 for any cable class.

The worked examples below use the clause figures. Every step is shown so you can re-run it against the clause text you are designing to.

Table 1 — Which clause governs your tray
Tray typeWhat is in itGoverning clauseTest
Ladder / ventilated trough / wire meshMulticonductor power or lighting, or any mix of power, lighting, control, signal392.22(A)(1)Area ≤ Table 392.22(A) Col. 1; mixed → Col. 2; all ≥4/0 AWG → diameter sum ≤ width, single layer
Ladder / ventilated troughMulticonductor control and/or signal only392.22(A)(2)Area ≤ 50% of interior area, depth taken as 150 mm max
Solid bottomMulticonductor power or lighting, or any mix of power, lighting, control, signal392.22(A)(3)Area ≤ Table 392.22(A) Col. 3; mixed → Col. 4; all ≥4/0 AWG → diameter sum ≤ 90% of width
Solid bottomMulticonductor control and/or signal only392.22(A)(4)Area ≤ 40% of interior area, depth taken as 150 mm max
Ladder / ventilated troughSingle-conductor, 1/0–4/0 AWG392.22(B)(1)(d)Sum of diameters ≤ tray width; single layer (392.22(D))
Ladder / ventilated trough / wire meshSingle-conductor, 250–900 kcmil392.22(B)(1)(b)Area ≤ Table 392.22(B)(1) Col. 1
Ladder / ventilated trough / wire meshSingle-conductor, 1000 kcmil and larger392.22(B)(1)(a)Sum of diameters ≤ tray width; single layer
Ventilated / solid channelMulticonductor, any type392.22(A)(5) / (A)(6)Single cable → Col. 1 of the channel table; more than one → Col. 2

Clause numbering per Article 392 as published in the 2020 edition of the NEC (adopted as the 2022 California Electrical Code). The structure of 392.22(A)(1)–(A)(6) and 392.22(B)(1)(a)–(d) is unchanged in the 2023 edition.

02The five inputs you need before sizing anything

Sizing goes wrong at the data-gathering stage far more often than at the arithmetic. Five inputs, in this order:

  1. The tray type and usable inside dimensions. Ladder, ventilated trough, wire mesh, solid bottom or channel — it decides which clause you are in. "Usable" matters: side-rail intrusion and rung profile mean a 600 mm nominal ladder does not present 600 mm of cable bed.
  2. The cable class for every cable in the run. Multiconductor or single-conductor, and the conductor size bracket (below 4/0 AWG, 4/0 and above, 250–900 kcmil, 1000 kcmil and above). One cable in the wrong bracket and you are reading the wrong column.
  3. Finished outside diameter from the manufacturer's data sheet. Not the bare conductor diameter, and not the conduit trade size. Every Sorivo product page publishes the finished OD; for example the THHN building wire and YY/SY/CY flexible control cable pages.
  4. Quantity per size. The fill calculation is a sum, so it needs counts, not counts-and-a-bit-for-spare. Add the spares as a separate line so the client can see them.
  5. The support span and the load class you are designing to. Fill is only half of the tray decision — span and load come from the product standard, not from Article 392.
Do this before quoting

Put the OD, quantity and conductor size bracket on one line per cable size, then compute the governing quantity — area or diameter sum — once per bracket. If your schedule mixes 4/0 and smaller cables, expect to compute two figures, not one.

03Worked example 1: single-conductor 4/0 feeders

Six single-conductor 4/0 AWG THHN copper feeders, to be laid in a ladder tray, single layer. This is 392.22(B)(1)(d) territory — the diameter sum test — and the calculation takes two lines.

Table 2 — Inputs for example 1 (single-conductor)
CableClassQtyFinished OD (mm)Diameter sum (mm)
4/0 AWG THHN, copper, single coreSingle-conductor, 1/0–4/0 AWG bracket617.3103.8

OD is a representative figure from the manufacturer's data sheet for finished 4/0 AWG THHN. Substitute the OD from the data sheet for the cable you are actually buying — the test and the clause do not change.

392.22(B)(1)(d) — diameter sum test
  1. Sum of diameters = 6 × 17.3 = 103.8 mm
  2. Requirement: sum of diameters ≤ tray inside width
  3. 103.8 mm ≤ 150 mm → PASS at 150 mm width
  4. 103.8 mm ≤ 200 mm → PASS with 96 mm of spare width

Two consequences worth carrying into the submittal. First, tray depth is irrelevant to this test — a 50 mm deep tray and a 150 mm deep tray pass identically at 150 mm width, because the clause constrains width only. Second, the spare width is not spare fill: 392.22(D) requires these conductors in a single layer, so the 96 mm of headroom at 200 mm width is headroom for future cables laid alongside, not above.

Contrast that with the same ampere rating in a different construction. Take six single-conductor 250 kcmil cables instead, which sit in the 250–900 kcmil bracket and therefore switch to the area table:

392.22(B)(1)(b) — area test for comparison
  1. Area per cable = π × (21.2 / 2)² = 353 mm²
  2. Sum of areas = 6 × 353 = 2,118 mm²
  3. Table 392.22(B)(1) Column 1: 100 mm width → 2,800 mm²; 150 mm width → 4,200 mm²
  4. 2,118 ≤ 2,800 → PASS at 100 mm width

One size bracket down the list, and the governing quantity flipped from a diameter sum to an area. Reading the right row of Table 1 is the whole skill here.

When you have the numbers Send us the cable schedule with conductor sizes and quantities and we will return the minimum tray width and depth against the clause you are designing to — request a tray and cable quote.

04Worked example 2: mixing power and control

Now the case that trips most people: large multiconductor power cables sharing a tray with smaller control cables. One cable class is above the 4/0 AWG line, the rest below it, so 392.22(A)(1)(c) governs and the deduction term Sd appears.

Table 3 — Inputs for example 2 (mixed multiconductor)
CableBracketQtyOD (mm)Area each (mm²)Subtotal (mm²)
4/0 AWG multiconductor power cable, copper4/0 AWG and larger627.0572.63,435.4
12 AWG 4-core shielded control cableSmaller than 4/0 AWG1211.9111.21,334.4

OD values are representative manufacturer data-sheet figures for the constructions named. The 4/0-and-larger cables are not counted in the area column that matters — under (A)(1)(c) they are handled by the deduction term, not by an area sum.

392.22(A)(1)(c) asks one question: is the total area of the smaller cables within Column 2? And Column 2 is defined as Column 1 minus 30 mm times Sd, where Sd is the sum of the diameters of the 4/0-and-larger cables in the same tray.

392.22(A)(1)(c) — mixed size test, 200 mm tray first
  1. Sd = 6 × 27.0 = 162 mm
  2. Column 1 at 200 mm width = 6,000 mm²
  3. Column 2 = 6,000 − (30 × 162) = 6,000 − 4,860 = 1,140 mm²
  4. Smaller-cable area = 12 × 111.2 = 1,334.4 mm²
  5. 1,334.4 > 1,140 → FAIL at 200 mm width
Same run in a 225 mm tray
  1. Column 1 at 225 mm width = 6,800 mm²
  2. Column 2 = 6,800 − 4,860 = 1,940 mm²
  3. 1,334.4 ≤ 1,940 → PASS at 225 mm width
  4. Layout check: the six 27 mm cables need 162 mm of width as a single layer, which fits inside 225 mm

Two things to take from this. The deduction term is not small: on a 200 mm tray it consumed 4,860 of the 6,000 mm² allowance, or 81% of the table value, purely because six large cables share the tray. And the arithmetic is indifferent to how you feel about the answer — the run that "looks fine" at 200 mm is short by 194 mm² of allowable area, and the fix is one width step, not a redesign.

If the same two cable groups sat in a solid bottom tray instead, you would repeat the calculation against Column 3 and Column 4: Column 3 at 225 mm is 5,100 mm², Column 4 is 5,100 − (25 × 162) = 1,050 mm², and the 1,334.4 mm² of control cable would fail at every width up to 300 mm. Solid bottom trays are materially stricter, and that is the only sense in which a percentage such as 40% describes power trays — loosely, and by coincidence of the numbers.

The mistake this replaces

Using conductor diameter instead of finished cable OD. A 4/0 bare conductor is roughly 13 mm; the finished cable is roughly 17 mm. In area terms that is a 36% difference — enough to move a tray one or two standard widths. Always the data sheet, never the conductor table.

05The lookup tables, in the units you work in

Both tables are published in the NEC with a millimetre column and an inch column side by side. They are separate tabulations rather than conversions of one another — the inch figure for a 100 mm tray is 4.5 in², while the millimetre figure of 3,000 mm² converts to about 4.65 in². Work from the column that matches your drawings and do not convert between them. The tables below reproduce the millimetre columns, which is how SORIVO trays and most export project drawings are specified.

Table 4 — Table 392.22(A): allowable fill area, multiconductor cables ≤2000 V
Inside width (mm / in)Col. 1 — ladder, ventilated trough, wire meshCol. 2 — same trays, mixed sizesCol. 3 — solid bottomCol. 4 — solid bottom, mixed sizes
50 / 21,500 mm²1,500 − (30 × Sd)1,200 mm²1,200 − (25 × Sd)
100 / 43,000 mm²3,000 − (30 × Sd)2,300 mm²2,300 − (25 × Sd)
150 / 64,500 mm²4,500 − (30 × Sd)3,500 mm²3,500 − (25 × Sd)
200 / 86,000 mm²6,000 − (30 × Sd)4,500 mm²4,500 − (25 × Sd)
225 / 96,800 mm²6,800 − (30 × Sd)5,100 mm²5,100 − (25 × Sd)
300 / 129,000 mm²9,000 − (30 × Sd)7,100 mm²7,100 − (25 × Sd)
400 / 1612,000 mm²12,000 − (30 × Sd)9,400 mm²9,400 − (25 × Sd)
450 / 1813,500 mm²13,500 − (30 × Sd)10,600 mm²10,600 − (25 × Sd)
500 / 2015,000 mm²15,000 − (30 × Sd)11,800 mm²11,800 − (25 × Sd)
600 / 2418,000 mm²18,000 − (30 × Sd)14,200 mm²14,200 − (25 × Sd)
750 / 3022,500 mm²22,500 − (30 × Sd)17,700 mm²17,700 − (25 × Sd)
900 / 3627,000 mm²27,000 − (30 × Sd)21,300 mm²21,300 − (25 × Sd)

Sd = the sum, in millimetres, of the diameters of all 4/0 AWG and larger multiconductor cables sharing the tray. Column 1 applies under 392.22(A)(1)(b); Column 2 under (A)(1)(c); Column 3 under (A)(3)(b); Column 4 under (A)(3)(c). The allowable area does not vary with tray depth. Column 1 follows the tray width at roughly 30 mm² per millimetre of width, but read the table rather than the ratio — the published values are the enforceable ones.

Table 5 — Table 392.22(B)(1): allowable fill area, single-conductor cables ≤2000 V
Inside width (mm / in)Col. 1 — 250–900 kcmilCol. 2 — mixed with 1000 kcmil and larger
50 / 21,400 mm²1,400 − (28 × Sd)
100 / 42,800 mm²2,800 − (28 × Sd)
150 / 64,200 mm²4,200 − (28 × Sd)
200 / 85,600 mm²5,600 − (28 × Sd)
225 / 96,100 mm²6,100 − (28 × Sd)
300 / 128,400 mm²8,400 − (28 × Sd)
400 / 1611,200 mm²11,200 − (28 × Sd)
450 / 1812,600 mm²12,600 − (28 × Sd)
500 / 2014,000 mm²14,000 − (28 × Sd)
600 / 2416,800 mm²16,800 − (28 × Sd)
750 / 3021,000 mm²21,000 − (28 × Sd)
900 / 3625,200 mm²25,200 − (28 × Sd)

Sd here is the sum, in millimetres, of the diameters of all 1000 kcmil and larger single-conductor cables in the same tray. Single conductors of 1/0–4/0 AWG do not appear in this table at all — they are governed by the diameter sum test in Table 1.

06Ampacity derating once the tray is sized

Fill is the geometric check. The electrical check is 392.80, and it is where a passing fill calculation can still produce a cable that runs hot. The factors depend on whether the cables are multiconductor or single-conductor, and on whether the tray is covered.

Table 6 — Ampacity adjustment in cable tray, 392.80(A)
Cable typeTray conditionMaximum ampacityClause
Multiconductor, ≤2000 VLadder, ventilated trough, uncoveredTable 310.16 / 310.18 values392.80(A)(1)
Multiconductor, ≤2000 VContinuously covered >1.8 m with solid unventilated covers95% of Table 310.16 / 310.18392.80(A)(1)(b)
Single-conductor, 1/0 AWG–500 kcmilUncovered65% of Table 310.17 / 310.19392.80(A)(2)(b)
Single-conductor, 1/0 AWG–500 kcmilContinuously covered >1.8 m60% of Table 310.17 / 310.19392.80(A)(2)(b)
Single-conductor, 600 kcmil and largerUncovered75% of Table 310.17 / 310.19392.80(A)(2)(a)
Single-conductor, 600 kcmil and largerContinuously covered >1.8 m70% of Table 310.17 / 310.19392.80(A)(2)(a)
Single-conductor, 1/0 AWG and largerSingle layer, spacing ≥1 cable diameterTable 310.17 / 310.19 values392.80(A)(2)(c)

The four derating percentages are quoted from 392.80(A)(1)(b) and (A)(2)(a)(b) as published. Note that (A)(2)(a)–(b) apply to single-conductor installations following 392.22(B) — which is exactly the case in worked example 1, where six 4/0 THHN feeders fall in the 1/0–500 kcmil bracket and are therefore held to 65% of the free-air table in an uncovered tray unless they are laid single-layer with at least one cable diameter of spacing between conductors.

Correction — derating figures

An earlier version of this page gave the covered-tray derating as 95% for 4–6 cables, 90% for 7–24 and 85% for 25–42. Those three bands do not appear in 392.80. The clause gives a single 95% factor for covered multiconductor installations, and a set of size-based factors for single-conductor installations. If you are working from the earlier figures, re-check the ampacity column of the design — the difference between 90% and 65% on a 4/0 feeder is not a rounding matter.

Ambient temperature and grouping corrections still apply on top, and the tray is not special in that respect — the same correction factors that apply in conduit and direct burial apply here. We work through the stacking of temperature, grouping and altitude corrections in the ampacity derating factors guide, and the installation-method comparison for tray versus conduit versus burial is in cable ampacity by installation method.

07NEMA VE 1 vs IEC 61537: which load number are you reading?

Article 392 tells you how full the tray may be. It says nothing about whether the tray can carry the load. That comes from the product standard, and the two families in common use derive their numbers differently — which is why a load figure quoted without its span is not a comparison at all.

Table 7 — NEC 392, NEMA VE 1 and IEC 61537 side by side
AspectNEC 392NEMA VE 1IEC 61537
ScopeInstallation: permitted uses, fill limits, deratingProduct: load classes, testing, materialsProduct + tests, internationally adopted
Fill limitAreas from Table 392.22(A) and (B); 50% / 40% for control-only traysNot specifiedNot a percentage — cables per layer by OD and tray width, with spacing factors
Basis of the load figureNot addressedLoad-based: test to destruction, published load carries a 1.5 safety factor, plus a 200 lb (90.7 kg) concentrated load without collapseDeflection-based: the declaration pairs a safe working load with a support span and a deflection criterion
Load class notationSpan in feet plus letter: A = 50, B = 75, C = 100 lb/ftNo letter class — the load, span and deflection are stated together
Natural marketUSANorth AmericaEurope, Middle East, Africa, Asia

NEMA VE 1 figures from the type-test description published in manufacturer engineering guides; IEC 61537 structure per the 2023 edition's published scope and change list. The two are not convertible: a NEMA class and an IEC declaration describe different tests of the same physical tray.

Correction — comparison table

An earlier version of this page gave the load-test row as "NEMA VE 1: 1.5× SWL, deflection ≤ span/150" and "IEC 61537: 1.5× SWL, deflection ≤ span/200". The 1.5 safety factor is correct for NEMA VE 1, but NEMA VE 1 verifies its published load by testing to destruction and does not impose a span-fraction deflection acceptance criterion in the way that phrasing suggests. Nor does 1.5 × SWL with a span/200 deflection figure describe the IEC method — IEC declarations are deflection-based, and the criterion travels with the declaration rather than being inherited from the standard. Both rows have been replaced with what the two frameworks actually define.

Standards update

IEC 61537:2023 (edition 3.0) was published on 24 January 2023 and cancels the 2006 edition. It is a technical revision, not a reprint: figures were repositioned and renumbered, the corrosion classification was revised, the SWL test types and procedures were revised, tests were added for vertical mounting and running orientations and for support devices, and new annexes were added including guidance on using the tray as a protective earth conductor. A test report to the 2006 edition is not automatically a report to the 2023 edition — confirm which edition your project specification invokes and ask suppliers for load data aligned to it. IEC 61537:2023 publication page.

08What separates a 20-year tray from a 3-year tray

Fill and load get the attention; coating and traceability decide whether the installation is still sound in year fifteen. Steel gauge, galvanizing quality and published load data vary widely between suppliers, and the differences are visible in the documents rather than in the catalogue photograph.

Table 8 — Evidence to ask for, and what its absence means
What to checkWeak answerAnswer that survives a submittal review
Steel thicknessNominal gauge only, no per-width figureStated thickness per width, e.g. 2.0 mm at 300 mm width, with the load class it supports
Galvanizing"Hot dip galvanized" with no standard or gradeCoating per ASTM A123 / ISO 1461 with the minimum thickness grade stated for each steel thickness on the shop drawing
Load dataA bare SWL number with no spanLoad table indexed by support span, with the test factor and the deflection criterion stated
FittingsField modification expected at bends and teesStandardised splice, bend and tee family, so the installed system matches the tested one
TraceabilityNo marking on the sectionBatch-traceable marking, mill certificates and coating thickness reports on request

How to read a tray load table

A usable load table carries three numbers, not one: the safe working load, the support span it is valid at, and the deflection criterion at that load. A figure quoted without the span cannot be compared with your route, and a figure quoted without a deflection criterion cannot be compared with a project that specifies one. When you hold all three constant between two suppliers, the comparison becomes arithmetic instead of impression.

Two checks catch most submittal problems. Confirm the span in the table matches your actual support spacing — load capacity falls quickly as span increases, so a table based on a 1.5 m span tells you nothing about a 3 m run. Then ask for the underlying test report rather than the summary figure; a supplier with certified tables and batch traceability produces both within a day.

Galvanizing: what the coating numbers mean

Both ASTM A123 and ISO 1461 set minimum coating thickness by steel thickness rather than as a single site-wide figure. ASTM A123 Table 1 grades for structural shapes step up through 45, 65, 75 and 100 µm as the steel gets thicker; ISO 1461 works in minimum mean thickness bands, in the region of 45–55 µm for steel under 3 mm and 70–85 µm at and above 3 mm. That is why a specification written as "galvanized to 65 µm" is incomplete: on a thin rail it may be generous, and on a 3 mm side rail it may be below the grade the standard assigns.

Hot-dip galvanizing after fabrication is what makes the coating work at the edges. Every sheared edge and punched hole on a pre-galvanized (coil-coated) tray is bare steel — typically around 18–20 µm of zinc per side on the coil, with nothing on the cut face — which is why thin pre-galvanized trays rust at the cut edges and splice plates first, not in the middle of the rail. Match the finish to the environment: dry conditioned interiors tolerate the thinner coatings, while outdoor, coastal, wastewater and chemical areas justify stainless 304/316 or aluminium despite the premium. When a specification simply says galvanized to ASTM A123 or ISO 1461, ask for the coating thickness grade per steel gauge on the shop drawing. It turns site acceptance into a measurement rather than an argument.

09Three things that change the sum

Covered and solid-cover trays

A solid cover traps heat and triggers 392.80(A)(1)(b): covered for more than 1.8 m, multiconductor cables are held to 95% of the ampacity table, and single-conductor cables generally to a lower figure still. A tray that passes the fill check at 40% of the available area can still fail the ampacity check once the cover is on. Size the cables, not just the tray, with the cover in the calculation.

Multi-layer arrangement

Ladder trays physically accept multiple layers, and Article 392 constrains the ones that matter: cables 4/0 AWG and larger — and in mixed trays, all of them — must sit in a single layer with nothing laid on top, and 1/0–4/0 AWG single conductors must be single-layer as well. Each extra layer of the cables that are permitted to stack reduces airflow and pushes you toward the derating figures above.

Firestop at rated penetrations

Firestop pillows, wrap strips and putty pads occupy tray volume at the crossing. Where the tray passes through a fire-rated wall or floor, size the penetration so the listed firestop system can be installed around the cables without compressing them against the rungs, and carry the extra width through the rest of the run rather than narrowing it immediately either side of the wall.

10What we publish, and what we do not

This page quotes clause-level fill and derating requirements from Article 392 as published, and gives two worked examples with the arithmetic visible so a reviewer can re-run them. It does not interpret your local amendment cycle, and it does not replace the engineer of record's check against the edition your jurisdiction has adopted — adoption of a new NEC edition varies by state and by project, and the clause structure is what has to be confirmed, not the article number.

On the tray side, we publish what we build and test: tray types, materials, finishes and load data, with certificates where a project requires them. We do not publish a fill calculator that silently mixes the three tests in Table 1, because the most common sizing failure we see is not arithmetic — it is applying the control-cable percentage to a power-cable tray.

Short version. Identify the cable class per cable, not per tray. Read the governing clause off Table 1. Compute the area or the diameter sum with finished outside diameters. Then apply 392.80 before you accept the ampacity column. Four steps, and the tray stops being the reason the inspection fails.

Need the tray width checked against your cable schedule?

Send us the cable types, conductor sizes, quantities and finished outside diameters, plus your support span. We will return the minimum tray width and depth against the clause you are designing to, with the cable side of the schedule quoted at the same time.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Experienced in cable specification aligned with IEC standards.

Sources checked for this article

  • NFPA 70, Article 392 — Cable Trays. Clause structure, fill limits and derating references quoted throughout; read against the full article text of the edition adopted as the 2022 California Electrical Code. NFPA National Electrical Code
  • California Building Standards Commission — Electrical Code. The adopted state text from which the clause numbering in this article is verified. California codes and standards
  • IEC 61537:2023 — Cable management: cable tray systems and cable ladder systems. Edition 3.0, published 2023-01-24, cancels the 2006 edition; scope, change list and test structure as cited. IEC 61537:2023 publication page
  • Eaton B-Line — Cable Tray Design Considerations Guide. Manufacturer engineering guide describing the NEMA VE 1 and IEC 61537 load-test methods and why their figures are not interchangeable. Cable tray design considerations (PDF)
  • NEMA VE 1 — Metal Cable Tray Systems. Load class notation, the 1.5 safety factor on published load and the 200 lb (90.7 kg) concentrated-load requirement, as stated in B-Line series tray load data. B-Line series straight section load data
  • ASTM A123 / A123M — Zinc (hot-dip galvanized) coatings on iron and steel products. Minimum coating thickness grades by material category and steel thickness. ASTM A123
  • ISO 1461 — Hot dip galvanized coatings on fabricated iron and steel articles. Minimum mean coating thickness bands by steel thickness. ISO 1461

Related reading

Related products · cables and trays quoted against the same schedule
THHN 10 AWG Stranded Copper Building Wire
ApplicationBranch circuits, feeders and tray or conduit runs in North American installations
StandardsUL 83
ConductorStranded copper
InsulationPVC with nylon jacket
Voltage Rating600 V
YY/SY/CY Flexible Control Cable 300/500 V
ApplicationFlexible control and signal wiring; CY screened versions for EMC-sensitive runs
StandardsBS EN 50525
InsulationPVC
Voltage Rating300/500 V
CU/XLPE/SWA/PVC 0.6/1 kV Armoured Power Cable
ApplicationArmoured LV power distribution, including routes that leave the tray
StandardsIEC 60502-1
ConductorCopper
InsulationXLPE
Voltage Rating0.6/1 kV
Tray and cable from one supplier? Send both schedules and we will quote them together so the OD figures you sized the tray with are the ones we ship against. request a quote.
Q1What is the maximum cable tray fill ratio under NEC 392.22?

There is no single ratio for power cables. Multiconductor power and lighting cables are limited by the absolute areas in Table 392.22(A) Column 1 — 3,000 mm² at 100 mm tray width, 6,000 mm² at 200 mm — and mixed-size trays by Column 2. The two percentages in 392.22 apply to control and signal cables only: 50% in a ladder or ventilated trough tray, 40% in a solid bottom tray.

Q2Is cable tray fill 40% or 50%?

Neither figure describes a power cable tray. The 50% limit is 392.22(A)(2), for a ladder or ventilated trough tray carrying multiconductor control and/or signal cables only. The 40% limit is 392.22(A)(4), the same cable class in a solid bottom tray. Both are calculated on the tray's inside depth capped at 150 mm. A power tray is checked against a fill area read from the table, not against a percentage.

Q3How do you calculate the minimum cable tray width?

Identify the cable class for each cable first, because the test changes. Multiconductor cables under 4/0 AWG use the sum of their cross-sectional areas against Table 392.22(A) Column 1. Single conductors of 1/0–4/0 AWG use the sum of their diameters against the tray width. Then step up through standard widths until the governing figure passes, and check ampacity under 392.80 separately.

Q4Can power and control cables share the same cable tray?

Yes. NEC 392.20(A) permits power, control and signal cables in one tray subject to the fill rules, and above 600 V a barrier or maintained separation is required. In a mixed tray the large multiconductor cables take the deduction term in Column 2, the smaller cables must fit within what is left, and the large cables go in a single layer with nothing laid on top of them.

Q5How much do you derate cable ampacity in a covered cable tray?

For multiconductor cables in a tray continuously covered for more than 1.8 m with solid unventilated covers, 392.80(A)(1)(b) allows not more than 95% of the ampacity table. Single-conductor cables of 1/0–500 kcmil are held to 65% uncovered and 60% covered; 600 kcmil and larger to 75% uncovered and 70% covered. Ambient and grouping corrections apply on top of these.

Q6Does IEC 61537 use the same fill rules as NEC 392?

No. IEC 61537 does not set a percentage fill limit at all — it works from the number of cables per layer based on cable outer diameter and tray width, with spacing factors. The NEC fill percentages are nevertheless widely written into international project specifications, so confirm which framework the specification invokes rather than assuming either one.