Solar Cable · 2026-09-10

10kW Solar Cable Size: 4mm² or 6mm²? Voltage Drop Guide

A 10 kW array is the most common capacity class in distributed generation, and the DC cable is the one component where a one-size-up decision is cheap at purchase and expensive to reverse later. This article gives the full sizing chain — design current, conductor resistance, temperature correction, voltage drop, ampacity check — with every input written down so you can substitute your own module data and reproduce the numbers.

Published 2026-09-10Updated 2026-09-10 Reading ~18 minLevel: Designer / EPC

01The reference 10kW system this article is built on

Voltage drop percentages are meaningless without the system they were calculated for, so here is the reference array in full. It is a typical 2026 residential-to-light-commercial build: 18 modules of 550 Wp, arranged as two strings of nine into a dual-MPPT inverter.

Table 1 — reference system parameters
ParameterValueNote
Array capacity9,900 Wp18 × 550 Wp, nominally 10 kW
Module Vmp / Imp at STC41.5 V / 13.25 ARepresentative high-efficiency mono module
Module Voc / Isc at STC49.5 V / 14.0 ARepresentative; take yours from the datasheet
Configuration A2 strings × 9Vmp 373.5 V, Imp 13.25 A, Voc 445.5 V
Configuration B1 string × 18Vmp 747 V, Imp 13.25 A, Voc 891 V — needs a 1,100 V or 1,500 V inverter
InverterDual MPPT string inverterConfig A: one string per tracker, no array-level combiner box
One-way cable distance20 / 40 / 60 / 80 / 100 mMeasured along the routed path, not straight-line

Module electrical data is representative of the 550 Wp class. Your datasheet controls — particularly Isc, which sets the design current in section 02, and the Voc temperature coefficient, which decides whether Configuration B is legal at your site's record low temperature.

02Start with the design current, not the cable

This is the step that most cable sizing articles skip, and it is the step that changes the answer. You do not size a PV cable to Imp. You size it to a design current that carries a safety factor, because a PV module can deliver more than its STC rating under cloud-edge irradiance and cold-cell conditions.

Table 2 — design current under the two main frameworks
FrameworkRuleResult for this array
IEC 60364-7-712Ib = Isc × 1.2514.0 × 1.25 = 17.5 A
NEC 690.8Isc × 1.25 × 1.25 = 156% of Isc14.0 × 1.56 = 21.8 A

The NEC factor is the product of two separate 1.25 factors in 690.8(A) and 690.8(B), not a single 1.56 rule — the distinction matters if you ever have to defend the calculation. Note also that bifacial modules require you to use the highest Isc on the datasheet, which may be the bifacial figure rather than the front-side STC value.

For the voltage drop work in sections 03 to 05 we use Imp = 13.25 A, because voltage drop is an energy-yield question evaluated at the operating point, not a thermal safety question. The 17.5 A or 21.8 A figure returns in section 06 for the ampacity check. Using the design current for the voltage drop calculation is conservative but slightly overstates the loss.

03The voltage drop formula, and which resistance to put in it

The DC voltage drop across a two-conductor string circuit is:

ΔV = 2 × L × I × R

  • L = one-way cable length in metres, measured along the routed path
  • I = string current in amperes (Imp at STC for a yield calculation)
  • R = conductor resistance in Ω/m at the operating temperature
  • 2 = the return path; both the positive and negative conductor drop voltage

The percentage drop is then ΔV% = ΔV / Vmp(string) × 100.

Two ways to get R, and why they differ by about 18%

Most published calculators use ideal copper resistivity divided by cross-section: R = ρ / A, with ρ20 = 0.017241 Ω·mm²/m. That is physically correct for a solid annealed copper conductor of exactly the nominal area. It is not what you will be supplied.

A certified flexible PV cable has a class 5 stranded conductor, and IEC 60228 permits a maximum DC resistance that is materially higher than ρ/A, because stranding adds length, lay and contact effects. Since you are buying a cable that meets IEC 60228, using the IEC 60228 maximum is both more traceable and more conservative:

Table 3 — conductor resistance basis at 20 °C and 90 °C
SizeIEC 60228 class 5 max at 20 °C (Ω/km)Ideal ρ20/A (Ω/km)DifferenceR at 90 °C (Ω/m)
2.5 mm²8.216.90+19%0.010469
4 mm²5.094.31+18%0.0064903
6 mm²3.392.87+18%0.0043226
10 mm²1.951.72+13%0.0024864
16 mm²1.241.08+15%0.0015811

Column 2 from EN 50618 parameter tables (five manufacturers agree). Column 3 = 0.017241 / A. Column 5 = column 2 ÷ 1,000 × 1.2751, the temperature correction explained below.

Temperature correction

Copper resistance rises with temperature: R(T) = R20 × [1 + α(T − 20)] with α = 0.00393 /°C. A PV cable on a dark roof in summer runs hot. At a conductor temperature of 90 °C the multiplier is 1 + 0.00393 × 70 = 1.2751, which is the factor used in column 5 above.

90 °C is a deliberate choice, not a rounding convenience. It is the maximum continuous conductor temperature for which EN 50618 PV cable is rated, and a rooftop conduit in a hot climate will approach it. Using 20 °C resistance would understate the drop by roughly 22% at the worst moment of the year — which is exactly the moment the inverter is clipping.

04How much voltage drop is acceptable?

This is one of the most searched questions in the category and the answer is less tidy than people want. IEC 60364-7-712 does not mandate a specific voltage drop percentage. What circulates as "the 3% rule" is a mixture of national practice, IEC 62548 guidance and NEC informational notes:

Table 4 — voltage drop targets in circulation, and where they come from
TargetValueStatus
IEC 60364-7-712No figure specifiedConfirmed by two independent readings of the standard
Common DC design practice1–2% on the DC sideWidely adopted QA and interconnection target
IEC 62548 (DC, module to inverter)3% combinedSingle-source reading [B]
NEC (US)2% source circuit + 1% output circuitInformational in the NEC; routinely enforced by AHJs

The binding constraint on your project is the one written into the interconnection agreement or enforced by the authority having jurisdiction. Where nothing is specified, 2% on the DC side is a defensible default and 1% is a reasonable stretch target for high-yield sites.

CorrectionAn earlier version of this article stated that IEC 60364-7-712 requires a 3% DC voltage drop. That is a misattribution: 712 does not set a percentage. The 3% figure belongs to IEC 62548 as a combined DC limit. Corrected above.

054mm or 6mm solar cable: results from 20 m to 100 m

Applying ΔV = 2 × L × 13.25 × R90 to Configuration A (Vmp = 373.5 V) gives the grid below. Percentages are of string Vmp.

Table 5 — voltage drop by cross-section and one-way distance, Configuration A (2 × 9 modules, Vmp 373.5 V, Imp 13.25 A)
One-way distance2.5 mm²4 mm²6 mm²10 mm²16 mm²
20 m1.49%0.92%0.61%0.35%0.22%
40 m2.97%1.84%1.23%0.71%0.45%
60 m4.46%2.76%1.84%1.06%0.67%
80 m5.94%3.68%2.45%1.41%0.90%
100 m7.43%4.60%3.07%1.76%1.12%

Every cell is reproducible: ΔV% = 2 × L × 13.25 × R90 / 373.5 × 100, with R90 from Table 3. Example, 4 mm² at 40 m: 2 × 40 × 13.25 × 0.0064903 = 6.880 V; 6.880 / 373.5 = 1.84%.

Voltage drop rises linearly with distance. At 40 metres, 4 mm² gives 1.84%, 6 mm² gives 1.23% and 10 mm² gives 0.71%. At 100 metres, 4 mm² reaches 4.60%, 6 mm² reaches 3.07% and 10 mm² reaches 1.76%. The 2% design target is crossed by 4 mm² at about 43 metres and by 6 mm² at about 65 metres; 10 mm² stays under 2% to beyond 100 metres. 0% 1% 2% 3% 4% 5% 20 m 40 m 60 m 80 m 100 m 4 mm² 6 mm² 10 mm² FIG 1 — DC VOLTAGE DROP vs DISTANCE, 10 kW ARRAY (2 × 9, 13.25 A) 2% target
Percentages are of string Vmp at a 90 °C conductor temperature. Read the crossing points rather than the absolute values: 4 mm² passes 2% at roughly 43 m, 6 mm² at roughly 65 m, and 10 mm² stays under 2% past 100 m.

The practical reading

  • Up to about 25 m: 4 mm² keeps you under 1.2%. Going to 6 mm² buys very little and costs copper for no measurable yield.
  • 25–45 m: 4 mm² is still inside 2%, but this is the band where 6 mm² starts to be worth pricing. The break-even maths is in section 08.
  • 45–70 m: 6 mm² is the right default. 4 mm² is now above the 2% target on yield grounds even where it still passes an ampacity check.
  • Beyond 70 m: start with 10 mm², and seriously consider whether the inverter can be moved closer. Cable is usually the more expensive way to fix a layout problem.
Where to go nextThese results are specific to a 373.5 V string. For 600 V, 1,000 V and 1,500 V system voltages, and for the general method rather than a worked 10 kW example, see the DC cable sizing guide. Once the size is fixed, the installation constraints that decide whether it survives 25 years are in our solar cable installation guide.

06Ampacity: the check that almost never binds

Voltage drop decides the size on PV DC circuits. Ampacity is the check you still have to do, and it usually passes with room to spare — which is worth stating explicitly, because the opposite is true on almost every other cable type.

Table 6 — EN 50618 current carrying capacity (60 °C ambient, 120 °C conductor) and temperature factors
SizeSingle cable in airSingle cable on a surfaceTwo loaded cables touching, on a surface
2.5 mm²41 A39 A33 A
4 mm²55 A52 A44 A
6 mm²70 A67 A57 A
10 mm²98 A93 A79 A
16 mm²132 A125 A107 A

Ambient temperature factors relative to 60 °C: 70 °C → 0.91, 80 °C → 0.82, 90 °C → 0.71, 100 °C → 0.58, 110 °C → 0.41. Grouping factors for more than two cables, conduit and burial come from IEC 60364-5-52, not from this table.

CorrectionAn earlier version of this article published 30 A, 40 A, 55 A and 74 A for 2.5, 4, 6 and 10 mm². Those values do not line up with the EN 50618 table reproduced consistently by five manufacturers — the correct figures are 41, 55, 70 and 98 A. If you sized a project from the old table, re-run the check; it was conservative for 2.5 mm² and 4 mm² and wrong in the unsafe direction nowhere, but it was wrong.

Now the actual check. At a 90 °C ambient — hotter than almost anywhere on earth at roof level — the 4 mm² single-cable value becomes 55 × 0.71 = 39 A. Two cables touching on a surface: 44 × 0.71 = 31 A. Both sit comfortably above the 21.8 A NEC design current and the 17.5 A IEC design current. Ampacity is not the constraint here; voltage drop is.

There is one situation where that flips: a long run bundled with many other cables in a tray or conduit in a hot climate. Six or more loaded cables together can push the grouping factor low enough that a 2.5 mm² or even a 4 mm² selection stops being safe. The full derating treatment for bundled and buried runs is in the current carrying capacity guide.

07When 10mm² is right, and when 1500 V is the cheaper answer

Two decisions get conflated in cable sizing: how big the conductor is, and how the array is configured. The second one is usually worth more.

When to step up to 10mm²

  • Long runs beyond about 70–80 m where 6 mm² would exceed your voltage drop target.
  • Combiner-box output circuits carrying the summed current of several strings — here the current genuinely is higher, and so is the stake.
  • High ambient sites with heavy grouping derating, where the ampacity check starts to matter.
  • Bifacial modules with a materially higher Isc than a comparable monofacial module; check the datasheet figure before reusing a previous design.

The 1500 V option

Configuration B in Table 1 puts all 18 modules in one string: Vmp doubles to 747 V while the current stays at 13.25 A. Because voltage drop is a percentage of a now-doubled voltage, every figure in Table 5 halves and you halve the number of cable runs:

  • 40 m on 4 mm²: 0.92% instead of 1.84%
  • 60 m on 4 mm²: 1.38% instead of 2.76%
  • 80 m on 6 mm²: 1.23% instead of 2.45%
  • 100 m on 10 mm²: 0.88% instead of 1.76%

The constraint is not the cable — H1Z2Z2-K is rated for DC 1,500 V. The constraint is the inverter's maximum DC input voltage and the string Voc corrected to your record low temperature. At 18 modules, a Voc temperature coefficient of −0.25 %/°C and a record low of −10 °C, the correction is 35 K below STC: 891 V × 1.0875 = about 969 V. That is 97% of a 1,000 V inverter's rating, which most designers will not accept; it fits a 1,100 V or 1,500 V inverter comfortably. Colder sites or a worse coefficient push it higher, so run this with your own module data and your own record low before committing to Configuration B.

For NEC projectsThe sizing chain above follows IEC practice. Under NEC 690 the design current is 156% of Isc rather than 125%, and the permitted conductor types are PV Wire (UL 4703) and USE-2 rather than the EN 50618 designation. The arithmetic is identical; the inputs and the cable standard are not. Confirm with a supplier who lists to the relevant UL standard.

08What a percentage point of voltage drop is worth over 25 years

Resistive loss as a fraction of delivered power is exactly ΔV/V — the same number as the voltage drop percentage. So a 1.84% drop is a 1.84% energy loss at the operating point, and the conversion to money is direct.

Assumptions, stated so you can change them: annual yield 15,000 kWh for the 9.9 kWp array, electricity at US$0.10/kWh, 25-year horizon, 5% discount rate. The 25-year annuity factor at 5% is 14.094.

Table 7 — net present value of eliminating voltage drop, by upgrade step
RunUpgradeDrop before → afterEnergy recovered25-year NPV
40 m2.5 → 4 mm²2.97% → 1.84%169 kWh/yrUS$239
40 m4 → 6 mm²1.84% → 1.23%92 kWh/yrUS$130
60 m4 → 6 mm²2.76% → 1.84%138 kWh/yrUS$195
60 m6 → 10 mm²1.84% → 1.06%117 kWh/yrUS$165
80 m6 → 10 mm²2.45% → 1.41%156 kWh/yrUS$220
100 m6 → 10 mm²3.07% → 1.76%195 kWh/yrUS$275

Reproduce any cell: percentage points saved × 15,000 kWh × US$0.10 × 14.094. Example, 40 m 4→6 mm²: 0.615 × 15,000 = 92.3 kWh/yr; × 0.10 = US$9.23/yr; × 14.094 = US$130.

The decision ruleAt these assumptions, one percentage point of voltage drop is worth about US$211 per string pair over 25 years in net present terms — about US$21 for every 0.1 percentage point. That is the number to hold against the quotation: if the upgrade from 4 mm² to 6 mm² on a 40 m run costs less than roughly US$130 in net terms, it pays. At a commercial tariff of US$0.20/kWh, double it.

We are deliberately not publishing cable prices here. Copper moves monthly, and a static price table in an article is wrong within weeks and misleading from the day it is written. Get the delta from a live quotation and compare it against the NPV figure.

RelatedIf the procurement question is bigger than the cross-section — supplier qualification, audit, contract terms — start with the cable supplier audit guide and the solar cable manufacturer shortlist. For what drives the price itself, see solar cable price per metre.

09What this article does not claim

  • The reference system is representative, not universal. Substitute your own Vmp, Imp, Isc and string voltage; the formula is the deliverable, the table is an illustration.
  • The module electrical data is typical of the 550 Wp class. We did not pull it from a specific manufacturer's datasheet, and your datasheet controls.
  • The 3% IEC 62548 figure is graded [B] — a single-source reading. The 1–2% DC practice figure is graded [A].
  • We publish no cable prices, by design. Compare the quoted delta against the NPV in Table 7.
  • This is not a substitute for a stamped design. Where an AHJ, an interconnection agreement or an insurer specifies a limit, that limit wins.

Send us the string layout and we will size it with you

Give us the module datasheet, string configuration, one-way run distances, installation method and ambient temperature range. We will come back with the recommended cross-section, the voltage drop and ampacity workings in a form you can paste into the project file, and a covering quotation for the cable and any factory-terminated harnesses.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Experienced in cable specification aligned with IEC standards.

Sources checked for this article

Related reading

Related product — PV DC string cable
H1Z2Z2-K photovoltaic cable, single core
ConductorFlexible tinned copper, class 5, to EN 60228
Insulation / sheathHalogen-free cross-linked LS0H-XL compound
Rated voltageDC 1.5 kV; AC 1.0/1.0 kV
StandardsEN 50618; IEC 62930 equivalent designation
Temperature range−40 °C to +90 °C; conductor max 120 °C
Ampacity 4 / 6 mm²55 A / 70 A at 60 °C ambient, single cable in air
Max DC resistance 4 / 6 mm²5.09 / 3.39 Ω/km at 20 °C (IEC 60228 class 5)
Sizes1.5 mm² to 240 mm² single core
Values are the type-level ratings published for the EN 50618 designation. Ampacity and resistance figures for the specific construction supplied, together with certificate numbers, come from the project datasheet and control over anything on this page. View the solar cable range.

Scope and limitations

  • Results are calculated for the reference system in Table 1. Substitute your own module and string data before applying them to a project.
  • Conductor resistance uses IEC 60228 class 5 maximum values corrected to a 90 °C conductor. Actual supplied values may be lower.
  • EN 50618 ampacity figures are manufacturer reproductions of the standard's table at 60 °C ambient and 120 °C conductor. Grouping, conduit and burial derating must be applied separately per IEC 60364-5-52.
  • No cable pricing is published. Compare a live quotation against the net present values in Table 7.
  • This is engineering information, not a stamped design and not legal or compliance advice.

FAQ

What size cable do I need for a 10kW solar system?

For a typical 10 kW array of 18 × 550 Wp in two strings of nine (373.5 V, 13.25 A per string), 4 mm² keeps voltage drop under 2% out to about 43 m, and 6 mm² out to about 65 m. Beyond 70 m, use 10 mm². Ampacity is rarely the binding constraint on PV DC circuits — voltage drop is.

4mm or 6mm solar cable — which should I use?

Use 4 mm² for runs up to roughly 40–45 m and 6 mm² from 45 m to about 70 m, assuming a two-string 10 kW array at 13.25 A. On a 40 m run the difference is 1.84% versus 1.23% voltage drop, which at 15,000 kWh/year and US$0.10/kWh is worth about US$130 over 25 years in present-value terms.

How much voltage drop is acceptable on a solar DC cable?

IEC 60364-7-712 does not specify a percentage. Common DC design practice is 1–2%; IEC 62548 is read as a 3% combined DC limit; NEC treats 2% on the source circuit and 1% on the output circuit as informational. Where nothing is specified, 2% on the DC side is a defensible default.

How far can I run 4mm solar cable?

On a 10 kW array at 13.25 A per string with a 373.5 V string voltage, 4 mm² reaches a 2% voltage drop at about 43 m one way and 3% at about 65 m, using IEC 60228 class 5 resistance corrected to 90 °C. Halve those percentages — and double the allowable distance — if you configure the array as a single 18-module string at 747 V.

Do I need 10mm² cable for a 10kW system?

Usually not for the string runs. 10 mm² becomes appropriate beyond about 70–80 m, on combiner-box output circuits carrying summed string current, or where grouping derating in a hot climate brings the ampacity check into play. For most residential 10 kW arrays at 20–40 m, 4 mm² or 6 mm² is correct.

Does ampacity or voltage drop decide PV cable size?

Voltage drop, in almost every case. A 4 mm² EN 50618 cable is rated 55 A at 60 °C ambient, derating to 39 A at 90 °C and 31 A for two cables touching on a surface — all comfortably above the 17.5 A IEC or 21.8 A NEC design current for a single 13.25 A string. Ampacity only becomes binding on long bundled runs or aggregated combiner outputs.