35 kV Collector Circuits: How MV Cable Selection Actually Works

A medium voltage collector circuit is specified by its voltage basis before anything else: a 6/10 kV cable has a maximum system voltage Um of 12 kV, not 10 kV, and IEC 60502-2 fixes the insulation thickness at 3.4 mm at that rating across every conductor size from 16 to 1000 mm². This article walks the selection chain a utility-scale wind or solar plant actually goes through — voltage basis, insulation and screen, screen bonding, burial and ampacity — and where UL Type MV-105 and the ICEA family diverge from the IEC system.

Published 2026-09-28Updated 2026-09-28 Reading ~19 minLevel: Intermediate

01What a collector circuit is, and why it is specified differently

The short answer

A collector circuit is the MV network that gathers power from many distributed sources — PV inverters, wind turbine generators, or battery containers — and delivers it to a step-up transformer or substation bus. On a utility-scale site it normally runs at 33 kV or 35 kV nominal, which sits inside the NEC Type MV definition (2001 V to 35,000 V). The IEC side needs a qualification: a 33 kV system, whose equipment maximum voltage Um is 36 kV, sits at the top of the IEC 60502-2 range; a system specified at 35 kV nominal has Um = 40.5 kV per GB/T 156, which is above the 36 kV ceiling of IEC 60502-2 and falls under IEC 60840 instead. The distinction matters because it decides which standard the insulation thickness, test voltage and screen construction are read from. The reason selection is harder here than on a feeder is that the cable must satisfy four constraints at once: the insulation level, the metallic screen's earth-fault duty, the ampacity of a route that may be kilometres long, and a bonding scheme that decides how much of that ampacity survives.

Utility-scale generation is built as a hierarchy of voltages, and the collector circuit occupies the middle rung. At the bottom, PV strings run at up to 1,500 V DC and turbines generate at roughly 690 V to 1 kV. At the top, the point of interconnection may be 110 kV, 220 kV or higher. Between them sits the collector system, typically 33 kV or 35 kV, whose job is to aggregate tens or hundreds of megawatts across a site that can be several square kilometres in extent.

That geography is what makes the collector circuit a cable problem rather than a switchgear problem. There is one substation and many generators, so the cable route length is set by the site layout, and the route length is what drives the screen bonding decision, the induced screen voltage, and how much of the standard ampacity table you can actually use.

Three source types on one network

A hybrid or combined site may have all three of the following collector branches, and they behave differently under fault:

  • PV inverter branches — current-limited by the inverter's own rating, so the MV cable's earth-fault current is largely set by the inverter contribution and the transformer impedance.
  • Wind turbine branches — each turbine is an induction or doubly-fed machine with its own reactive behaviour, and the collector cable may also have to carry the reactive current the turbines exchange with the grid.
  • Battery storage branches — a storage unit can deliver fault current from both the battery and the power conversion system, and it can also be a source when the rest of the site is de-energised.

For cable selection, what matters is that the earth-fault current and its clearing time are not the same on all three branches, and the metallic screen is sized for that current. A screen sized for an inverter-limited branch may be undersized for a storage branch on the same network.

Where the collector circuit sits between two standards worlds

This is the structural fact that shapes every MV procurement decision, so it is worth stating plainly. A 35 kV collector circuit can be built to one of two parallel standards families, and they are not interchangeable:

  • The IEC system — IEC 60502-2 defines the cable itself for rated voltages from 6 kV (Um = 7.2 kV) up to 30 kV (Um = 36 kV), covering construction, dimensions and test requirements for extruded solid insulation in fixed installations. Above that ceiling the same family continues in IEC 60840, which covers rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV).
  • The North American system — Type MV cable is defined in NEC 311.2 as solid dielectric insulated cable rated 2001 V up to and including 35,000 V nominal, and a North American MV catalogue typically names UL 1072 for the Type MV designation alongside ICEA S-93-639 / NEMA WC 74 and AEIC CS8, which set the insulation thicknesses and test voltages.

The two families use different rated temperatures, different insulation thickness tables and different test voltages for what a buyer may reasonably think is the same cable. On a given project the governing one is decided by the site's wiring regulations and by the specifications of the equipment the cable terminates into — not by preference. Our own medium voltage armoured power cable page is explicit that the ICEA and AEIC values are named for identification only and are not used or implied in the IEC construction we publish there.

02The voltage basis: U0, U and Um are three different numbers

If there is one error that propagates through an entire MV enquiry, it is collapsing the voltage rating into a single figure. A "10 kV" cable does not exist as a procurement item. What exists is a cable rated 6/10 kV, whose maximum system voltage Um is 12 kV.

The three symbols mean this:

  • U0 — the rated power-frequency voltage between conductor and earth, or between conductor and metallic screen.
  • U — the rated power-frequency voltage between conductors.
  • Um — the maximum value of the highest system voltage for which the cable is designed to operate in service.

IEC 60502-2 works in five standard ratings, and each has its own Um and its own specified AC test voltage. Writing them as a single "6–30 kV" range is how the wrong insulation thickness and the wrong routine test value end up on a purchase order.

Table 1 — The five IEC 60502-2 voltage ratings, with Um and specified AC test voltage
U0/U ratingUm (max. system voltage)AC test voltage, rmsTypical collector-circuit use
3.6/6 kV7.2 kV12.5 kVShort in-plant runs, small distributed generation, auxiliary supplies
6/10 kV12 kV21 kVSmaller collector systems and industrial distribution; the common industrial rating
8.7/15 kV17.5 kV30.5 kVWhere earth-fault clearing is slower or the neutral is impedance-earthed
12/20 kV24 kV42 kVMedium collector networks and larger industrial feeds
18/30 kV36 kV63 kV33 kV collector circuits (Um = 36 kV); the top of the IEC 60502-2 range

Ratings, Um values and AC test voltages as published on our medium voltage armoured power cable page for the IEC 60502-2 construction. The AC test voltage column is the value specified by IEC 60502-2 for that rating — a standardised test value, not a service voltage and not a description of any manufacturer's in-house routine.

The practical consequence runs like this. A 33 kV collector network usually sits under the 18/30 kV rating, because its Um of 36 kV covers the system. A collector network specified at 35 kV nominal does not: its equipment maximum voltage is 40.5 kV, so it is above the 36 kV ceiling of IEC 60502-2 and its cable is procured against IEC 60840, which covers rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV). On the North American side the type MV definition tops out at 35,000 V nominal, so the number that governs on a North American project is the nominal one, and on an IEC project it is Um. Same physical system, two different numbers being checked — and on the IEC side, a standard boundary that a 35 kV designation crosses.

The most common addressable error in an MV enquiryQuoting a cable by "10 kV" instead of "6/10 kV", or by "35 kV" instead of the rating that actually covers the system voltage. Within the IEC 60502-2 range Um is higher than U at every rating: 6/10 kV gives 12 kV, 8.7/15 kV gives 17.5 kV, 12/20 kV gives 24 kV, 18/30 kV gives 36 kV. If a datasheet or a purchase order carries only one voltage figure for an MV cable, that document is incomplete.
What this changes on the enquiryOnce the U0/U rating is fixed, insulation thickness and the routine test value are fixed with it — they are no longer variables you negotiate. What remains a real choice is the screen and armour system, which is where the rest of this article goes. Send us the system voltage and the earthing arrangement and we will confirm the rating on paper.

03Construction: what is fixed by the rating and what you choose

An MV cable is a layered dielectric system, not a conductor with more rubber on it. The construction chain is the same at every rating, but the responsibilities change at each layer.

  • Conductor — annealed copper to IEC 60228 Class 1 (solid) or Class 2 (stranded), sized for both the continuous load and the conductor short-circuit duty.
  • Conductor screen — an extruded semiconductive non-metallic layer bonded to the insulation, whose purpose is to eliminate voids at the conductor surface.
  • Insulation — XLPE as standard, with EPR/HEPR available; thickness set by the voltage rating.
  • Insulation screen — a second extruded semiconductive layer over the insulation, bonded or strippable.
  • Metallic screen — copper wire (CWS) or copper tape (CTS), sized for the earth-fault current and its duration.
  • Bedding or separation sheath — extruded layer under the armour.
  • Armour — aluminium wire (AWA) or steel tape (STA), where mechanical protection is required.
  • Oversheath — PVC, LSZH or PE depending on the environment and the fire requirement.

The two semiconductive layers are the reason an MV cable cannot be jointed like a low voltage one. The conductor screen and the insulation screen are what hold the electric field inside the insulation; a void or a protrusion at either interface becomes a site of partial discharge, and partial discharge is what eventually fails the cable. This is also why the finishing of the screen at a termination is an accessory-engineering question rather than a cable question — our cold-shrink termination and joint range for 10 kV to 35 kV exists for exactly that step.

CROSS-SECTION inside → out, top to bottom Cu 1 2 3 4 5 6 7 8 LAYER WHO DECIDES IT VALUE 1 · Conductor IEC 60228 Class 1/2 standard 2 · Conductor screen always present rating > 2 kV 3 · Insulation fixed by rating 2.5–8.0 mm 4 · Insulation screen bonded or strippable accessory 5 · Metallic screen sized by project CWS or CTS 6 · Bedding / separation sheath formula-based 0.02·Du+0.6 7 · Armour mechanical duty AWA or STA 8 · Oversheath environment PVC / LSZH / PE READING THE FIGURE Shaded rows are the two the project actually decides. Layers run inside-out.
Eight layers, and only two of them are actually open to choice. The conductor and its two semiconductive screens are dictated by the standard and by the fact that the cable operates above 2 kV. The insulation thickness is fixed by the voltage rating — the same 3.4 mm at 6/10 kV whether the conductor is 16 mm² or 1000 mm², and 3.4 mm does not vary with conductor size from 6/10 kV upwards. Only the lowest rating behaves differently: at 3.6/6 kV the thickness is 2.5 mm on small conductors and 3.2 mm at the top of the size range, which is why the figure spans 2.5 mm to 8.0 mm. What the project actually decides is the metallic screen (sized to its own earth-fault current and clearing time) and the mechanical layers above it: bedding, armour and oversheath, chosen against the installation conditions.

Insulation thickness is fixed by the rating, not by the conductor size

The single most useful dimensional fact in the whole IEC 60502-2 system is this: from 6/10 kV upwards, the nominal insulation thickness is determined by the rating and does not change with conductor size. Only the 3.6/6 kV rating moves with the conductor.

Table 2 — Nominal insulation thickness by voltage rating (XLPE or EPR/HEPR)
Conductor size3.6/6 kV6/10 kV8.7/15 kV12/20 kV18/30 kV
16–185 mm²2.5 mm3.4 mm4.5 mm5.5 mm8.0 mm
240 mm²2.6 mm3.4 mm4.5 mm5.5 mm8.0 mm
300 mm²2.8 mm3.4 mm4.5 mm5.5 mm8.0 mm
400–630 mm²3.0–3.2 mm3.4 mm4.5 mm5.5 mm8.0 mm

Reference construction values published on our IEC 60502-2 medium voltage armoured power cable page, cross-checked against the dimensional data of the individual voltage ratings of a European MV cable range held in our library (240 mm² single-core: 2.6 mm at 3.6/6 kV, 3.4 mm at 6/10 kV, 4.5 mm at 8.7/15 kV, 5.5 mm at 12/20 kV, 8.0 mm at 18/30 kV). Sizes below 16 mm² and the 800–1000 mm² range are quoted per rating. The thickness applied to a specific order is confirmed on the drawing.

Read across the 6/10 kV column: 3.4 mm at 16 mm² and 3.4 mm at 1000 mm². The thickness is not a function of how much copper is in the conductor. It is a function of how much voltage the dielectric has to withstand, which is set by the rating alone. A buyer who asks for "thicker insulation for the bigger cable" is asking for something the standard does not provide, and a supplier who quotes it is quoting outside the standard.

04The metallic screen: the layer that decides the procurement

The metallic screen is where MV cable selection actually gets decided, because it is the one layer whose duty is set by the project's own fault study rather than by the voltage rating.

The NEC states the purpose of shielding directly. Under 311.44, nonshielded ozone-resistant insulated conductors with a maximum phase-to-phase voltage of 5000 V are permitted in Type MC cables in industrial establishments where maintenance and supervision ensure that only qualified persons service the installation; for other establishments, solid dielectric insulated conductors operated above 2000 V in permanent installations must have ozone-resistant insulation and must be shielded, and all metallic insulation shields must be connected to a grounding electrode conductor, a grounding busbar, an equipment grounding conductor, or a grounding electrode. Two exceptions carve out narrower cases — nonshielded conductors listed for use up to 2400 V under stated conditions, and airfield lighting cable in series circuits rated up to 5000 V. The code's own informational note lists what the shield is for: confining the voltage stresses to the insulation, dissipating insulation leakage current, draining off the capacitive charging current, and carrying ground-fault current so that ground-fault protective devices operate in the event of a cable fault.

That last function is the sizing criterion. The screen is a fault-current path, and it is a much smaller conductor than the phase conductor it sits around.

Copper wire and copper tape are not equivalent at the same nominal size

Both screen types are standard, and both are described by a nominal cross-section in square millimetres. Those two numbers do not produce the same short-circuit performance, because a tape screen and a wire screen of equal nominal area do not have equal effective cross-section once the tape's overlap and the wire's lay are accounted for.

Table 3 — Metallic screen types and their short-circuit duty
Screen typeReference cross-sectionShort-circuit capacity, 1 sWhere it fits
CWS — copper wire screen16 mm²1.96 kAHigher earth-fault duty; the default where fault current is significant
CWS — copper wire screen25 mm²3.06 kALarger conductor sizes and higher fault levels
CWS — copper wire screen35 mm²4.29 kA400–630 mm² conductor sizes
CWS — copper wire screen50 mm²6.13 kA800–1000 mm² conductor sizes
CTS — copper tape screen16 mm² at 6/10 kVabout 0.86 kALower fault duty, and where a compact screen is preferred

Values for the reference construction as published on our medium voltage armoured power cable page. The copper wire screen cross-section is graded by conductor size — 16 mm² for 16–120 mm², 25 mm² for 150–300 mm², 35 mm² for 400–630 mm², 50 mm² for 800–1000 mm² — and that grading does not change between the five voltage ratings. The CTS figure is quoted for the 6/10 kV rating with a 16 mm² tape; tape cross-section is derived from the construction and rises with conductor size. Screen selection must be made against the earth-fault current and its clearing time for the actual installation.

Look at the first and last rows: 1.96 kA against roughly 0.86 kA for the same 16 mm² nominal figure. That is a factor of well over two, and it is the reason a specification that says "16 mm² copper screen" without stating wire or tape has not actually specified the screen at all.

Why this decides the orderA screen undersized for the earth-fault duty will not fail on the day the cable is energised. It fails the first time a fault has to be cleared through it, and by then the joint or termination is being replaced on an outage the plant cannot afford. Sizing the screen needs two inputs from the fault study: the earth-fault current, and the time protection takes to clear it. Both are project-specific, and neither is in the standard.

Armour is a mechanical choice with an electrical consequence

Armour exists to protect the cable from mechanical damage — the load of backfill, a dig-in, a rodent, the pull load during installation. Two forms dominate MV work:

  • AWA — round aluminium wire armour, applied helically over the extruded separation sheath. Non-magnetic, so it does not introduce the eddy-current and hysteresis losses a steel armour would in a single-core AC circuit, and it is the usual choice for single-core MV cable.
  • STA — steel tape armour, generally on multicore constructions where the magnetic circuit is balanced around all phases and the tape's mechanical protection per unit cost is higher.

The electrical consequence is that armour is a conductive part, and therefore has a bonding requirement of its own, which the NEC states plainly in 311.36: the metallic shield, sheath or armour must be connected to a grounding electrode conductor, a grounding busbar, or a grounding electrode. The same article's 311.44 carries the shielding requirement itself. On a single-core cable the armour and the screen sit in the same field, so the bonding decision taken for the screen applies to the armour as well. That is the subject of the next section.

05Screen bonding: the decision that changes the cable's current rating

This is the part of MV collector design that is least visible in a procurement document and most consequential to the installed plant. The screen runs parallel to its own conductor for the whole route, which makes it, in part, the secondary of a 1:1 transformer. Alternating current in the conductor induces a longitudinal EMF in that parallel screen, proportional to the conductor current, the route length and the conductor-to-screen mutual inductance.

What happens next depends entirely on where the screen is earthed.

Both ends bonded: no standing voltage, but a circulating current

Earthing the screen at both ends closes a loop. The induced EMF drives a current around the screen–earth circuit, and that current produces an I²R loss in the screen — heat, and a correspondingly lower permissible current for the circuit. Sources differ on the magnitude: one cable-engineering source quotes 50–80% of conductor current on long circuits, another quotes 30–40% in some installations. Both figures come from practice at different voltage levels and constructions, so the honest statement is that the circulating current can reach a substantial fraction of the conductor current and that it must be computed for the actual route rather than assumed from either range.

The trade-off is that both-ends bonding leaves a standing screen voltage of only a few volts, requires no surge voltage limiters and no parallel earth-continuity conductor, and is the safest arrangement to touch. It is normal practice on short runs where the induced EMF and the resulting loss are affordable.

Single-point bonding: no circulating current, but a standing voltage at the open end

Earthing the screen at one end only breaks the loop, so no circulating current flows and the screen loss disappears — and the circuit keeps its full tabulated ampacity. The price is a standing induced voltage at the unearthed end, proportional to route length and load current. That voltage is what limits the length of a single-point-bonded section, because it has to stay below the project's touch-voltage limit.

Single-point bonding also needs two additional components: a parallel earth-continuity conductor so that fault current has a path back, and surge voltage limiters at the open end so the screen survives through-fault and transient overvoltages. Link-box-mounted SVLs in the range of about 0.8–4.8 kV MCOV, and outdoor units around 4–14 kV, are typical product practice — selected by an insulation-coordination study, not by the cable standard.

The failure mode worth knowing aboutA sheath-to-earth fault converts a single-point-bonded section into a solidly bonded one, silently. Nothing trips. The circuit simply begins circulating screen current, loses ampacity and runs hotter for the rest of its life. Keentel Engineering describes the sheath test at commissioning as the test that detects this, and notes that the conductor test sequence will not find it. We did not find the sheath test required explicitly by a standard in our library, so treat it as established industry practice rather than a clause obligation.

Cross-bonding: cancelling the EMF by transposition

Cross-bonding splits a major section into three electrically equal minor sections and transposes the screens at each intermediate joint, so that each screen in turn sees the induced EMF of each phase. Over a complete transposition cycle the three induced EMFs sum to approximately zero: no circulating current, no large standing voltage, and screens solidly earthed at both ends of the major section.

The cost is complexity. Cross-bonding needs sectionalised joints, a link box at each transposition point, and equal section lengths — unequal minor sections leave a residual circulating current, typically a few percent of conductor current, because the cancellation is incomplete. A sheath fault on a cross-bonded system also unbalances the transposition, and the same sheath test is the only thing that finds it.

Table 4 — Screen bonding schemes compared
SchemeCirculating screen currentStanding screen voltageExtra componentsLimiting factor
Both ends bondedYes — a substantial fraction of conductor currentNear zero, a few voltsNoneRoute length against acceptable loss and derating
Single-pointNoYes — at the unearthed end, proportional to length and currentParallel earth-continuity conductor, SVLs at the open endTouch-voltage limit at the open end
Cross-bondedApproximately zero over a full cycle; a few percent residual if sections are unequalLow, with screens earthed at both ends of the major sectionSectionalised joints, link box at each transpositionRequirement for three electrically equal minor sections

Schemes and their operating characteristics are established cable-engineering practice, documented by Keentel Engineering, PTE (Power Transmission Engineering), QD Britop and Power & Cables, all held in our library. The circulating-current magnitudes quoted in the text are illustrative ranges from separate sources at different voltage levels, not a design rule; the SVL figures are link-box product practice rather than a standard requirement.

A · BOTH ENDS BONDED standing voltage ≈ 0 · circulating current present conductor screen circulating screen current I²R heat → circuit derates B · SINGLE-POINT BONDING no circulating current · full ampacity · standing voltage at the open end conductor screen earthed SVL left open & insulated standing induced voltage grows with route length × load current parallel earth-continuity conductor C · CROSS-BONDING three equal minor sections, screens transposed — induced EMFs sum to ≈ 0 A→B B→C C→A link box at each transposition point screens earthed both ends
The bonding scheme decides how much of the tabulated ampacity survives. Earthing the screen at both ends closes a loop the induced EMF drives current around, so the circuit loses ampacity to I²R heat in the screen. Leaving one end open breaks the loop and keeps the full rating, but a standing voltage appears at the unearthed end and must be kept below the project's touch-voltage limit — which is what caps a single-point-bonded section's length. Cross-bonding buys low standing voltage and earthed screens at both ends by transposing the screens across three electrically equal minor sections, so the induced EMFs cancel over a full cycle; unequal sections leave a residual current.

The NEC states the ampacity consequence explicitly

This is the point at which the bonding decision and the ampacity table meet, and the NEC is unusually direct about it. Under 311.60(D)(1), the ampacities given in four specific tables — 311.60(C)(69), (70), (81) and (82), which are the single-conductor tables for cables in air and directly buried respectively — apply only to cables whose shields are grounded at one point only. Where shields are grounded at more than one point, the ampacities must be adjusted to take into account the heating due to shield currents. The code then adds an informational note: the other tables in that group contain the ampacity of cables with shields grounded at multiple points.

So the tabulated ampacity is not a property of the cable. It is a property of the cable plus its bonding scheme. A collector circuit designed from the single-point-grounded table but installed with both ends bonded will not deliver the tabulated current, and the error is not detectable from the cable datasheet.

Where this hits a real projectA long collector run is the case where single-point bonding pays: the full ampacity is retained and the screen loss is eliminated, at the cost of surge voltage limiters and a continuity conductor. A short run between a turbine and the next one in the string is the case where both ends bonded is simpler and the loss is affordable. The decision is length- and current-dependent, so it belongs in the electrical design, not in the cable purchase order. If you have the route length and the fault study, we can confirm which screen construction fits.

06Burial, ducts and the ampacity baseline

A collector circuit on a wind or solar site is almost always buried. That makes it worth knowing exactly what the standard ampacity tables assume, because the baseline conditions are specific and the corrections away from them are prescribed.

For direct-buried cable and underground duct banks, 311.60(F) sets out the basis on which the NEC ampacity tables are computed: an ambient earth temperature of 20 °C, an arrangement in accordance with the standard installation figures, a 100% load factor, a soil thermal resistance (Rho) of 90 (cm·K/W — the NEC states the figure without a unit), conductor temperatures of 90 °C or 105 °C, and a maximum depth to the top of the duct bank or direct-buried cable of 750 mm and 900 mm respectively. Minimum burial depths follow the general installation rules for underground conductors and cables under 300.50.

The relevant correction provisions are:

  • Ambient earth temperature. Where the ambient differs from the 20 °C baseline, 311.60(D)(4) applies a correction factor from the standard's table. At 30 °C the factor is 1.10 for a 90 °C conductor and 1.07 for a 105 °C conductor; at 10 °C or below it is 1.26 and 1.21.
  • Burial depth. Under 311.60(D)(2), no correction is required where the burial depth is decreased. Where it is increased beyond the tabulated depth, a derating of 6% per 300 mm of additional depth is permitted for all values of Rho.
  • Multiple circuits. The tables are published per circuit count — one, three, six, and larger groupings — and the ampacity falls as more circuits share the same corridor.
  • Two different ampacities applying. Under 311.60(A)(2), where more than one calculated or tabulated ampacity could apply to a circuit, the lowest value is used, with a narrow exception for short portions of lower ampacity not exceeding the lesser of 3.0 m or 10% of the total circuit.

The soil thermal resistivity term is where collector circuits most often go wrong, because it is a site measurement rather than a catalogue value. If the backfill or the native soil is drier or more insulating than the assumed baseline, the cable runs hotter at the same current, and no amount of cable oversizing fixes a thermal problem in the ground. Our separate treatment of soil thermal resistivity and its effect on direct-buried cable ampacity goes into the measurement side; this article only needs the point that the baseline is an assumption, and that a collector circuit running through a long dry section is a different thermal problem from the same cable in damp clay.

Cross-check worth doing on any MV quotationAsk what ambient earth temperature, what soil thermal resistivity and what circuit grouping the quoted current rating is based on. A rating quoted without those three inputs cannot be checked against the site, and it cannot be compared against another supplier's rating. Where a manufacturer declines to publish a generic ampacity table at all — which is what our own MV product page does — the reason is precisely that the number is a function of the installation, not of the cable.

07IEC 60502-2 against UL Type MV-105: two procurement worlds

A collector circuit specification has to name one of these families, and the two are not convertible. Naming both, or assuming the values of one carry into the other, is a defect that surfaces at the type-test stage.

Table 5 — The two MV cable standards worlds side by side
ItemIEC systemNorth American system
Cable standardIEC 60502-2 — extruded solid insulation, 6 kV (Um 7.2 kV) to 30 kV (Um 36 kV), for fixed installationsUL 1072 for Type MV; construction details from ICEA S-93-639 / NEMA WC 74 and AEIC CS8
Voltage basis usedU0/U with Um — five standard ratingsNominal rating — Type MV covers 2001 V up to and including 35,000 V
Rated conductor temperature90 °C for XLPE, 250 °C short circuit for 5 s maximumType MV-90 at 90 °C and Type MV-105 at 105 °C; the higher rating applies where design conditions require it
Insulation and jacket thicknessFixed by rating in IEC 60502-2 tablesSet by the ICEA / AEIC family, with a separate table for shielded and nonshielded constructions
Insulation level conceptExpressed through the U0/U rating and its specified test voltageExplicit 100%, 133% and 173% insulation levels; 100% requires ground faults to be cleared within 1 minute, and 173% is the level for systems where a ground fault may persist
Range exclusionsOverhead networks, mining, nuclear plants, submarine and shipboard applications are outside IEC 60502-2Type MV is a wiring-method designation; mining and portable cable are separate product families
Ampacity sourceProject calculation against the installation conditionsNEC MV ampacity tables, by installation method, with temperature and depth corrections

IEC column: IEC 60502-2:2014, Edition 3.0 — scope, voltage range and exclusions as recorded in our library from the IEC webstore record for the consolidated edition including Amendment 1:2024. North American column: NEC Article 311 (medium voltage conductors and cable, 2022 California Electrical Code) for the Type MV definition, the MV-90 / MV-105 temperature ratings, the 100% / 133% / 173% insulation levels and the ampacity tables; UL 1072 and the ICEA / AEIC families as named in the MV cable specifications of a North American cable manufacturer held in our library. The insulation thickness, test voltage and rated temperature values of the two families are not interchangeable, and a construction qualified to one is not qualified to the other without its own testing. Note that the 2023 edition of the NEC renumbers this article as Article 315; clause references in this article follow the 2022-based text we hold, and a project working to the 2023 edition should verify the numbering against its own copy.

The insulation-level convention you will meet in a Type MV specification

The North American system carries a concept the IEC system expresses differently. Shielded MV cable is specified at a 100%, 133% or 173% insulation level, and the difference is a protection requirement rather than a cable quality grade. The three levels are defined in 311.10(C):

  • 100% insulation level — permitted under 311.10(C)(1) where the system has relay protection such that ground faults will be cleared as rapidly as possible and, in any case, within 1 minute. These cables are applicable to grounded systems, and are permitted on other systems provided the same clearing requirement is met in completely de-energising the faulted section.
  • 133% insulation level — permitted under 311.10(C)(2) in situations where the clearing-time requirement of the 100% level cannot be met and the faulted section will be de-energised in a time not exceeding 1 hour. It provides additional insulation margin for the longer duration a fault may persist on an ungrounded or impedance-grounded system.
  • 173% insulation level — permitted under 311.10(C)(3) only where all four conditions hold at once: the installation is in an industrial establishment where maintenance and supervision ensure that only qualified persons service it; the fault-clearing time requirements of the 133% category cannot be met; an orderly shutdown is required to protect equipment and personnel; and the faulted section will be de-energised in that orderly shutdown. It is the level for a system that is allowed to run with a fault present until it can be taken out deliberately, rather than being tripped immediately.

This is the clearest illustration of why the two families cannot be mixed: the IEC system already encodes the slow-clearing case in the rating itself. The 8.7/15 kV rating exists precisely for installations where earth-fault clearing is slower or the neutral is impedance-earthed, which is the same engineering situation the 133% level addresses in the North American system. Two different mechanisms, one underlying question — and the 173% level marks out the further case where the fault is not cleared at all until an orderly shutdown.

08What we publish, and what we will not pretend to publish

This article sets out the selection logic and the standard values that govern it. It is worth being explicit about the boundary, because MV procurement is full of documents that imply more certainty than the standards provide.

What this article does state, with sources: the voltage ratings, Um values and test voltages; the fact that insulation thickness is fixed by rating from 6/10 kV upwards; the screen grading and short-circuit figures; the three bonding schemes and their trade-offs; the assumptions behind the buried ampacity tables and the correction provisions; and the scope of both standards families.

What this article does not do — and no honest article can: give you a current rating for your cable. The current rating is a function of the installation method, the ambient and earth temperature, the soil thermal resistivity, the circuit grouping, the burial depth and the bonding scheme. Any generic ampacity table for an MV collector cable is a table for some other site. That is why our MV cable page declines to publish one, and why the screen type is confirmed against the earth-fault duty you send us rather than offered as a standard option.

The other boundary is certification. IEC 60502-2 is a product standard: it specifies how the cable is constructed and tested. It is not a factory certification, and holding a cable built to it is not the same as holding an approval. Certification and test documentation for the construction supplied is issued with the quotation for that construction.

Specifying a collector circuit? Send us the numbers that decide it.

The U0/U rating or the system voltage, the conductor size, the earth-fault current and its clearing time, and the installation method — trenches, ducts or direct burial, with the soil thermal resistivity if you have it. We will come back with the construction, the screen type and the dimensioned drawing for your design to check.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Experienced in cable specification aligned with IEC standards.

Sources checked

  • NFPA 70, National Electrical Code, Article 311 (Medium Voltage Conductors and Cable) — scope, the Type MV definition (2001 V to 35,000 V nominal), the MV-90 / MV-105 temperature ratings, the 100% / 133% / 173% insulation levels, shielding requirements including the two exceptions, direct-burial requirements, and the ampacity provisions including the single-point-grounded shield condition and the burial-depth and ambient-temperature corrections. Read in the 2022 California Electrical Code text held in our library; the 2023 edition renumbers this article as Article 315. nfpa.org
  • UL 1072, Standard for Medium-Voltage Power Cables — the UL standard behind the Type MV designation. Named here for identification; we hold no copy of the standard text, so no clause-level citation is made. ul.com
  • Prysmian / Anaconda, Mining Cables catalogue, AIRGUARD EPR / copper tape shield / polymeric armour / PVC shielded UL Type MV-105 sections for 5 kV, 8 kV, 15 kV, 25 kV and 35 kV — the North American MV construction chain (extruded strand shield, EPR insulation, extruded insulation shield, annealed copper tape with 25% nominal overlap, split bare copper ground conductors, polymeric armour, lead-free flame-retardant PVC jacket) and the compliance list including UL 1072, ICEA S-93-639 / NEMA WC 74, ICEA S-97-682 and AEIC CS8-13. Held in our library as text extraction only. prysmian.com
  • IEC 60840, Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) — Test methods and requirements — the standard that takes over from IEC 60502-2 above a 36 kV maximum system voltage, and therefore the governing cable standard for a collector system specified at 35 kV nominal (Um = 40.5 kV). Named here for scope identification; we hold no copy of the standard text, so no clause-level citation is made. webstore.iec.ch
  • GB/T 156, Standard voltages — the Chinese standard voltage series, which sets the equipment maximum voltage of a 35 kV nominal system at 40.5 kV. Named for the Um relationship used in this article; we hold no copy of the standard text, so no clause-level citation is made.
  • IEC 60502-2:2014, Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) — Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV), Edition 3.0, consolidated with Amendment 1:2024 — scope, the list of excluded special installation conditions (overhead networks, mining, nuclear power plants, submarine and shipboard), and the seven technical changes introduced by the third edition, which include a new subclause for a routine electrical test on oversheath. We hold the IEC webstore record for the consolidated edition in our library, not the clause text, so no clause-level citation is made. webstore.iec.ch
  • SORIVO, Medium Voltage Armoured Power Cable 6/10 kV – 18/30 kV (IEC 60502-2) — the published voltage ratings, Um values and AC test voltages; insulation thickness by rating and conductor size; the CWS and CTS screen cross-sections and their 1-second short-circuit capacities; the CWS grading by conductor size; and the declared scope limits on ampacity and certification. Values quoted in Tables 1 to 3 and in the text are taken from this page. sorivocable.com
  • European MV cable range dimensional data (single-core, IEC 60502-2, 95 mm² and 240 mm² at 3.6/6, 6/10, 8.7/15, 12/20 and 18/30 kV) — insulation thickness, bedding thickness, armour wire diameter, oversheath thickness, overall diameter and weight per voltage rating, used to cross-check the insulation-thickness table. Manufacturer data sheets held in our library. caledonian-cables.com
  • Keentel Engineering, Cable Testing Before Energization — sheath bonding schemes, the sheath-to-earth fault that silently converts single-point bonding into solid bonding, and the sheath test as the only commissioning test that detects it. Single source for the sheath-test claim, which is stated in the article as established industry practice rather than as a clause obligation. keentelengineering.com
  • PTE (Power Transmission Engineering), Link Boxes — single-point, split single-point and cross-bonding definitions, surge voltage limiter function, and the earth-continuity conductor requirement. pte-sa.com
  • QD Britop, Cable Sheath Circulating Current in High-Voltage Systems — the induced sheath voltage mechanism and the 50–80% circulating-current magnitude quoted for long single-core circuits. qdbritop.com
  • Power & Cables, HV Cable Sheath Bonding Methods — independent summary of solid, single-point and cross-bonding with their operating limits. powerandcables.com
  • Industrial Monitor Direct, IEC Cable Armor Grounding Requirements — armour bonding ends by cable construction and the 30–40% circulating-current figure quoted as an alternative magnitude. Manufacturer-distributor technical note, used as engineering practice rather than as a clause citation. industrialmonitordirect.com

How this was written: every standard and code figure in this article is checked against the standard text or the published clause summary listed in Sources before publication. Where our library does not hold a standard's clause text we state the principle without a clause number, and where two sources give different magnitudes for the same quantity we print both rather than choosing one. Site-level design decisions remain with the engineer of record.

Related product · MV collector and feeder cable to IEC 60502-2
Medium Voltage Armoured Power Cable 6/10 kV – 18/30 kV (IEC 60502-2)
ApplicationDistribution and feeder circuits from 6 kV to 30 kV, indoors, outdoors, in ducts, trenches and on tray, where mechanical protection is required
StandardsDesigned and manufactured to IEC 60502-2; conductor to IEC 60228 Class 1 or Class 2. IEC 60502-2 is a product standard, not a factory certification
ConductorAnnealed bare copper, IEC 60228 Class 1 (solid) or Class 2 (stranded)
InsulationXLPE as standard; EPR/HEPR available on request
Voltage Rating3.6/6 kV · 6/10 kV · 8.7/15 kV · 12/20 kV · 18/30 kV; Um 7.2–36 kV
AmpacityNot published as a generic table — current ratings depend on installation method, ambient, grouping and depth, and are issued per project against the installation conditions
TemperatureAmbient −5 °C with PVC or LSZH oversheath, −20 °C with PE oversheath; conductor 90 °C continuous, 250 °C short circuit for 5 s maximum
CertificationsCertification and test documentation for the construction supplied is issued with the quotation
Screen TypeCWS copper wire screen — 16/25/35/50 mm² by conductor size; or CTS copper tape screen. Screen sized to the earth-fault current and its duration
Building a collector circuit specification? Send the U0/U rating, conductor size, earth-fault current and clearing time, and installation method, and we will confirm the construction and screen type against them. request a quote.
Q1What voltage rating does a 35 kV collector circuit use?

On an IEC project, a 33 kV or 35 kV collector network normally sits under the 18/30 kV rating, whose maximum system voltage Um is 36 kV. On a North American project the governing figure is the nominal rating: Type MV cable is defined as solid dielectric insulated cable rated 2001 V up to and including 35,000 V. The two systems check different numbers for the same physical system, which is why a specification should always state U0/U and Um, not a single voltage.

Q2Is a 6/10 kV cable the same as a 10 kV cable?

No. The rating 6/10 kV means U0 = 6 kV phase-to-earth and U = 10 kV phase-to-phase; its maximum system voltage Um is 12 kV, not 10 kV. Writing the rating as a single figure of 10 kV loses the phase-to-earth value the insulation was designed against. The same pattern holds across the IEC range: 8.7/15 kV gives Um = 17.5 kV, 12/20 kV gives 24 kV, and 18/30 kV gives 36 kV.

Q3Why is copper tape screen not equivalent to copper wire screen at the same size?

Because the effective cross-section differs. Taking the 6/10 kV reference construction, a 16 mm² copper tape screen carries about 0.86 kA for one second, while a 16 mm² copper wire screen carries about 1.96 kA — well over twice as much. The screen is a fault-current path, so it must be sized against the earth-fault current and its clearing time for the installation. A specification that names a screen cross-section without naming the screen type has not specified the screen.

Q4How does screen bonding affect the current rating of a collector circuit?

Directly, and the NEC states it explicitly: four single-conductor ampacity tables — 311.60(C)(69), (70), (81) and (82), the in-air and direct-burial groups — apply to cables with shields grounded at one point only, and where shields are grounded at more than one point the ampacity must be adjusted for the heating caused by shield currents. Earthing both ends of a screen closes a loop that the induced longitudinal EMF drives a current around, and the I²R loss in the screen reduces the current the circuit can carry. Screen bonding is therefore part of the ampacity calculation, not a separate installation detail.

Q5When is cross-bonding worth the complexity on a collector circuit?

When the route is long enough that single-point bonding's standing voltage at the open end exceeds the project's touch-voltage limit, and long enough that accepting circulating current with both ends bonded would cost too much ampacity. Cross-bonding splits the route into three electrically equal minor sections and transposes the screens so the induced EMFs cancel over a full cycle, giving low standing voltage with the screens earthed at both ends. It needs sectionalised joints, a link box at each transposition and equal section lengths — unequal sections leave a residual current.

Q6Can IEC 60502-2 and UL Type MV-105 cable be used interchangeably on one project?

Not as equivalents. The two families use different rated temperatures, different insulation thickness tables and different test voltages for the same nominal service, and a construction qualified to one is not qualified to the other without its own testing. The typical arrangement is that the site's wiring regulations and the equipment being terminated into decide which family governs, and the specification names one of them for the whole circuit. Naming both, or carrying values from one into the other, is a defect that surfaces at type-test stage.