Professional cable manufacturer
Flexible tinned-copper DC cable for battery racks, battery containers and PCS connections in utility, C&I and residential BESS projects.

Everything a project engineer checks first — before diving into the full datasheet below.
The 1500V ESS Energy Storage System Cable is designed for electrical power connections in battery energy storage systems (BESS) — battery racks, battery containers and power conversion system (PCS) connections. The cable is based on the TÜV 2 PfG 2693 requirements for electric cables connected to battery energy storage systems.
Tinned copper Class 5 flexible stranded conductors combined with XLPO insulation provide the flexibility required for battery and power-electronics connections, while supporting conductor temperatures up to +125°C for the specified cable design.
For BESS environments, the cable can be supplied with halogen-free, low-smoke and chemically resistant LSZH construction. Depending on the selected construction and certification scope, environmental performance can include resistance to battery-related chemicals, oil and outdoor exposure.
Compared with conventional photovoltaic cables, an ESS cable is selected around battery-system requirements: thermal conditions, flexible routing, battery-environment exposure and high-voltage DC transmission. SORIVO supplies different cross-sections, colors and configurations for residential, commercial and utility-scale BESS projects.
More about the manufacturer: About SORIVO →
Designed around the TÜV 2 PfG 2693 requirements specifically developed for cables connected to battery energy storage systems.
Up to 1500V DC rating supports high-voltage BESS architectures and modern battery energy storage power connections.
Class 5 flexible stranded tinned copper provides flexibility for battery-rack routing and connection work while improving corrosion resistance.
The specified XLPO construction supports a maximum conductor operating temperature of up to +125°C.
Cross-linked polyolefin insulation provides the thermal and electrical performance required for high-voltage DC energy storage connections.
Low-smoke, halogen-free and chemical-resistant constructions are available where required by the project specification and certification scope.
Available sizes from 2.5mm² to 95mm² support different BESS connection and power-distribution requirements.
Suitable for battery racks, battery containers, PCS connections and other energy-storage power connections, subject to final system design.
From utility-scale containers to residential battery walls — same construction philosophy, project-specific certification scope.
Rack and container interconnections in grid-scale battery storage plants.
Battery-to-PCS and DC distribution wiring for C&I storage cabinets.
Wall-mounted battery systems and hybrid inverter DC connections.
Flexible routing inside racks and containers, tight bends and cabinet entry.
High-current DC links between battery banks and power conversion systems.
DC cabling for hybrid PV plants where storage and generation share infrastructure.
Buffered DC bus cabling in charging stations with integrated battery storage.
Off-grid storage, industrial battery banks and UPS backup power circuits.
The complete parameter set — the same data our engineers quote from.
| General Information | |
| Product Name | 1500V ESS Energy Storage System Cable |
| Primary ESS Standard | TÜV 2 PfG 2693 — Requirements for Electric Cables Connected to Battery Energy Storage System |
| Rated Voltage | Up to 1500V DC |
| Cable Structure | Single-core cable; multi-core configurations available according to project requirements |
| Conductor | |
| Conductor Material | Tinned copper, providing corrosion resistance and suitable flexibility for BESS connections |
| Conductor Type | Class 5 flexible stranded conductor, according to applicable EN/IEC 60228 requirements |
| Cross Sections | 2.5mm², 4mm², 6mm², 10mm², 16mm², 25mm², 35mm², 50mm², 70mm², 95mm² |
| DC Resistance at 20°C | According to the applicable conductor standard and specific cable cross-section |
| Insulation & Sheath | |
| Insulation Material | XLPO (cross-linked polyolefin) |
| Sheath / Jacket | LSZH construction, with oil and chemical resistance according to the applicable cable construction and test scope |
| Jacket Colors | Black standard / Orange / Custom colors available |
| Halogen-Free | Available with halogen-free construction according to the applicable test requirements |
| Low Smoke | Available with low-smoke construction according to the applicable test requirements |
| UV Resistance | Available according to the specified cable construction and applicable certification scope |
| Electrical Ratings | |
| Rated Voltage (DC) | Up to 1500V DC |
| Finished Cable Voltage Test | For 1500V DC cable construction: 6.8 kV AC / 5 min, no breakdown, according to 2 PfG 2693/03.23 requirements |
| Long-Term DC Withstand Test | For 1500V DC cable construction: 1.5 kV applied for 240 h, no breakdown, according to 2 PfG 2693/03.23 requirements |
| AC Voltage Rating | Not specified in this product summary; confirm the applicable AC rating from the exact cable construction and certification |
| Temperature & Environmental | |
| Temperature Rating | Down to −40°C; maximum conductor operating temperature up to +125°C for the specified XLPO construction |
| Maximum Conductor Temperature | +125°C |
| Battery Acid Resistance | Suitable for BESS environments where the specified cable construction meets the applicable chemical-resistance requirements |
| Oil / Chemical Resistance | Available according to the tested cable compound and certification scope |
| Flame Performance | IEC 60332-1-2 or other applicable flame-performance requirements according to the certified construction |
| Minimum Bend Radius | According to cable construction and installation requirements; please confirm the value for the selected cable size |
| Packaging & Logistics | |
| Packaging | Wooden drum / coil / reel / custom packaging per request |
| Standard Length | 100m / 200m / 500m / 1000m per roll, customizable |
| MOQ | 1,000 meters; sample orders negotiable |
| Lead Time | 10–20 working days; stocked sizes may be available sooner |
Final cable selection should be based on system voltage, continuous current, short-circuit conditions, installation method and applicable local requirements. Our engineers confirm the exact construction and certification scope with your project data.
Requirements for electric cables connected to battery energy storage systems — the dedicated BESS cable specification this product is designed around. Certificate scan available on request.
Request certificate copy →Flexible stranded conductor class per the applicable EN/IEC 60228 requirements — verified for every production batch.
Request test report →Flame performance per IEC 60332-1-2 or other applicable requirements according to the certified construction.
Request test report →
Every drum of ESS cable is produced under controlled processes and released against the applicable standard requirements.
Tell us cross-section, color, quantity and destination market.
We confirm construction, certification scope and quotation within one working day.
Sample for qualification — stocked sizes within a few working days.
10–20 working days lead time with batch test documentation.
Wooden drum packing, shipping documents and after-sales support.