H1Z2Z2-K vs. PV1-F: Which Solar Cable Standard Should Your Project Specify?

A clear, practical breakdown of the two most common solar cable standards—EN 50618 (H1Z2Z2-K) and TÜV 2PfG 1169 (PV1-F)—and how to choose the right one for your market, voltage class, and installation environment.

📅 Updated July 2026 📖 15 min read 🏷️ H1Z2Z2-K, PV1-F, EN 50618, TÜV 2PfG 1169, Solar Cable

1. Introduction: The Solar Cable Alphabet Soup

If you've ever looked at a spool of solar cable and wondered what "H1Z2Z2-K" or "PV1-F" actually means, you're not alone. These designations aren't brand names—they're code that describes the cable's construction, voltage rating, and applicable standard. And the difference between them matters a lot more than most buyers realize.

Here's the short version: H1Z2Z2-K (EN 50618) is the current, modern standard. PV1-F (TÜV 2PfG 1169) is the previous generation. For any new installation, especially if it's a 1500V DC system, H1Z2Z2-K is the appropriate choice. But the market is still full of PV1-F cables, and many buyers—particularly in price-sensitive markets—continue to specify them for projects where the voltage and environment would be better served by the newer standard.

The thing is, the cost difference per meter between the two is usually small. What's large is the difference in voltage rating, water ingress protection, and the scope of certified cross-sections. So let's walk through what each standard actually requires, where they diverge, and how to make a specification decision you won't second-guess in year 15 of a 25-year system life.

2. Decoding the Cable Designation

Type designations aren't random. Each letter and number tells you something specific:

H1Z2Z2-K:

  • H — Harmonized type (CENELEC)
  • 1 — Voltage class: 1.5 kV DC nominal
  • Z2 — Insulation: cross-linked polyolefin (XLPO), halogen-free
  • Z2 — Sheath: cross-linked polyolefin (XLPO), halogen-free
  • K — Flexible conductor (IEC 60228 Class 5)

PV1-F:

  • PV — Photovoltaic application
  • 1 — Voltage class: historically 1.0 kV DC nominal
  • F — Flexible conductor

The PV1-F designation, unlike H1Z2Z2-K, doesn't encode the insulation and sheath material in the name itself. Those are defined by the manufacturer's specification under the TÜV 2PfG 1169 certificate.

3. The Two Standards: Where They Come From

TÜV 2PfG 1169/08.2007 was developed by TÜV Rheinland in the mid-2000s as a certification specification for cables used in photovoltaic systems. At the time, there was no European harmonized standard specifically for solar cables—installers were using generic rubber or PVC cables that degraded quickly under UV exposure. 2PfG 1169 filled that gap and served the industry well for over a decade.

EN 50618:2014 was developed by CENELEC (the European Committee for Electrotechnical Standardization) as the first Europe-wide harmonized standard for photovoltaic cables. It was designed to supersede the various national and third-party specifications—including 2PfG 1169—and to raise the testing bar in several important areas. It's since been adopted across the EU, and many non-European markets also reference it in their national codes.

⚠️ Important Distinction

TÜV 2PfG 1169 is a certification specification issued by a third-party testing body. EN 50618 is a European harmonized standard adopted by CENELEC member countries. Under the EU's Construction Products Regulation (CPR), EN 50618 carries legal weight for compliance; 2PfG 1169 does not.

4. Head-to-Head: Key Technical Differences

ParameterPV1-F (TÜV 2PfG 1169)H1Z2Z2-K (EN 50618)
Nominal DC voltage1.0 kV (max 1.8 kV system voltage)1.5 kV (max 1.8 kV system voltage)
AC voltage rating0.6/1.0 kV1.0/1.0 kV
ConductorClass 5, tinned copper (mandatory per 2PfG 1169)Class 5, tinned copper (mandatory per EN 50618)
Insulation materialXLPO, single or double layerXLPO, double layer (thicker wall)
Cross-section range1.5 – 35 mm²1.5 – 240 mm²
Ambient temp range (fixed install)–40°C to +90°C–40°C to +90°C
Max conductor temp (continuous)120°C120°C
Short-circuit temp200°C (5 sec)250°C (5 sec)
Water immersion ratingAD7 (occasional submersion)AD8 (permanent submersion)
UV test durationPer HD 605/A1Per EN 50618 Annex E
Ozone resistance testEN 50396 Method BEN 60811-403 / EN 50396
Halogen-freeYesYes
Flame retardancyIEC 60332-1-2 + IEC 61034IEC 60332-1-2 + IEC 61034 (stricter criteria)
Min bending radius4× / 5× cable OD4× / 5× cable OD
Design life25 years25 years
Standard statusLegacy (being phased out)Current (active)

* Some manufacturers offer PV1-F cables up to 50 mm² or larger under extended certification. The 35 mm² limit reflects the original 2PfG 1169 specification scope.

5. Testing Deep Dive: What EN 50618 Adds

In my view, the real story is in the testing regime. Both cables will work for basic solar applications. Where EN 50618 raises the bar is in how it tests—the methodology is more clearly defined and the pass criteria are more stringent in several areas.

Ozone Resistance (EN 60811-403)

Ozone is present in the upper atmosphere and around electrical equipment. It attacks unstabilized rubber and polyolefin compounds, causing surface cracking that deepens under mechanical stress. Both standards require ozone resistance testing—EN 50618 via EN 60811-403 and 2PfG 1169 via EN 50396 Method B (typically 250 pphm at 40°C for 72 hours). The test methods differ slightly, but both are designed to prevent surface cracking in ozone-rich environments. For rooftop installations in high-UV areas—where ozone concentrations are naturally elevated—this is a meaningful requirement regardless of which standard you specify.

Thermal Endurance (EN 60216)

Both standards claim a 25-year design life, but EN 50618 requires it to be verified through Arrhenius-style accelerated thermal aging per EN 60216. The cable must demonstrate that its insulation and sheath retain sufficient mechanical properties after aging at multiple temperature points, with the results extrapolated to a 25-year service temperature index. A PV1-F cable might deliver the same field life—but it hasn't been tested to prove it in the same way.

Water Immersion — AD8 vs AD7

The immersion rating difference deserves attention. AD7 means the cable can withstand temporary submersion (think heavy rain or shallow puddles). AD8 means it can handle permanent submersion—relevant for floating solar, cable runs in water-filled trenches, or high-humidity tunnel environments. For a standard rooftop installation, AD7 is probably sufficient. For a ground-mount system where cables enter the soil, or for any floating solar application, AD8 is the safer choice.

💡 Practical Takeaway

If your project lives in a moderate climate, has good cable management, and operates at 1000V DC or below, PV1-F cables from reputable manufacturers will perform adequately. But if any of the following apply—1500V DC system, desert or tropical climate, floating PV, direct burial, or export to a market that enforces EN 50618—specifying H1Z2Z2-K removes uncertainty and ensures code compliance.

6. Market Acceptance: Which Standard Where?

Market / RegionDominant StandardNotes
European UnionEN 50618Harmonized under CPR. Mandatory for CE marking of PV cables.
United KingdomEN 50618BS EN 50618, retained after Brexit. BS 7671 references it.
Middle East / AfricaBoth (EN 50618 preferred)High-UV/desert specs often require EN 50618 UV+ozone performance.
Southeast AsiaBoth (PV1-F common)Price sensitivity favors PV1-F, but large IPP projects specify H1Z2Z2-K.
AustraliaEN 50618AS/NZS references EN 50618 for new installations.
North AmericaUL 4703 (separate)Neither EN 50618 nor 2PfG 1169 is recognized; UL 4703 applies.
IndiaBoth (transitioning)MNRE guidelines increasingly favor EN 50618 for large-scale projects.

7. The Cost Question

Here's what I've seen across hundreds of procurement RFQs: the price gap between a certified H1Z2Z2-K cable and a comparable PV1-F cable from the same manufacturer is typically $0.02–$0.08 per meter for common sizes (4–6 mm²). For a 500 kW ground-mount system requiring roughly 8,000–10,000 meters of DC cable, that's a total difference of about $200–$800—essentially negligible in the context of the total project cost.

Where the difference isn't negligible is in the cross-section range. PV1-F is generally certified only up to 35 mm². For utility-scale solar farms where DC cable runs use 50–150 mm², H1Z2Z2-K is the only option—not because of preference, but because the certification doesn't exist for PV1-F at those sizes.

Cost FactorPV1-F (Legacy)H1Z2Z2-K (Modern)
Material cost per meter (4 mm²)Baseline~$0.02–$0.08 more
Material cost per meter (10 mm²)Baseline~$0.05–$0.15 more
Available up to35 mm²240 mm²
Certification validityBeing phased outCurrent, fully recognized
Risk of future non-complianceIncreases over timeNegligible

8. SORIVO's Approach: Dual-Certified, One Less Headache

At Sorivo, we took the view early on that asking customers to choose between standards wasn't doing anyone any favors. Our solar cables are dual-certified to both EN 50618 and TÜV 2PfG 1169 (depending on size and product variant), which means:

  • You don't need to match cable certification to a specific project market. The same cable works for EU, UK, Middle East, and Asian projects.
  • Our H1Z2Z2-K cables use Class 5 tinned copper conductors per EN 50618, with double-layer XLPO insulation and sheath. They carry the same cross-section range as the standard allows—from 1.5 mm² up to 240 mm².
  • Each production batch is third-party tested to the applicable standard. Test reports are available on request with the batch number.
  • For customers who still need PV1-F for legacy system repairs or replacement, we maintain that certification as well—so you're not forced to upgrade your entire stock if you're maintaining an existing installation.

✅ The Practical Benefit

One cable, two certifications. You buy it once, stock it in your warehouse, and it covers 90% of the solar projects that come through your door. No second-guessing which standard applies to which market.

Our dual-certified solar cable range includes:

9. Field Identification: How to Tell H1Z2Z2-K from PV1-F

If you're looking at a cable on site and need to confirm which standard it's certified to, here are the quick checks:

Read the cable markings. A certified cable will have its type designation printed along the sheath every meter or so. If it says "H1Z2Z2-K," it's EN 50618. If it says "PV1-F," it's TÜV 2PfG 1169. If it doesn't say either—walk away.

Check the test voltage on the print line. EN 50618 cables are marked with 1.5 kV DC or 1.8 kV DC. PV1-F cables will show 1.0 kV DC or 0.6/1.0 kV AC.

Look for the certification mark. A genuine TÜV-certified PV1-F cable will carry the TÜV Rheinland logo and certificate number on the sheath. An EN 50618 cable may carry a mark from a notified body or the manufacturer's declaration of conformity to the harmonized standard.

⚠️ What About "PV1-F 1.5 kV" Markings?

Some cables on the market are marked "PV1-F" but rated 1.5 kV DC. These are non-standard hybrid products that don't conform to the original 2PfG 1169 specification (which caps nominal DC voltage at 1.0 kV). They may work, but the certification basis is unclear. For a project where compliance matters, stick to clearly designated H1Z2Z2-K for 1.5 kV systems.

10. Choosing the Right Standard: A Decision Guide

If your project is...Specify...Why
A new residential or commercial installationH1Z2Z2-KFuture-proof. Covers 1500V systems. Code-compliant in all EU/UK/AU markets.
A utility-scale solar farmH1Z2Z2-KOnly option at cross-sections above 35 mm². Required for 1500V DC.
A floating solar PV systemH1Z2Z2-KAD8 permanent immersion rating is the right specification for this environment.
Repair or replacement on an existing PV1-F systemPV1-FMatching the existing standard avoids warranty complications. Keep H1Z2Z2-K in mind for future replacements.
A small off-grid system (12V/48V DC)EitherVoltage is low enough that both standards work. Choose by availability and price.
Export to a market with unclear regulatory requirementsH1Z2Z2-KEN 50618 is the most widely recognized solar cable standard internationally.

11. Frequently Asked Questions

Can I use H1Z2Z2-K cable on a 1000V DC system, or is it oversized?
Yes, you can. Using a cable rated for a higher voltage than the system requires is always safe—the limitation runs the other direction. H1Z2Z2-K on a 1000V system provides additional safety margin, and the cost difference is minimal. Many installers standardize on H1Z2Z2-K across all their projects for inventory simplicity.
Does EN 50618 require the cable to be halogen-free?
Yes, it does. EN 50618 mandates zero halogen per IEC 60754-1/2 (acid gas content below 0.5% HCl) and smoke density per IEC 61034-2 (minimum 60% light transmittance). TÜV 2PfG 1169 also requires halogen-free construction for certified cables, so this is one area where the two standards agree.
Is PV1-F still being certified for new products?
As of 2025–2026, TÜV Rheinland still offers 2PfG 1169 certification, but the industry is clearly moving toward EN 50618 as the baseline. Most major manufacturers now list H1Z2Z2-K as their primary offering and PV1-F as a secondary or legacy option. If you're developing a new product or project specification, I'd recommend building it around EN 50618.
What about IEC 62930—where does that fit?
IEC 62930 was developed as an international standard for solar cables, parallel to EN 50618. It's largely harmonized with EN 50618 but offers an optional halogen-free path (IEC 60754-1/2 for zero halogen, or an alternate path for cables that don't need to be halogen-free). In practice, most buyers who reference IEC 62930 also accept EN 50618 as equivalent. If you're working in a market that follows IEC rather than EN, IEC 62930 is the standard to reference—but an EN 50618 cable will typically meet its requirements.
Does Sorivo offer dual-certified H1Z2Z2-K + PV1-F cables?
Yes. Our solar cables carry both EN 50618 and TÜV 2PfG 1169 certifications on selected sizes. Contact us with your project requirements and we'll confirm certification coverage for your specific cable size and quantity. Our product pages also list the certifications held by each cable variant.

12. Conclusion: The Standard You Choose Shapes Your Project's Risk Profile

To be honest, neither standard is bad. PV1-F served the solar industry well for over a decade and continues to be specified in many markets. But standards evolve for a reason. EN 50618 was developed to address failure modes—ozone cracking, long-term thermal degradation, water ingress—that the earlier specification didn't fully cover, and the industry's experience since 2014 has confirmed those gaps were real.

If you're procuring cable for a new installation today, especially one that will operate for 25 years, H1Z2Z2-K is the standard I'd recommend. The cost premium is small, the certification is current, and the testing is more comprehensive. For legacy system repairs, PV1-F remains a valid choice. But for anything new—H1Z2Z2-K removes questions before they get asked.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Member of IEC TC 20 (Power Cables). Previously contributed to cable selection for 500MW+ solar PV and BESS projects across Asia, Europe, and the Middle East.

Need dual-certified solar cable for your next project?

Our engineering team can help you select the right cable standard, cross-section, and certification for your market. Request a quote or specification sheet.

📧 sale@sorivocable.com 📞 +86 19282905529