Standard cross-reference · Building wiring · 2026

Building Wire Cross-Reference: GB/T vs H07V, THHN and BS 6004

A single-core PVC building wire is called BV in China, H07V-R or 6491X in Europe and the UK, and THHN in North America. This page decodes each code letter by letter and gives the cross-reference table, so a specification written in one system can be quoted in another.

Published 2026-10-14 Updated 2026-10-14 Level: reference Reading time ~17 min
The short answer

For a single-core, unsheathed PVC building wire, three current standards cover the same product: GB/T 5023.3-2008 in China (type 60227 IEC 01, commonly written BV), BS EN 50525-2-31 in Europe and the UK (types H07V-U / H07V-R / H07V-K, the UK name of which is 6491X), and UL 83 in North America (type THHN). The Chinese standard is an identical adoption of IEC 60227, so its type codes track the IEC ones; the European and North American systems are their own documents, so they are compared on construction and ratings, not on code names. China and Europe land on the same practical ratings for the common sizes — 450/750 V, a 70 °C PVC conductor limit for the plain PVC types, and a 2 500 V finished-cable test. The North American type is its own case: 600 V and 90 °C dry, under the UL 83 test regime.

This page is the building-wiring companion to our cable standard cross-reference hub, which maps the four standard systems as a whole. The hub page answers "which family does this belong to"; this page goes one level down and answers the question that actually reaches a quotation desk: the customer wrote H07V-R, or THHN, or BV — what do I quote, and what exactly does each letter mean?

The four systems do not sit on the same footing, and the difference matters before any table is read. The Chinese and European systems are both built on IEC 60227 — but the Chinese one adopts it identically while the European one harmonised it into its own EN document. The North American system never used IEC 60227 at all; it grew a separate letter alphabet that encodes ratings rather than materials. That single fact explains most of the mismatches in this article.

01What a building wire is, before the standards get involved

A building wire is the basic single-core conductor that runs inside conduit, trunking or a wall to feed lighting and power circuits. In every one of the three systems it is the same physical object: a copper conductor, one layer of PVC insulation, and no outer sheath. What changes between systems is how much detail the type code carries and what the code is anchored to.

  • China: the code is a two-digit number after 60227 IEC, and it points at an IEC type; the familiar letters (BV, BVR, RV) are the older-generation names that the market still uses, now carried by the JB/T 8734 series.
  • Europe / UK: the code is a harmonised designation of the form H + voltage + insulation letter + conductor-class letter, and it points at an EN 50525 part; the UK numeric names (6491X, 2491X) come from the superseded BS 6004.
  • North America: the code is a string of rating letters (T, H, HH, W, N and a -2 suffix), and it points at a UL standard; the code says nothing about the conductor material, which has to be stated separately.
First move on any quotationThe single most useful question to ask about a building-wire enquiry is not "what size" but "which standard is this written to". The same product name can mean a different test regime depending on the answer.

02China: GB/T 5023 and the two-digit code

The current Chinese standard for PVC-insulated cables up to 450/750 V is the GB/T 5023 series. Its Part 1 states the general rules, and Part 3 covers non-sheathed cables for fixed wiring. The standard's designation annex gives the naming rule in one line: every cable type is designated by a two-digit number placed after "60227 IEC", where the first digit is the basic classification and the second is the specific variant within it.

For fixed wiring, classification 0 covers the unsheathed types (01–08) and classification 1 the light sheathed type (10). The types you meet are:

Table 1 — The GB/T 5023 fixed-wiring types, their IEC parent number, and the 1985-vintage letter name each one replaced
GB/T 5023 typeDescriptionVoltage1985-vintage letter code
60227 IEC 01General purpose, single core, rigid (solid) conductor, unsheathed450/750 VBV
60227 IEC 02General purpose, single core, flexible conductor, unsheathed450/750 VRV
60227 IEC 05Internal wiring, single core, solid conductor, 70 °C300/500 VBV
60227 IEC 06Internal wiring, single core, flexible conductor, 70 °C300/500 VRV
60227 IEC 07Internal wiring, single core, solid conductor, 90 °C300/500 VBV-90
60227 IEC 08Internal wiring, single core, flexible conductor, 90 °C300/500 VRV-90
60227 IEC 10Light PVC sheathed cable300/500 VBVV

Columns 1 and 4 are the two sides of the comparison table in the standard's informative Annex B, which pairs each current two-digit designation with the letter code used by the 1985/1986 editions. The first four fixed-wiring rows are shown; the remaining rows of Annex B cover cords, lift cables and screened types.

Why BV still shows up, and what it actually means

The letters did not disappear. BV, BVR, BLV and the rest are the 1985-edition names, and they remain the everyday market vocabulary. Two things follow, and both catch people out.

First, a Chinese supplier's own technical table often writes both at once — 60227 IEC 01(BV) — and cites GB/T 5023.3-2008 for that row. In this reading, BV is simply the colloquial name for the IEC 01 type, and the governing standard is GB/T 5023.3.

Second, the JB/T 8734 series (current edition 2016) also lists BV and BVR as its own types, with different voltage ratings: in that series BV is a 300/500 V wire and BVR is a 450/750 V flexible wire. So the same three letters, BV, can appear as a 450/750 V IEC-01 equivalent or as a 300/500 V JB/T 8734 type, depending on which standard the document is written to.

The distinction that decides a quotation When you see BV, the voltage and the test regime are not fixed by the letters alone. Read the standard number on the quotation. If it says GB/T 5023.3-2008, treat BV as the 450/750 V IEC 01 type. If it says JB/T 8734, treat BV as the 300/500 V series type and BVR as the 450/750 V flexible wire. They are not the same product, and the difference is a voltage class, not a synonym.

Decoding the letters, when letters are used

Where the older or the JB/T letter codes are used, the letters follow a fixed logic, grouped by function rather than by position:

  • By use: B fixed wiring · R flexible cord / flexible conductor · A installation wire
  • By conductor: copper is omitted; L marks an aluminium conductor
  • By material: V PVC insulation or sheath · VY oil-resistant PVC sheath
  • By construction: B flat (in the sheath families) · S twisted pair · P screened · R flexible stranding
  • By heat rating: 70 °C is omitted; 90 marks the 90 °C version

So BV reads as fixed-wiring, PVC, copper (omitted letter); BVR adds flexible stranding; BLV swaps the conductor letter in for aluminium. The decoding is deliberately shallow — the letters only describe material and construction, never the electrical rating.

Next stepIf you are matching a Chinese quotation to a European or North American specification, the fastest route is to send us the type code and the standard it cites — send the specification and we will answer against it.
CURRENT TYPE · 60227 IEC 01 the IEC parent number, then a two-digit classification 60227 IEC the IEC 60227 family 0 fixed wiring, unsheathed 1 general purpose, rigid first digit = classification, second = variant — 01 reads as "zero-one" LEGACY TYPE · BVR letters only, one meaning each B fixed wiring V PVC insulation R flexible stranding
Figure 1 — The current GB/T 5023 type is a number built from the IEC parent plus two digits; the legacy letter code describes material and construction only.

03Europe and the UK: the harmonised code and 6491X

Europe harmonises low-voltage cables through CENELEC, and the harmonised designation is what you read off the insulation. The current product standard for a single-core, unsheathed PVC building wire is BS EN 50525-2-31; its predecessor documents were BS 6004 in the UK and HD 21.3 at CENELEC level. A manufacturer's sheet may cite all three as historic lineage, as TEKIMA does when it prints "CEI EN 50525-2-31 and HD 21.3 S3" for its H07V2-K single core.

The designation is built from four fields:

Table 2 — Reading a harmonised building-wire designation, field by field
FieldExampleMeaningWorked code
HHHarmonised (CENELEC) cableH…
Voltage07 / 05 / 0307 = 450/750 V · 05 = 300/500 V · 03 = 300/300 VH07… / H05…
InsulationV / V2 / ZV = PVC 70 °C · V2 = heat-resistant PVC 90 °C · Z = halogen-freeH07V… / H07V2…
Conductor classU / R / KU = Class 1 solid · R = Class 2 stranded · K = Class 5 flexible…V-U / …V-R / …V-K

The field order and meanings follow the harmonised designation system; because HD 361, the document that fixes the rules, was not obtained for this article, no clause number is cited. The field meanings are stated from multiple manufacturer datasheets that print the same construction.

So H07V-U is a 450/750 V PVC building wire with a solid conductor; H07V-R is the same with a stranded conductor; H07V-K is the flexible (Class 5) version used for panel and equipment wiring. Swap the 07 for 05 and the voltage drops to 300/500 V, which is the internal-wiring class.

Where 6491X fits

6491X is the British numeric name that came from BS 6004, the older UK standard. It is not a second, parallel standard — it is the familiar name for a cable now built to BS EN 50525-2-31. The mapping is consistent across manufacturer datasheets:

  • 6491X → H07V-U (solid) or H07V-R (stranded), 450/750 V
  • 2491X → H05V-K (0.5–1.0 mm², 300/500 V) / H07V-K (1.5 mm² and above, 450/750 V) — the flexible, Class 5 version
  • 6491XHR → H07V2-U / H07V2-R, the 90 °C heat-resistant version

Our own 6491X / H07V-R single-core building wire is quoted to BS EN 50525-2-31 and built around the H07V-R construction: Class 2 stranded copper to IEC 60228, 450/750 V, a 70 °C maximum conductor temperature, a 160 °C short-circuit limit, and a 2500 V finished-cable test voltage. The conductor class is the whole point of the R in the code — H07V-U, H07V-R and H07V-K are not interchangeable just because they share the H07V stem.

The trap in the -R and -K A European enquiry that asks for "H07V" without the final letter is incomplete. The last letter sets the conductor class (solid, stranded or flexible), which changes the bending radius, the termination method and often the price. Ask for the full code, not the stem.
HARMONISED DESIGNATION · H07V-R four fields, read left to right H harmonised 07 450/750 V V PVC, 70 °C R Class 2 stranded U = solid · R = stranded · K = flexible
Figure 2 — The European code carries the voltage, the insulation and the conductor class; the UK name 6491X maps onto the H07V-U and H07V-R rows.

04North America: the THHN letter string

North American building wires do not use a material-based code. The letters encode ratings, and they stack up: each letter adds a property, and the code has to be read left to right as an accumulation. THHN is the most common building wire in the United States and the one most often compared against a Chinese or European type.

Table 3 — Decoding the North American building-wire letter string
LetterMeansWorked in THHNWorked in XHHW-2
TThermoplastic insulationT…—
XCross-linked polyethylene (XLPE), a thermoset—X…
HHeat-resistant (75 °C class)…H…—
HHHigh heat-resistant (90 °C, dry)…HH……HH…
WWet-location rated…W……W…
NNylon jacket over the insulation…N—
-2Rated 90 °C in wet as well as dry locations—…-2

Read across a row, not down a column: a letter present in one type and absent in another is the whole difference between them. THHN therefore reads as thermoplastic, high-heat (90 °C dry), wet-rated, nylon-jacketed — a description of ratings, with no statement about the conductor material.

What the letters prove, and what they do not

THHN is defined by UL 83 (thermoplastic-insulated wires and cables); XHHW is defined by UL 44; USE by UL 854. A manufacturer's sheet for a THHN conductor, such as the Southwire SIMpull THHN/THWN-2 data, adds the ratings in plain terms: 600 V, PVC insulation with a nylon sheath, a 90 °C dry rating for the THHN/T90 marking, a 90 °C wet-or-dry rating for THWN-2, a 75 °C limit where exposed to oil, and VW-1 / FT-1 flame ratings. The jacket and insulation construction — PVC plus nylon — is what earns the N and the friction-reducing pull properties; it is not encoded as a material letter the way V is in the Chinese and European systems.

The comparison that fails silently THHN and H07V-R can have the same copper conductor, the same nominal cross-section and the same 90 °C-capable PVC, and still not be interchangeable. THHN carries a nylon jacket and a UL 83 listing; H07V-R carries neither. Matching on "single core PVC 450/750 V" gets you close, but the nylon layer and the listing are differences the type name hides.

05The cross-reference table

This is the table to bookmark. It maps the four systems by the building-wire types you actually meet, and it deliberately leaves cells blank where no genuine equivalent exists. A blank is information: it tells you the comparison has to be made on construction and ratings rather than on names.

Table 4 — Building-wire cross-reference by type
ProductChina (GB/T, JB/T)IECEurope / UKNorth America
Single core, PVC, solid conductor, unsheathedBV / 60227 IEC 01
GB/T 5023.3
IEC 60227-3H07V-U · 6491X
BS EN 50525-2-31
—
Single core, PVC, stranded conductor, unsheathedBVR / 60227 IEC 02
GB/T 5023.3 · JB/T 8734
IEC 60227-3H07V-R · 6491X
BS EN 50525-2-31
THHN — but with nylon jacket, UL 83
Single core, PVC, flexible conductorRV / 60227 IEC 02IEC 60227-3H07V-K
BS EN 50525-2-31
MTW / AWM
Single core, PVC, 90 °CBV-90 / 60227 IEC 07IEC 60227-3H07V2-U · H07V2-R
6491XHR
THHN (90 °C dry)
Light PVC sheathed cableBVV / 60227 IEC 10IEC 60227-4H05VV-U / H05VV-RNM-B (different construction)
Flexible sheathed cordRVV / 60227 IEC 53
GB/T 5023.5
IEC 60227-5H05VV-F · 318-YSJT · SVT (UL 62)

The empty North American cell in the first row is a genuine gap, not a missing lookup: UL 83 does not define an unsheathed PVC-only building wire equivalent to BV or H07V-U, because the American type carries the nylon jacket as part of its construction. Rows 2 and 4 show the nearest North American type with the caveat stated in the cell.

The two flexible-cord rows are developed elsewhere on this site: the sheathed-cord family is covered by the tray-and-cord standards comparison and the control-side equivalent sits with the RVV multi-core PVC cable.

Cross-reference index

The table above settles BV against THHN. The cable on your desk may be neither: H07V-U, 6491X, 60227 IEC 01, RW90 and TW75 all describe single-core PVC builds, and each system writes the size and the temperature class differently. Type the designation you have into the cross-reference index and it returns the code each of the six systems uses, with the voltage base beside it — 450/750 V and 600 V are not the same wire.

Open the cross-reference index →

06What does not translate

Four things survive a building-wire cross-reference as false friends. Each has a specific failure mode attached.

1. A bare letter does not carry a voltage

BV on its own does not fix the voltage: it is 450/750 V under GB/T 5023.3 and 300/500 V under JB/T 8734. H07V fixes 450/750 V only through its 07 field; drop to 05 and the class changes. THHN fixes 600 V by its UL 83 listing rather than by a digit. Never read a voltage off the letters alone — read it off the standard number or the digit field.

2. PVC in one system is not PVC in another

All three systems specify PVC insulation, but they specify it through different compound designations and test regimes. Europe names the compound (PVC Type TI1 for 70 °C, TI3 for 90 °C, to EN 50363-3). China specifies the compound performance in GB/T 5023.1. North America adds a nylon jacket on top, which is not an insulation change but does change the construction. The word "PVC" is common; the specification behind it is not identical.

3. Certification does not travel

CCC in China, CE/DoP in Europe and a UL listing in North America are separate schemes with separate scopes. A cable built to BS EN 50525-2-31 is not thereby acceptable on a project that requires CCC, and a UL listing for one construction does not cover a different build. Where a project turns on mutual recognition, that question belongs to the accepting authority, and we say so rather than answer it ourselves.

4. Conductor class and cross-section are separate decisions

The European letter (U/R/K) and the American construction (stranded or solid) both encode conductor class rather than size, and the metric-to-AWG step is a second, independent decision. Two wires with the same nominal area can differ in strand count and conductor class, which changes the bending radius and the termination. When a project specifies one class and the supply is in another system, convert on class and rating, not on area alone.

Reading the wire's own marking is the ground truth these tables are checked against, and the cable markings decoder works through what each layer of print does and does not prove.

07What this page publishes, and what it will not

The tables above are built from standard documents, standard records and manufacturer datasheets, and the adoption label on the Chinese side — identical adoption of IEC 60227 — is taken from the standard itself rather than inferred. Where a document was not available, the page says so and stops at the standard name: HD 361's text was not obtained, so the European table gives field meanings without clause numbers, and the North American row states the nylon-jacket caveat rather than pretending the types are equal.

What this page does not do is decide a project. It will not tell you that a particular BV wire satisfies a particular H07V or THHN requirement on your job, because that depends on the build, the certificate scope and the accepting authority. Bring us the two specifications and the site conditions, and we will work the comparison against what we actually manufacture.

Send us the code and the standard, and we will work the cross-reference

Give us the standard the enquiry is written to, the type code, the conductor class, the cross-section range and the site conditions. We will come back with the corresponding type and the points where the two standards diverge.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Experienced in cable specification aligned with IEC standards.

How this was written: every figure in this article is checked against the standard or datasheet listed in Sources before publication. Where a value is our own measurement, it is labelled as such.

Sources checked for this article

  • GB/T 5023.1-2008 — PVC-insulated cables up to 450/750 V, Part 1; designation annex, anchor comparison table, and the identical-adoption statement (IEC 60227-1:2007, IDT). Standard record — 温州标准化 GB/T 5023.1-2008.
  • GB/T 5023.3-2008 with IEC 60227-3 — non-sheathed cables for fixed wiring; type list and voltage class. Manufacturer technical table — Jiangsu Huachuang Cable.
  • JB/T 8734 — PVC-insulated wires and flexible cables up to 450/750 V; BV (300/500 V) and BVR (450/750 V) as series types. Manufacturer table — 小猫线缆 wire construction table.
  • BS EN 50525-2-31 — single-core, non-sheathed PVC-insulated cables for fixed wiring; conductor classes and voltage classes. Manufacturer datasheets — Tratos 6491X and Nassau National Cable 6491X.
  • BS 6004 → EN 50525-2-31 code mapping — 6491X to H07V-U / H07V-R and 2491X to H05V-K / H07V-K, both Class 5 flexible, with the 2491X voltage class set by size (0.5–1.0 mm² at 300/500 V; 1.5 mm² and above at 450/750 V) — Caledonian Cables 2491X and Nexans H05V-K (2491x) datasheet, via RS.
  • classicwire, Thermoplastic vs Thermoset Insulated Wire & Cable — North American type-letter table and UL standard assignment for THHN, THWN-2, XHHW-2 and USE-2 — PDF.
  • Southwire SIMpull THHN/THWN-2 — construction (PVC insulation, nylon sheath), 600 V, 90 °C dry / 90 °C wet-or-dry, 75 °C oil, VW-1 and FT-1 ratings — southwire.com datasheet.
  • Sorivo product page, 6491X H07V-R 1.5 mm² — BS EN 50525-2-31, Class 2 stranded copper to IEC 60228, 450/750 V, 70 °C conductor, 160 °C short-circuit, 2500 V AC test — sorivocable.com.
Related product · the building-wire constructions this page maps
6491X / H07V-R PVC Single Core Building Wire
ApplicationFixed wiring in conduit, trunking and switchgear, and the internal wiring of equipment
StandardsBS EN 50525-2-31; conductor to IEC 60228 (Class 2)
ConductorClass 2 stranded copper, 1.5–16 mm²
InsulationPVC Type TI1
Voltage Rating450/750 V Uo/U
Ampacity—
TemperatureAmbient −15…+70 °C; conductor +70 °C, +160 °C short-circuit
CertificationsConfirmed against the certificate for the exact construction and cross-section
THHN 12 AWG Stranded Copper Building Wire
ApplicationBranch circuits and feeders in conduit and cable tray, per the National Electrical Code
StandardsUL 83; NFPA 70 (NEC)
ConductorStranded copper, 14–8 AWG on this range
InsulationPVC insulation with nylon jacket
Voltage Rating600 V
Ampacity20 A (12 AWG, 75 °C column basis)
TemperatureAmbient —; conductor +90 °C dry, +75 °C in wet or oil
CertificationsUL 83 listed for the exact construction
Which type does your specification map to? Send the standard, the type code and the cross-section range and we will answer against them — request a quote.
Q1Is BV the same as H07V-R?

They are close but not identical. BV is the Chinese market name for a PVC single-core building wire, rated 450/750 V under GB/T 5023.3-2008 (as 60227 IEC 01) or 300/500 V under JB/T 8734. H07V-R is the European harmonised type under BS EN 50525-2-31, also 450/750 V, with a Class 2 stranded conductor. Compare them on conductor class, voltage and test regime rather than on the name.

Q2What does the R stand for in H07V-R?

R is the conductor class, not the sheath. In the harmonised code U is a Class 1 solid conductor, R is a Class 2 stranded conductor, and K is a Class 5 flexible conductor. So H07V-R is a 450/750 V PVC building wire with a stranded conductor, which is the construction most fixed building wiring is specified in.

Q3Does THHN have a GB/T equivalent?

No. THHN is defined by UL 83 and belongs to a separate letter system that encodes ratings rather than materials, and it carries a nylon jacket over the PVC insulation that BV and H07V-R do not. There is no GB/T type code that means THHN. What can be compared is the construction, the insulation material, the 90 °C dry rating and the 600 V class — not the type name.

Q4What is the difference between 6491X and 2491X?

Both the conductor class and the voltage class. 6491X covers the rigid and stranded 450/750 V construction — H07V-U and H07V-R. 2491X is the flexible, Class 5 cable: 0.5–1.0 mm² is the 300/500 V H05V-K, while 1.5 mm² and above is the 450/750 V H07V-K. Both names came from BS 6004 and both are now harmonised.

Q5Can a cable to BS EN 50525-2-31 be used on a Chinese-standard project?

Compliance with one system does not carry into another. CCC, CE marking and UL listing are separate schemes with separate scopes, and certification attaches to the exact construction rather than to a family. That determination belongs to the accepting authority on the project, so treat any informal answer as provisional until the authority confirms it.

Q6Why is the North American cell blank for some building-wire types?

Because no genuine equivalent exists. UL 83 does not define an unsheathed PVC-only building wire comparable to BV or H07V-U; the American types add a nylon jacket as part of the construction, which makes them a different build rather than a translated name. The blank tells you to compare on construction and rating instead of on the code.