Junior service cord with a Class K rope-stranded bare copper conductor and a slim, oil-resistant EPDM / CPE construction — the 300V cord for hand tools, maintenance work and light equipment where weight and flexibility matter more than the higher voltage class.

Everything an electrical engineer checks first on a junior service cord — before reading the full specification below.
The SJOOW 12/3 is a three-conductor, 300V rubber portable cord built to the UL 62 flexible-cord construction and its CSA C22.2 No. 49 equivalent. The SJ prefix marks it as a junior service cord: same construction family as SOOW, one voltage class below it, and noticeably slimmer and lighter, which is what makes it the cord that gets carried from job to job with the tool it feeds.
The conductor is 65 × 30 AWG bare copper, Class K rope-stranded per ASTM B-174 — the same copper as the 600V cord of this size. Maximum DC resistance is 1.59 Ω/1000 ft (5.22 Ω/km) at 20°C, the finished cord measures about 0.43 in (10.9 mm) overall, and it weighs 146 lbs/1000 ft (217 kg/km).
Insulation is heat- and moisture-resistant EPDM rubber at a thinner wall than the SOOW version, inside a black CPE jacket that is also slimmer. Together they give the cord its oil, grease, ozone, water and UV (SUN RES) resistance, and keep it flexible down to −20°C. Maximum conductor temperature is +90°C for continuous operation.
Ampacity is 25 A per NEC Table 400.5(A)(1). The value comes from column A — 2 current-carrying conductors — because the green conductor in a 3-conductor cord is the equipment grounding conductor and is not counted as a current-carrying conductor. The table's basis is a 30°C ambient; above that, or where cords are bundled or run in a raceway, apply the correction and adjustment factors of NEC Table 400.5(A)(2). Ampacity follows the conductor size and not the voltage class, so the same 25 A applies to the 600V SOOW cord of this size.
More about the manufacturer: About SORIVO →
Built to the UL 62 junior service cord construction and the CSA C22.2 No. 49 equivalent, with NEC Article 400 covering how the cord may be used.
65 × 30 AWG bare copper, Class K rope-stranded per ASTM B-174 — the same flexible copper as the 600V cord of this size.
A 0.030 in (0.76 mm) EPDM insulation wall inside a slimmer black CPE jacket. That thinner wall is exactly what makes the SJ cord smaller and lighter than SOOW.
300V junior service cord rated 25 A per NEC Table 400.5(A)(1) column A — 2 current-carrying conductors plus the equipment grounding conductor, on a 30°C ambient basis.
Resistant to oil, greases, ozone, weathering effects, water and UV radiation (SUN RES) — the same rubber compounds as the heavy duty cord.
+90°C maximum conductor temperature. The full temperature range is −20°C to +90°C while flexible and −40°C to +90°C in a fixed installation.
Flame-retardant to CSA FT2 as declared for this construction, with MSHA flame-test performance available on request and test documents issued with the quotation.
0.43 in (10.9 mm) overall and 146 lbs/1000 ft (217 kg/km) — a coil one person can carry, for tools that move with the job.
Hand tools, maintenance work and light equipment on 300V circuits — one cord construction, sized per project.
Drills, sanders, grinders and saws on 300V single-phase supplies, where a lighter cord is easier to work with all day.
Maintenance, repair and overhaul work where the cord is plugged in, moved and coiled again every shift.
Bench tools, task lighting and small equipment in workshops where the cord drapes rather than runs in a tray.
Task and inspection lighting strings, where the smaller diameter keeps a run of cords manageable.
Feeds to small pumps, fans and bench machinery on 300V circuits, sized for continuous current and voltage drop.
Distribution to stands, stages and rental equipment that is connected and struck on every job.
Yard tools, small pumps and outbuilding equipment in damp conditions the CPE jacket is formulated for.
Power leads and pendant drops on light machinery, supplied cut to length with your own printing and terminations.
The complete parameter set — the same data our engineers quote from.
| Size AWG × cond. | Conductor stranding Class K per ASTM B-174 | Nominal outer diameter in (mm) | Approx. weight lbs/1000 ft (kg/km) | Max. DC resistance at 20°C | Ampacity at 30°C, A |
|---|---|---|---|---|---|
| 12 AWG × 3 | 65 × 30 AWG | 0.43 (10.9) | 146 (217) | 1.59 Ω/1000 ft (5.22 Ω/km) | 25 |
The 12 AWG × 3 row is the size this page covers, and it is the only SJOOW size quoted here. Ampacity is taken from NEC Table 400.5(A)(1), column A (2 current-carrying conductors), at a 30°C ambient: in a 3-conductor cord the green conductor is the equipment grounding conductor and is not counted as current-carrying. Above 30°C, or for bundled or raceway installations, apply NEC Table 400.5(A)(2). All dimensions and weights are nominal and may vary according to plant of manufacture; the data is provided for information only and does not create a binding obligation or liability.
| General Information | |
| Product Name | SJOOW 12/3 Medium Duty Portable Cord 300V UL62 Rubber Cable |
| Primary Standard | UL 62 — flexible cords and cables |
| Further Standards | CSA C22.2 No. 49; NEC Article 400; ASTM B-174 (Class K rope-stranded conductor) |
| Rated Voltage | 300V AC — junior service cord class |
| Construction | 3 conductors — 2 current-carrying conductors plus 1 green equipment grounding conductor (EGC) |
| Usage Rating | Hard usage — one grade below the extra-hard usage class of the 600V SOOW cord; the applicable rating for the selected size and routing is confirmed on the quotation |
| Conductor | |
| Conductor Material | Bare copper, fully annealed per ASTM B-174 |
| Conductor Type | Class K rope-stranded, extra-flexible |
| Conductor Stranding | 12 AWG: 65 × 30 AWG |
| Max. DC Resistance | 12 AWG: 1.59 Ω/1000 ft (5.22 Ω/km) at 20°C |
| Insulation & Jacket | |
| Insulation Material | EPDM (ethylene propylene diene monomer) rubber — heat and moisture resistant |
| Insulation Thickness | 12 AWG: 0.030 in (0.76 mm) — a thinner wall than the SOOW cord of the same size |
| Jacket Material | CPE (chlorinated polyethylene), black — oil, ozone and weather resistant; slimmer than the SOOW jacket of the same size |
| Core Identification | Black, white, green (EGC) |
| Nominal Outer Diameter | 12 AWG × 3: 0.43 in (10.9 mm) |
| Approx. Weight | 12 AWG × 3: 146 lbs/1000 ft (217 kg/km) |
| Jacket Marking | SORIVO SJOOW 12 AWG (3.31 mm²) 3/C 300V UL 62 CSA C22.2 No. 49 FT2 <year> — or per customer requirement |
| Electrical Ratings | |
| Current Carrying Capacity | 12 AWG × 3: 25 A per NEC Table 400.5(A)(1), column A (2 current-carrying conductors counting the EGC out), 30°C ambient |
| Ampacity Derating | Per NEC Table 400.5(A)(2) — ambient temperature correction and conductor-count adjustment for bundled or raceway installations |
| Test Voltage | 2500 V core to core, as a routine production test to UL 62 |
| Voltage Drop (12 AWG) | ≈ 10.44 V/A/km for the complete circuit loop at 20°C conductor temperature, calculated from the maximum DC resistance |
| Temperature & Environmental | |
| Temperature Range | Flexible: −20°C to +90°C; fixed installation: −40°C to +90°C |
| Max. Conductor Temperature | +90°C continuous |
| Oil & Grease Resistance | Oil-resistant EPDM insulation and CPE jacket per the UL 62 / CSA C22.2 No. 49 construction |
| Water & Weather Resistance | Weather-resistant jacket; resistant to weathering effects and water |
| Ozone Resistance | Resistant to ozone |
| UV Resistance | Resistant to UV radiation (SUN RES) — suitable for outdoor service in dry or damp locations |
| Flame Rating | Flame-retardant to CSA FT2, as declared for this construction |
| MSHA Flame Test | MSHA flame-test performance available on request. The MSHA file number in circulation belongs to the third-party cord makers whose data sheets publish it, so we do not reproduce it as our own; our own MSHA documentation and flame-test records are supplied with the quotation for the exact construction |
| Min. Bending Radius | Manufacturer-recommended: 10 × overall diameter when flexible, 6 × overall diameter in a fixed installation |
| Packaging & Logistics | |
| Packaging | Wooden drum / coil / spool |
| Standard Length | 250 ft / 500 ft / 1000 ft |
| MOQ | 1,000 ft |
| Lead Time | 5–15 working days |
Final selection should be based on load current, circuit voltage, cord length, ambient temperature, installation method and the applicable local code. Certification scope and the applicable usage rating are confirmed in writing against the factory documents for the selected construction before the order is placed.
| Same construction family, two voltage and duty classes | ||
| Parameter | SJOOW 12/3 (this page) | SOOW 12/3 (600V) |
| UL 62 letter code | SJ — junior service cord | S — service cord |
| Rated voltage | 300V AC | 600V AC |
| Usage rating | Hard usage | Extra-hard usage |
| Conductor stranding | 65 × 30 AWG, Class K | 65 × 30 AWG, Class K |
| Insulation thickness (EPDM) | 0.030 in (0.76 mm) | 0.045 in (1.14 mm) |
| Nominal outer diameter | 0.43 in (10.9 mm) | 0.595 in (15.1 mm) |
| Approx. weight | 146 lbs/1000 ft (217 kg/km) | 224 lbs/1000 ft (333 kg/km) |
| Ampacity at 30°C | 25 A | 25 A |
| Test voltage | 2500 V core to core | 2500 V core to core |
| Min. bending radius | 10 × OD flexible / 6 × OD fixed | 10 × OD flexible / 6 × OD fixed |
| Temperature range | −20°C to +90°C flexible / −40°C to +90°C fixed | −20°C to +90°C flexible / −40°C to +90°C fixed |
| Flame rating | CSA FT2 | CSA FT2 |
At the same 12 AWG conductor size the SJOOW cord is 27.7% smaller in overall diameter (10.9 mm against 15.1 mm) and 34.8% lighter (146 against 224 lbs/1000 ft). Ampacity is identical because it follows the conductor, not the voltage class — the difference between the two cords is the voltage rating and the usage class, plus the thinner wall that makes the junior cord smaller.
This SJOOW 12/3 is built to the UL 62 junior service cord construction and the CSA C22.2 No. 49 equivalent. Certificate and listing scope for the selected construction are supplied in writing with the quotation.
Request certificate copy →Flame-retardant to CSA FT2 as declared for this construction. MSHA flame-test performance is available on request: the MSHA file number in circulation belongs to the third-party cord makers whose data sheets publish it, so we do not reproduce it as our own, and our own MSHA documentation and flame-test records are supplied with the quotation for the exact construction.
Request test report →Compliant with RoHS-2 (European Directive 2011/65/EU). Compound and conductor declarations for the selected construction are available on request.
Request declaration →
Every reel of junior service cord is produced under controlled processes and released against the applicable UL 62 construction requirements.
Tell us the AWG size, conductor count, colour, quantity and destination market.
We confirm the SJ construction, flame and mining test scope, and quotation within one working day.
Cut-length samples for qualification — stock items within a few working days.
5–15 working days lead time with batch test documentation.