A national standard can adopt an IEC standard in three different ways, and only one of them lets you swap a cable without checking. GB/T 5023.1-2008 is identical (IDT) to IEC 60227-1:2007 — the model codes match one for one. GB/T 12706.1-2020 is modified (MOD) from IEC 60502-1:2004 — the standard maps, the type code does not. North American codes such as THHN and XHHW-2 are a separate letter system with no GB/T equivalent code at all; only the ratings can be compared. This page is the translation table for the engineer or salesperson moving between the two.
Ask three different people what "IEC 60502-1 cable" means and you get three answers: a buyer means a construction, an engineer means a test regime, and a factory means a type code that may or may not be called the same thing in Chinese. Procurement fails at exactly this seam. A quotation comes back with a GB/T 12706.1 cable against an IEC 60502-1 enquiry, and it is approved because the two standard numbers look interchangeable.
They are not interchangeable as codes. Chinese practice separates three layers that English-language enquiry documents usually merge into one string:
A standard relationship tells you whether the two documents describe the same test regime. It tells you nothing about whether the type code is the same, and nothing at all about whether the certification travels. Engineer and sales staff both need all three, in that order.
The rest of this page supplies the three layers as tables you can look up: the standard families, the adoption relationships, and the letter systems that generate the codes.
Almost every cable specification in the world traces back to one of eight bodies. Four of them are adopters rather than authors; three — the North American UL and NEC pair, Canada's CSA system and the Australian/New Zealand AS/NZS system — stand outside IEC altogether and generate their own type codes. Getting the parent right tells you which document to check first when two specifications disagree.
| Family | Role | What it governs | Examples you will meet |
|---|---|---|---|
| IEC | Parent for most of the world | International base documents for cables and their accessories | IEC 60227 · IEC 60502 · IEC 62930 |
| Chinese GB / GB/T / JB/T | Adopter (IDT / MOD / NEQ) | National standards; GB is mandatory, GB/T is recommended, JB/T is industry level | GB/T 5023 · GB/T 12706 · GB/T 9330 |
| European EN (CENELEC) | Adopter, then re-exporter | EU harmonised standards; adopted nationally as BS EN, DIN EN, NF EN | EN 50525 · EN 50618 · EN 50288 |
| British BS | Mixed | Some British standards are harmonised with CENELEC; some are independent national documents | BS 5467 · BS 6724 · BS 6387 · BS 7671 |
| North American UL + NEC | Independent | UL writes product-safety standards; NEC (NFPA 70) writes the installation code that governs where a listed type may be used | UL 83 · UL 44 · UL 1277 · NEC Article 310 |
| Canadian CSA | Independent | Canada's national system; product parts are numbered separately from the wiring code, and a listing in one country does not carry into the other | CSA C22.2 No. 38 · No. 51 · No. 131 |
| German DIN / VDE | Mostly EN-aligned | National designations that in most cases now run in parallel with the EN version | VDE 0295 · HD 361 designations |
| Australia / New Zealand AS/NZS | Independent, IEC-influenced | National standards with their own type codes, used across Oceania and in mining export work | AS/NZS 5000.1 · AS/NZS 1802 |
The "role" column is the only part that matters for translation work. An adopter's document can be diffed against the parent; an independent system's document cannot.
Chinese practice labels the relationship explicitly on the cover of the standard. There are three labels, and they are not a quality ranking — they describe how much of the parent document survives.
| Label | Meaning | Worked example | What it means for a type code |
|---|---|---|---|
| IDT identical | The national standard is the IEC text, with only editorial changes such as decimal separator or a deleted foreword. | GB/T 5023.1-2008 is IDT to IEC 60227-1:2007. The cover itself carries (IEC 60227-1:2007, IDT). | The type codes correspond one for one. Substitution is a paperwork exercise, not an engineering one. |
| MOD modified | The national standard is built on the IEC text but changes technical content — thickness rules, test parameters, added grades. | GB/T 12706.1-2020 is MOD from IEC 60502-1:2004. The standard record states the relationship directly. | The type codes do not correspond. Sharing the same construction does not mean the same code, and a table value read off one document may not hold in the other. |
| NEQ / independent | The national system is its own construction; the IEC document is at most a reference. | There is no IEC equivalent of the North American building-wire codes. THHN exists under UL 83 and nowhere else. | Nothing maps at the code level. Compare ratings and construction, then decide from scratch. |
The distinction between IDT and MOD is the highest-value sentence on this page. Sales teams get burned by treating a MOD pair as if it were IDT; engineers get burned by treating an IDT pair as if it were MOD and re-verifying work that did not need it.
Chinese type codes are not arbitrary strings; they are built from a small alphabet. What follows is split into the two coding systems you will actually see on a Chinese quotation, because they work differently and mixing them is the most common decoding error.
The current GB/T 5023 series for PVC-insulated cables up to 450/750 V does not name products with letters at all. Its annex on the designation method states the rule in one line: every cable type in the series is designated by a two-digit number placed after "60227 IEC", where the first digit is the basic classification and the second is the specific variant within it.
| Classification | Type | Current designation | 1985-vintage letter code |
|---|---|---|---|
| 0 — fixed wiring, unsheathed | General purpose, single core, rigid conductor | 60227 IEC 01 | BV |
| 0 — fixed wiring, unsheathed | General purpose, single core, flexible conductor | 60227 IEC 02 | RV |
| 0 — fixed wiring, unsheathed | Internal wiring, 70 °C, solid | 60227 IEC 05 | BV |
| 0 — fixed wiring, unsheathed | Internal wiring, 90 °C, solid | 60227 IEC 07 | BV-90 |
| 1 — fixed wiring, sheathed | Light PVC sheathed cable | 60227 IEC 10 | BVV |
| 5 — general purpose sheathed cord | Light PVC sheathed cord | 60227 IEC 52 | RVV |
| 5 — general purpose sheathed cord | Ordinary PVC sheathed cord | 60227 IEC 53 | RVV |
| 5 — general purpose sheathed cord | Heat-resistant 90 °C, ordinary | 60227 IEC 57 | RVV-90 |
| 7 — special purpose sheathed cord | Round PVC sheathed lift cable | 60227 IEC 71c | TVV |
| 7 — special purpose sheathed cord | Oil-resistant PVC sheathed, screened | 60227 IEC 74 | RVVYP |
Columns 3 and 4 are the two sides of the comparison table in the standard's informative Annex B, which pairs each current two-digit designation with the letter code used by the 1985/1986 editions. Ten of the eighteen rows are shown here.
Where letter codes are still used — in the older GB 5023 editions, in JB/T 8734 today, and throughout the power-cable and control-cable families — the letters follow a fixed logic. The standard's annex groups them by function rather than by position:
So BVR reads as fixed-wiring, PVC, flexible conductor; RVV as flexible cord, PVC insulation, PVC sheath; RVVYP as the oil-resistant, screened version of the same cord.
Power cables use the same letter logic applied to a thicker construction. The most common low-voltage code you will meet from a Chinese supplier is YJV: XLPE insulation, PVC sheath, copper conductor, for fixed installation. Change one letter and you change one material:
The construction logic here is standard across the GB/T 12706 series and is the same logic you will see on the YJV / YJLV 0.6/1 kV XLPE power cable page, which also states the series' relationship to IEC 60502-1 explicitly.
Control cables have their own declared alphabet, and unlike the other two families it is written out in a numbered clause. The series code is K; everything after it is material and construction:
| Position | Code | Meaning | Worked code |
|---|---|---|---|
| Series | K | Control cable | K… |
| Material — conductor | (omitted) | Copper is the default and is not written | — |
| Material — insulation | V / YJ | PVC / cross-linked polyethylene | KV… / KYJ… |
| Material — sheath | V / Y | PVC / polyethylene or polyolefin | KVV / KVY |
| Construction — screen | P / P2 / P3 | Braided / copper tape / aluminium-plastic film screen | KVVP · KVVP2 · KVVP3 |
| Construction — flexibility | R | Flexible structure for mobile laying | KVVR |
| Armour digit | 2 / 3 | Double steel-tape armour / steel wire armour | KVV22 · KVV32 |
| Outer sheath digit | 2 / 3 | PVC oversheath / PE or polyolefin oversheath | KVV23 |
Read the digits as a pair, not a number: in KVV22 the first 2 is the armour and the second 2 is the oversheath. The standard's own worked examples include KVV, KYJVP2, KVV22, ZB-KVVRP and KYJY33.
North American building-wire codes are the hardest to translate because they encode ratings, not materials. Each letter is a claim about performance, and the claims are cumulative. The convention runs left to right:
| Letter | Claim | Notes |
|---|---|---|
| T | Thermoplastic insulation | In practice PVC. The default insulation family. |
| X | Cross-linked (thermoset) insulation | XLPE. Holds its rating wet or dry, unlike PVC. |
| R | Thermoset rubber insulation | Used in the RHW family. |
| H | Heat resistant, 75 °C | One H is the 75 °C claim. |
| HH | Heat resistant, 90 °C in dry locations | The second H raises the dry rating. |
| W | Moisture resistant — rated for wet locations | Without W, a type is dry-location only. |
| N | Nylon outer jacket | Abrasion and oil resistance; lowers pulling friction. |
| -2 | 90 °C in both wet and dry locations | A wet-location rating, not a version number. |
Letter conventions and the temperature/location ratings follow the type-letter system used with NEC Article 310; per-type construction is cross-checked against manufacturer construction sheets.
Applying the table: THHN is thermoplastic, high-heat, nylon-jacketed — a 90 °C dry conductor under UL 83. THWN-2 adds the wet rating and the "-2", becoming 90 °C wet and dry. XHHW-2 is cross-linked, high-heat, wet-rated, and the "-2" makes it 90 °C in both states under UL 44; some manufacturers hold listings under both UL 44 and UL 83, which is why the standard reference on a data sheet can differ between makers. USE-2 is the underground service-entrance type under UL 854.
The practical consequence for a Chinese supplier is blunt: there is no GB/T code that means THHN. A GB/T 12706.1 power cable and a UL 83 building wire can be compared on conductor, insulation material, temperature rating and voltage, and nothing more. For the type-by-type comparison, the THHN / UL 83 building wire guide walks through one family in detail.
European harmonised designations solve the same problem the other way round: instead of letters that claim ratings, the code is positional and each field states a fact. The format is H + voltage + insulation + sheath + "-" + conductor.
| Field | Code | Meaning |
|---|---|---|
| Prefix | H | Harmonised type — the designation is common across the CENELEC countries |
| Voltage | 03 | 300/300 V |
| Voltage | 05 | 300/500 V |
| Voltage | 07 | 450/750 V |
| Insulation | V | PVC · V2 marks the 90 °C PVC grade |
| Insulation | R | Natural or synthetic rubber (EPR) |
| Insulation | Z | Cross-linked, halogen-free compound |
| Sheath | V / N / Z | PVC / polychloroprene / cross-linked halogen-free |
| Conductor | U / R / K / F | Solid Class 1 / stranded Class 2 / fine-wire Class 5 / extra-flexible Class 5·6 |
Field meanings are consistent across the manufacturer and industrial-wiring references listed in Sources. HD 361's own text was not obtained for this article, so no clause numbers are quoted here.
So H07RN-F reads as harmonised, 450/750 V, rubber insulation, polychloroprene sheath, extra-flexible conductor — the heavy portable rubber cable that appears on European jobsites. H07V-K is the single-core, PVC, fine-wire panel wire at the same voltage, and it is the closest European analogue of the Chinese BVR family and of UL 1015 / MTW on the American side. British practice keeps a parallel numeric designation: 6491X covers the 450/750 V H07V-U and H07V-R constructions, while 2491X is the flexible Class 5 name — the 300/500 V H05V-K at 0.5–1.0 mm² and the 450/750 V H07V-K at 1.5 mm² and above.
This is the table to bookmark. It maps every naming system this site covers, product family by product family — China, IEC, Europe and the UK, North America, Canada, and Australia/New Zealand — and it deliberately leaves cells blank where no genuine equivalent exists. A blank is information: it tells you the comparison has to be made on ratings rather than on names.
| Product family | China (GB/T, JB/T) | IEC | Europe / UK | North America | Canada (CSA) | Australia / New Zealand |
|---|---|---|---|---|---|---|
| Single-core building wire, unsheathed | BV / BVR 60227 IEC 01 | IEC 60227-1 | H07V-U · H07V-R 6491X | THHN · THWN-2 UL 83 | RW90 · TW75 CSA C22.2 No. 38 | V-90 AS/NZS 5000.1 · 5000.2 |
| XLPE power cable, 0.6/1 kV | YJV · YJLV GB/T 12706.1 | IEC 60502-1 | BS 5467 (PVC bedding) BS 6724 (LSZH bedding) | — | TECK90 CSA C22.2 No. 131 | AS/NZS 5000.1 4961 (neutral-screened) |
| Flexible PVC cord, sheathed | RVV GB/T 5023.5 · JB/T 8734 | IEC 60227-5 | H05VV-F · H03VV-F 318-Y · 218-Y | SJT · SVT UL 62 | — | — |
| Control and signal cable | KVV · KVVP · KYJVP2 GB/T 9330 | — | LiYY · LiYCY (German-style designation) | TC · PLTC UL 1277 | — | AS/NZS 5000.3 |
| PV DC cable, 1.5 kV | PV1-F | IEC 62930 | H1Z2Z2-K EN 50618 | PV Wire UL 4703 | — | — |
| Fire-resistant circuit integrity | NH-type power cable | IEC 60331 series | BS 6387 · BS 8491 | UL 2196 | — | AS/NZS 3013 (system, not cable) |
| Heavy portable rubber cable | YZ · YC | IEC 60245 series | H07RN-F | SOOW · SJOOW UL 62 | — | — |
| Mining / trailing cable | UC · UCP | — | — | ICEA S-75-381 | — | AS/NZS 1802 |
Blank cells mark a genuine gap, not a missing lookup. The control-cable row carries a scope-level observation: IEC 60227's structure list is organised around PVC-insulated cable types rather than around "control cable" as a category, which is why the IEC column is empty rather than filled with an equivalent series number. The two right-hand columns follow the same rule. The Canadian column stays blank wherever a construction has no published CSA type of its own, because Canada's parts are written around native types rather than as translations of IEC families. The Australian column lists two part numbers for the building-wire row on purpose: whether AS/NZS 5000.1 or 5000.2 governs a given building cable turns on the voltage marking printed on the cable itself, so the two are named together rather than resolved here.
Mining and trailing cable is the row that shows why a blank column is not a gap in the table: the Australian standard appears under Australia/New Zealand because that is the system that publishes it, and the Europe / UK cell is empty for the same reason the Canadian cell is empty elsewhere — no European document of this kind exists to write there.
The naming systems behind these columns are each worked through in full on this site. The British pair in the Europe column is worked through in the BS 5467 vs BS 6724 comparison; the North American letter system, in the THHN, THWN-2 and XHHW-2 comparison; the harmonized documents behind the European column, in HD 603 S1 and HD 620 S2; the German column, in DIN VDE 0250 vs 0276; the Canadian column, in CSA C22.2 No. 38 vs No. 131; and the two right-hand columns, in AS/NZS 5000.1 vs AS/NZS 3013. The PV row is developed in the IEC 62930 vs EN 50618 comparison and, on the Chinese side, in the H1Z2Z2-K vs PV1-F selection piece; the shipboard layer that sits between the power-cable row and the control row is opened out in IEC 60092 shipboard cable; and the fire-testing systems behind the circuit-integrity row are set side by side in BS 6387 vs IEC 60331.
Cross-reference index
This page puts eight standard families on one table. If the cable in front of you carries a code the table does not name — an OEM designation, a line from a customer schedule, or a type from a seventh system — enter it in the cross-reference index. It returns the code each of the six systems uses for that build, and the IDT / MOD / NEQ label that says whether the two codes actually correspond.
Four things survive a standard cross-reference as false friends. Each one has a specific failure mode attached to it.
A cable can be built to a standard and hold no certification, and the certification bodies recognise each other only where they have said so. CCC, CE marking and UL listing are separate systems with separate scopes. A CE declaration does not make a cable acceptable on a project that requires CCC, and a CCC certificate does not substitute for a UL listing in a North American inspection. Certification scope is also construction-specific — a certificate for one conductor material, screen type and cross-section range does not cover a different build. Where a project turns on mutual recognition, that question belongs to the accepting authority, and we say so rather than answer it ourselves.
China's flame-retardant and fire-resistant scheme is a national classification; Europe's CPR scheme is a construction-product classification with its own letter grades; IEC's flame tests are test methods, not classes. The three are not on a common scale, and a conversion table claiming to map a Chinese class onto a CPR Euroclass should be treated with suspicion. Match the underlying test method instead — for the halogen and smoke acid tests that separate LSZH from ordinary PVC, the XLPE vs LSZH insulation-versus-sheath comparison follows the test family in detail.
Metric cross-section and AWG are both nominal designations, and the "nearest" AWG to a metric size is not electrically identical — strand count, conductor class and the resulting current rating can differ even where the physical area is close. When a project specifies one scale and the supply is in the other, convert on current rating and voltage drop, not on area alone.
Chinese and IEC practice writes the rating as U0/U — the phase-to-earth and phase-to-phase values, with Um reserved for the maximum system voltage. North American practice writes a single number, such as 600 V. The two are not a straight translation, and a system's nominal voltage is not the same as its maximum equipment voltage; treating them as the same figure is how a cable ends up specified for a voltage class it does not cover.
Reading a cable's own marking is the ground truth these tables are checked against, and the cable markings decoder works through what each layer of print on a drum does and does not prove.
The tables above are built from standard documents and standard records, and the adoption labels — IDT, MOD, NEQ — are taken from the standards themselves rather than inferred. Where a document was not available, the page says so and stops at the standard name: HD 361's text was not obtained, so the European table gives field meanings without clause numbers, and the IEC column for control cables is left blank rather than filled with an assumed equivalent.
The two right-hand columns follow the same discipline. Both are built from the scope statements of the standards themselves and from the type designations those standards and their users publish, and both stop at the standard name wherever a document could not be obtained: no Australian or Canadian entry appears here that is not carried by the standard's own text or by a manufacturer's published type list, and the Canadian cells are limited to the CSA parts whose own scope names the type directly. A cell is left blank rather than filled with a type that merely looks similar.
What this page does not do is decide a project. It will not tell you that a particular GB/T cable satisfies a particular IEC or UL requirement on your job, because that depends on the build, the certificate scope and the accepting authority. Bring us the two specifications and the site conditions, and we will work the comparison against what we actually manufacture.
Give us the standard the enquiry is written to, the type code, the conductor material, the cross-section range and the site conditions. We will come back with the corresponding Chinese type and the points where the two standards diverge.

Only when the Chinese standard is an identical adoption of the IEC one. GB/T 5023.1-2008 is IDT to IEC 60227-1:2007, so the type codes correspond one for one. GB/T 12706.1-2020 is only modified from IEC 60502-1:2004, so the standard maps but the type code does not — check the construction and the test values, not just the number.
V means polyvinyl chloride, and it can appear twice for two different jobs. In BVR, the V is the PVC insulation. In RVV, the first V is insulation and the second V is the PVC sheath. In the control-cable system the same letter plays the same two roles, which is why KVV is PVC-insulated and PVC-sheathed.
No. THHN is defined by UL 83 and belongs to a separate letter system that encodes ratings rather than materials. There is no GB/T type code that means THHN. What can be compared is the construction, the insulation material, the 90 °C dry rating and the 600 V class — not the type name.
They describe how a national standard adopts an IEC standard. IDT means identical, allowing only editorial changes. MOD means the technical content was modified. NEQ means the national system is effectively its own document. The label is printed on the standard itself, and it is the first thing to read when two specifications are being compared.
Compliance with one system does not carry into another. CE marking, CCC and UL listing are separate schemes with separate scopes, and certification also attaches to the exact construction rather than to a family. That determination belongs to the accepting authority on the project, so treat any informal answer as provisional until the authority confirms it.
Compare them on current rating and voltage drop rather than on physical area. Metric cross-section and AWG are both nominal designations, and the nearest equivalent often differs in strand count and conductor class, which changes the rating. A cable that looks like the same size on paper can carry a different current in practice.