Flexible PVC insulated and sheathed multi-core cable to GB/T 5023.5-2008 — 2 to 5 cores, 0.75 to 2.5 mm², 300/500 V, with the light-duty 300/300 V version for 0.5 and 0.75 mm².

What a panel builder or equipment manufacturer checks first on an RVV cable — before reading the full specification below.
RVV is the Chinese designation for a flexible PVC insulated and PVC sheathed multi-core cable, and it is defined in GB/T 5023.5-2008 — the part of the GB/T 5023 series that covers flexible cables and cords, equivalent to IEC 60227-5. Under that standard there are two RVV types, and confusing them is the single most common error in this product category: 60227 IEC 52 is the light-duty type at 300/300 V, limited to 2–3 cores and 0.5–0.75 mm²; 60227 IEC 53 is the ordinary-duty type at 300/500 V in 0.75–2.5 mm², which is the construction this page is built around.
That distinction is not pedantry. A 2.5 mm² core cannot be a 300/300 V cable, because the light-duty type does not extend to that cross-section — so a datasheet that lists “300/300 V, 0.5–2.5 mm²” is describing two different products, and a buyer who orders to it may receive either. Table 1 sets out the two types side by side. Where a project needs 0.5 or 0.75 mm² for light duty, we supply the IEC 52 type and mark it as such; where it needs 1.0 mm² or above, or a 4- or 5-core construction, it is IEC 53 at 300/500 V.
The conductor is Class 5 flexible stranded copper to GB/T 3956, which is what makes an RVV cable easy to route and terminate by hand. Insulation is a PVC/D compound and the sheath a PVC/ST5 compound, the two grades GB/T 5023.1 assigns to flexible cables. The finished-cable withstand test follows the voltage class: 1500 V AC for 300/300 V, 2000 V AC for 300/500 V and 2500 V AC for 450/750 V, applied for 5 minutes.
Temperature-wise, the working range is −15 °C to +70 °C with a maximum conductor temperature of +70 °C. The cable is a general-purpose flexible type for indoor installation in conduits, ducts, trunking and equipment wiring. It is not an outdoor cable, not a buried cable and not a continuous-flexing cable: “flexible” describes how the cable is made and installed, not an ability to survive repeated movement.
Two compliance points are worth stating precisely. CCC certification applies to this cable type — PVC insulated cables rated 450/750 V and below to the GB/T 5023 series are in the China Compulsory Certification scope, and the certificate is provided with the shipment. CE does not apply to a cable built to a Chinese standard: where a European equivalent is needed the correct route is the EN 50525 family, and we quote it as a separate product rather than labelling a GB cable as CE. RoHS is a substance restriction and is documented by a test report rather than by a product standard; it is available on request.
For the single most-ordered size in this family, see the RVV 4 Core 1.5 mm² Cable. For the Chinese fixed-installation control cable standard, see the KVV / KVVR / KVVP Control Cable.
More about the manufacturer: About SORIVO →
The part of the GB/T 5023 series covering flexible cables and cords, equivalent to IEC 60227-5 — the standard RVV is actually defined by.
The ordinary-duty RVV type, covering 0.75 to 2.5 mm² in 2 to 5 cores. This is the construction the page is built around.
The light-duty type for 0.5 and 0.75 mm² in 2 or 3 cores — supplied and marked separately, and never mixed with the 300/500 V sizes.
Stranded copper to GB/T 3956 that routes and terminates by hand, which is the point of a flexible PVC cable.
The insulation and sheath compound grades GB/T 5023.1 assigns to flexible cables, rather than the fixed-installation grades.
1500 V AC at 300/300 V and 2000 V AC at 300/500 V for 5 minutes on the finished cable, recorded against the production length.
A working range of −15 °C to +70 °C, with a maximum conductor temperature of +70 °C for continuous operation.
CCC applies to this cable type under the PVC insulated cable scope of the China Compulsory Certification catalogue — the certificate is provided with the shipment.
General-purpose flexible wiring in equipment, panels and buildings, indoors and in dry conditions.
Internal power and control wiring in equipment that has to be assembled by hand, where a Class 5 flexible conductor is easier to route.
Panel wiring for indication, interlocking and low-power circuits in 4- and 5-core constructions.
Fixed indoor circuits inside conduit, trunking and ceiling voids, where a flexible cable is easier to pull than a solid one.
Fan, damper and small pump connections in plant rooms and risers, in dry indoor conditions.
Discrete signal and status wiring where no screen is required; for screened signal circuits see our CY shielded control cable.
Single-phase and small three-phase connections, where the earth core in a 3- or 4-core construction is part of the circuit.
Short flexible leads and adaptor assemblies inside buildings, where a purpose-made flexible cord is not appropriate.
A high-turnover stock item supplied on coils and reels with the sheath colour and core code confirmed on the drawing.
The complete parameter set — the same data our engineers quote from.
| Type | Duty | Rated voltage U0/U | Core count | Cross-sections |
|---|---|---|---|---|
| 60227 IEC 52 (RVV) | Light duty | 300/300 V | 2 to 3 cores | 0.5 – 0.75 mm² |
| 60227 IEC 53 (RVV) | Ordinary duty | 300/500 V | 2 to 5 cores | 0.75 – 2.5 mm², with 4 and 6 mm² available on some constructions |
The two types are separate products with separate voltage classes, and they must not be combined in one specification. In particular, a 0.5–2.5 mm² range cannot sit under a single 300/300 V heading: the light-duty type stops at 0.75 mm². Tell us the duty and the cross-section and we will confirm which type the order is built to, and mark the drum accordingly.
| Cross-section | Available cores | Type |
|---|---|---|
| 0.5 mm² | 2, 3 | 60227 IEC 52 — 300/300 V |
| 0.75 mm² | 2, 3 (IEC 52) or 2, 3, 4, 5 (IEC 53) | Both types are available at this size — the voltage class is confirmed on the order |
| 1.0 mm² | 2, 3, 4, 5 | 60227 IEC 53 — 300/500 V |
| 1.5 mm² | 2, 3, 4, 5 | 60227 IEC 53 — 300/500 V |
| 2.5 mm² | 2, 3, 4, 5 | 60227 IEC 53 — 300/500 V |
0.75 mm² sits on the boundary and can be supplied as either type; the 1.0 mm² row is highlighted because it is the size most often ordered in volume. Core identification follows the standard colour code for the construction, and larger or non-standard combinations are covered by the JB/T 8734 series of industry specifications where the project requires them.
| General Information | |
| Product Name | RVV Multi-Core PVC Control Cable 2–5 Cores |
| Model Designation | 60227 IEC 53 (RVV) — ordinary duty, 300/500 V, this product. 60227 IEC 52 (RVV) — light duty, 300/300 V, available separately for 0.5 and 0.75 mm². |
| Standard | GB/T 5023.5-2008, PVC insulated cables of rated voltages up to and including 450/750 V — Part 5: Flexible cables (cords), equivalent to IEC 60227-5 |
| General Requirements | GB/T 5023.1-2008 |
| Supplementary Standard | JB/T 8734.3, PVC insulated wires and flexible cords of rated voltages up to and including 450/750 V — Part 3: Flexible cords for connection. The JB/T 8734 series covers a wider size and core range than GB/T 5023 and is used as the basis for non-standard combinations. |
| Conductor Standard | GB/T 3956, Conductors of insulated cables |
| Electrical Ratings | |
| Rated Voltage (U0/U) | 300/500 V for 60227 IEC 53; 300/300 V for 60227 IEC 52 |
| Rated Voltage Test (finished cable) | 2000 V AC for 300/500 V and 1500 V AC for 300/300 V, 50 Hz, 5 minutes. 2500 V AC applies to the 450/750 V class, which is not this product. |
| Conductor Type | Class 5 flexible stranded copper to GB/T 3956 / IEC 60228 |
| Conductor Material | Annealed copper to GB/T 3956. The standard specifies conductor resistance and construction rather than a purity figure, so no purity percentage is claimed here. |
| Cross-sections | 0.75 / 1.0 / 1.5 / 2.5 mm² for 60227 IEC 53; 0.5 / 0.75 mm² for 60227 IEC 52 |
| Core Counts | 2 to 5 cores for 60227 IEC 53; 2 to 3 cores for 60227 IEC 52 |
| Insulation Resistance | Manufacturer test value, confirmed against the test report for the selected construction |
| Construction | |
| Insulation Compound | PVC/D compound per GB/T 5023.1 — the grade for flexible cables |
| Sheath Compound | PVC/ST5 compound per GB/T 5023.1 — the grade for flexible cables |
| Sheath Colour | Black, white or grey as standard; other colours to order |
| Core Identification | Standard colour code for the core count, with a green/yellow protective conductor where the construction includes one |
| Outer Diameter | Depends on core count and cross-section; confirmed on the construction drawing |
| Environment | |
| Max. Conductor Temperature | +70 °C continuous |
| Operating Temperature Range | −15 °C to +70 °C |
| Min. Installation Temperature | 0 °C recommended by the manufacturer — PVC becomes brittle below this and a cold bend can damage the insulation without visible signs |
| Bending Radius | 4 × outer diameter for fixed installation (manufacturer recommendation). GB/T 5023 does not set a bending radius for this cable type, so this is guidance rather than a standard requirement. |
| Flame Performance | Single-core vertical flame test to IEC 60332-1 as standard. This is not a flame-retardant product: ZA / ZB / ZC classes per GB/T 19666-2019 require a flame-retardant compound and are specified as ZR-RVV with the class stated. |
| Certification & Logistics | |
| Certification | CCC for this cable type under the PVC insulated cable scope of the China Compulsory Certification catalogue; certificate provided with the shipment. CE does not apply to a cable built to a Chinese standard — a European equivalent is quoted against the EN 50525 family. |
| RoHS | Compliance report available on request. RoHS is a substance restriction documented by a test report, not a product standard. |
| Standard Lengths | 100 m / 200 m / 500 m per coil; cut lengths on request |
| Packaging | Coil, reel or cut length |
| Customization | Core count, cross-section, sheath colour, cut length and customer marking |
| MOQ | 100 m — sample orders available |
| Lead Time | 5–15 working days; stocked configurations 3–5 days |
The two RVV voltage classes are what this specification is really about: 60227 IEC 53 at 300/500 V covers 0.75 to 2.5 mm² and is this product, while 60227 IEC 52 at 300/300 V covers 0.5 to 0.75 mm² in 2 or 3 cores and is supplied separately. The finished-cable withstand test follows the voltage class. Insulation and sheath compounds are the PVC/D and PVC/ST5 grades that GB/T 5023.1 assigns to flexible cables. The bending radius and the minimum installation temperature are manufacturer recommendations, because GB/T 5023 does not set either for this cable type. Final selection should be based on the circuit voltage, the installation method and the applicable local requirements.
The part of the GB/T 5023 series covering flexible cables and cords, equivalent to IEC 60227-5, with the general requirements in GB/T 5023.1-2008. The 60227 IEC 52 and 60227 IEC 53 types are kept apart in the specification rather than merged into one voltage heading.
Request standard reference →PVC insulated cables rated 450/750 V and below to the GB/T 5023 series are within the China Compulsory Certification scope, so CCC applies to this cable type. The certificate covering the ordered construction is provided with the shipment.
Request certificate →Flexible stranded annealed copper to GB/T 3956, with conductor resistance, insulation resistance and the voltage-matched withstand test measured on every production length and recorded. RoHS test reports are available on request.
Request test records →
Because RVV exists in two voltage classes, the release test follows the type rather than a single house figure.
Tell us the duty (IEC 52 or IEC 53), the core count and cross-section, the sheath colour and the quantity.
We confirm core count, cross-section, screening option and quotation within one working day.
Sample for qualification — stocked configurations within a few working days.
5–15 working days; stocked configurations within 3–5 days.
Drum packing, shipping documents and cut lengths on request, with the construction drawing issued for approval before the first production run.
Tell us the duty, core count, cross-section and quantity — we reply within one working day.
The more detail you give, the faster and more accurate quotation. Our engineers reply within one working day.
Thanks — our engineers will reply within one working day.