Brown, black, grey in Europe. The same black means something completely different in the USA. If you export cables or build international projects, getting core colours wrong means failed inspections and rework.
★ International Specification GuideIf there’s one thing that catches exporters out more than any electrical parameter, it’s the colour of the insulation. A perfectly manufactured cable with the wrong core colours is — in the eyes of the inspector — the wrong cable. I’ve seen containers of armoured cable flagged on site because the cores were identified to the wrong national convention.
Here’s the trap in a nutshell: in Europe, black is a live conductor and blue is the neutral. In the USA, black is usually a live conductor too — but blue is a phase, and the neutral is white. Same colours, opposite jobs on either side of the Atlantic, and the gap only widens the deeper you dig into each code. Get one export project wrong and you’re re-terminating or re-ordering.
Let me walk you through the three systems that matter for international work — the European harmonised code, the UK’s specific application of it, and the North American NEC practice — plus what to do when you’re specifying cable for a market that isn’t your own. Think of it as the cable core identification chart your export spec never came with.
HD 308 S2 is the CENELEC harmonisation document that standardises core identification for LV cables and flexible cords up to 1 kV across Europe.
The logic is simple: colour equals function, not phase order.
| Core Count | With Green/Yellow Core | Without Green/Yellow Core |
|---|---|---|
| 2 core | 2G: Green/Yellow – Brown | Brown – Blue |
| 3 core | 3G: Green/Yellow – Blue – Brown | Brown – Black – Grey |
| 4 core | 4G: Green/Yellow – Brown – Black – Grey | Brown – Black – Grey – Blue |
| 5 core | 5G: Green/Yellow – Blue – Brown – Black – Grey | Brown – Black – Grey – Blue – Black (no. 5) |
| Notation: "G" indicates one core is green/yellow (protective); "X" indicates no green/yellow core. Source: HD 308 S2. 5th and additional cores (beyond the four standard colours) are black with printed numbers per HD 308 S2. | ||
Single-core cables may be supplied in any colour (black, blue, red, yellow, white, violet, brown, grey, orange, pink) — with one exception: green/yellow stays reserved for the protective conductor alone. For single cores the function is defined at the termination, not by the factory colour. The harmonisation document has been adopted into national standards — BS 7671 in the UK, VDE 0293-308 in Germany — so it applies right across Europe.
The UK followed the European harmonised code, but the transition has left a few traps that still cause confusion today.
The UK adopted harmonised colours in two stages. From 1 April 2004 the new colours could be used optionally; from 1 April 2006 they became mandatory for all new installations, and old and new colours could not be mixed.
| Function | Old UK Colours (pre-2006) | New Harmonised Colours (BS 7671) |
|---|---|---|
| Single-phase live | Red | Brown |
| Three-phase live | Red / Yellow / Blue | Brown / Black / Grey |
| Neutral | Black | Blue |
| Protective (earth) | Green / Yellow | Green / Yellow (unchanged) |
The two changes that cause the most danger in legacy installations:
Because some core colours are now “functional” colours, BS 7671 requires that when a core is repurposed, it must be identified at every termination:
Getting the colours right is only half the job — the conductor still has to carry the load. If you’re sizing distribution runs to BS 7671, our high-rise riser cable sizing and voltage drop guide walks through the whole process with worked numbers.
Here’s the important difference: the NEC mandates only a few colours. The familiar black/red/blue system is an industry convention, not a code requirement.
This is the single biggest misunderstanding between European and American cable. In Europe, HD 308 S2 standardises which colour means which function. In the USA, NEC requires only three colour rules, and everything else is convention that can vary by contractor, region, or even project.
| Voltage System | Phase 1 | Phase 2 | Phase 3 | Neutral | Ground |
|---|---|---|---|---|---|
| 120/208 V, 3-phase | Black | Red | Blue | White | Green/bare |
| 120/240 V, single-phase | Black | Red | — | White | Green/bare |
| 120/240 V, 3-phase (high-leg delta) | Black | Orange (high-leg) | Blue | White | Green/bare |
| 277/480 V, 3-phase | Brown | Orange | Yellow | Grey | Green/bare |
| The ungrounded (phase) conductor colours are industry conventions, not NEC mandates. Local jurisdictions and older installations may differ. | |||||
The good news for specifiers: core colour is one of the easiest things to get right at the factory — and the hardest to fix on site.
Sorivo manufactures cables to your specified core identification. For export projects, we routinely produce:
| Market | Standard Colours Supplied | Notes |
|---|---|---|
| Europe (EU) | Brown / Black / Grey live, Blue neutral, Green/Yellow earth per HD 308 S2 | Standard for all EU-market power and control cables |
| United Kingdom | Harmonised colours per BS 7671 (brown/black/grey, blue, green/yellow) | Same physical colours as EU, but verify sleeving requirements on site |
| United States | Black / Red / Blue (120/208 V) or Brown / Orange / Yellow (277/480 V), White or Grey neutral, Green or bare ground | Confirm required colour scheme with the project spec before ordering |
| Custom / other markets | Any specified core colour sequence | Provide your colour schedule or reference standard; we manufacture to match |
| Feature | Market Generic / Economy | Sorivo Premium Grade |
|---|---|---|
| Core colour accuracy | Colour may drift between batches; stripes inconsistent | Consistent, durable insulation colours matched to your specified standard |
| Custom colour scheduling | Limited to standard stock colours | Manufactured to your exact colour schedule for export markets |
| Conductor quality | Variable — higher resistance affects the cable’s rating | IEC 60228 Class 1/2 verified, consistent DC resistance |
| Traceability | None — no batch records | Metre-marked, batch traceable, full certification available |
| Certification | Self-declared | Third-party tested to the relevant national standard for your market |