Shielded vs Unshielded Cable: Braid, Foil and Transfer Impedance

A braided screen and a foil screen are not two grades of the same thing, and cable standards do not treat them as one. IEC 61156-6 publishes transfer impedance limits by grade: Grade 1 — which requires a braid plus foil construction — is specified at 10 mΩ/m at 1 MHz rising to 100 mΩ/m at 100 MHz, while Grade 2, which a single foil layer can meet, is specified at 50 mΩ/m rising to 1 000 mΩ/m over the same range. The gap between the two widens with frequency: about 5× at 1 MHz and about 10× at 100 MHz. Shielding gets worse as frequency rises — the opposite of what most people assume. This guide covers what each screen construction does, how to read the numbers behind the word “shielded”, how to terminate a screen properly, and why a cable that moves needs a different answer from a cable that does not.

Published 2026-09-22Updated 2026-09-22 Reading ~15 minLevel: Specification

01A shield that is not terminated is an antenna

The short answer

Walk a plant floor with a fault logger and the pattern is familiar: analogue readings that drift when a large drive starts, encoders that lose counts as a crane passes, a position loop that trips without a fault code anyone can reproduce. The usual diagnosis is noise and the usual remedy is “fit a shielded cable”. The usual outcome is a screen that changes nothing, because a screen only performs as a screen when three separate things are all true at once: the construction suits the frequency of the interference, the screen is continuous along the run, and it is terminated in a way that gives the interfering current somewhere to go.

Get any one of the three wrong and the result is a cable that is heavier, stiffer and more expensive than the unshielded alternative, with no measurable benefit. Two of the three are decided on the datasheet and can be checked before the order is placed. The third — termination — is decided in the cabinet and at the motor junction box, and is where most field failures actually originate.

This article stays on sourced ground throughout. Every transfer impedance figure below is a limit published in a standard or stated on a manufacturer data sheet, and the installation rules are taken from drive manufacturers' engineering guidance and from the PROFINET cabling guideline, not from general practice. Where a common claim could not be traced to a primary source we say so rather than repeat it.

02Foil, braid and served wire: what each construction does

Three screening constructions dominate industrial cable, and they fail in different ways.

WHAT EACH SCREEN DOES coverage, strength, and the failure mode that follows from the same construction Foil on film COVERAGE Complete — no apertures STRENGTH High frequency and electrostatic; pair-to-pair isolation FAILS BY Work-hardens and cracks when it flexes; higher resistance Tinned copper braid COVERAGE About 85 %, up to 90 % optimised STRENGTH Low resistance, so strong at lower frequency; survives flexing FAILS BY Weave apertures leak once they stop being small vs the wavelength Served wire COVERAGE Lower than an equivalent braid STRENGTH Tolerates torsion — the winding opens and closes as it twists FAILS BY Less coverage, more resistance; wrong answer for linear travel Foil plus braid COVERAGE Complete, from the foil layer STRENGTH Both ends of the frequency range; braid gives a bondable surface FAILS BY Bulk, stiffness and cost; the foil still limits the flex life Coverage alone does not rank these constructions. The foil covers the most and protects the least at low frequency, because what a screen does is set by conductance as well as coverage — and transfer impedance is the parameter that ranks them. A served screen is for torsion, not for a drag chain: a linear back-and-forth axis is served by a braid at a flat braid angle.
A shield is a current path, and each construction is a different compromise along that path. Foil covers completely but has comparatively high resistance and cracks under repeated bending. Braid gives up coverage — typically about 85 % optical, up to about 90 % for optimised weaves — and buys conductance and mechanical toughness, but its apertures leak once they stop being small compared with the wavelength. Served wire is the torsion answer, not the linear-travel answer. Layering foil under a braid covers both ends of the frequency range and gives a surface that can be bonded around its circumference.

A foil screen is a thin aluminium layer bonded to a polymer film, wrapped around the core or around individual pairs. Its defining property is complete coverage: there are no apertures for a field to leak through, which makes it effective against electrostatic and high-frequency interference, and it is why individual pairs inside a multi-pair data cable are foil-wrapped to stop crosstalk between pairs. It is light, thin and inexpensive. Its weaknesses follow from the same construction: the metal layer is thin, so its resistance is comparatively high, and it is mechanically fragile. Under repeated bending the foil work-hardens and cracks. A foil screen is a sound choice for a fixed installation and a poor one for a continuously moving axis.

A braid screen is woven tinned-copper wire. Because it is a weave, it cannot reach complete coverage — a well-made industrial braid is typically specified in the region of 85 % optical coverage, and igus states a maximum of 90 % for its chainflex range. What the braid gives up in coverage it gains in conductance and in mechanical robustness: far lower resistance than foil, and the ability to survive handling, crushing and flexing. Its limitation is frequency. Once the apertures between the woven strands stop being small compared with the wavelength, the weave leaks, and the braid's advantage over foil narrows as frequency rises. For the classic industrial problem — a motor feeder, a drive output cable, or a control circuit running beside power — braid is the usual default and it is usually the right one.

A served or spirally wrapped screen is wire wound helically around the core in one direction rather than woven. Its advantage is that it tolerates twisting, because the winding can open and close as the cable is rotated — which is why cable makers specify a wrapped screen, not a braid, for torsional applications such as robot joints. Its disadvantage is that it offers less coverage and higher resistance than a braid. A point worth correcting, because it circulates widely: a spiral screen is not the standard answer for a drag chain. A linear back-and-forth travel application is served by a braid with a deliberately flat braid angle, and igus states explicitly that the same screen should not be used for linear travel and for torsion. Cables sold for energy chains are commonly braid-screened for this reason.

Table 1 — Screening constructions, and what each one is actually for
ConstructionCoverageStrengthFailure modeSuited to
Aluminium foil on polymer filmComplete — no aperturesHigh-frequency and electrostatic interference; pair-to-pair isolation inside multi-pair cableFoil cracks under repeated bending; thin metal layer has comparatively high resistanceFixed instrumentation and data runs; inner screens inside a multi-pair construction
Tinned copper braidTypically around 85 %, up to about 90 % for optimised braidsLow resistance, so strong at lower frequencies; mechanically tough; survives flexing and handlingWeave apertures leak as frequency rises and the strand spacing is no longer small against the wavelengthThe industrial default: motor feeders, drive output cables, control circuits near power
Served or spirally wrapped wireLower than an equivalent braidTolerates torsion — the winding can open and close as the cable twistsLess coverage and higher resistance than braid; not the right answer for linear travelTorsional duty, such as robot joints and rotating axes
Foil plus braid, layeredComplete from the foil; aperture-controlled by the braidAddresses both ends of the frequency range, and the braid provides a surface that can be terminated properlyLarger diameter, heavier, stiffer and more expensive; the foil layer remains the flex-limiting elementHigh-interference sites and any installation where the screen has to be bonded around its circumference

03Transfer impedance: the number behind the word “shielded”

Coverage tells you how much of the core is covered. Transfer impedance tells you how well the screen performs, and it is the parameter that separates a specified screen from a claimed one. Transfer impedance, usually written ZT, is the voltage induced on the conductors inside the screen per unit of current flowing on the screen itself. Lower is better.

The value of the parameter is that cable standards publish limits for it by grade. IEC 61156-6, the sectional specification for symmetrical pair and quad cables used in work area wiring, grades screened cable by transfer impedance and by coupling attenuation, and the grades differ by construction rather than by marketing language. The published limits are these.

Table 2 — Transfer impedance limits for symmetrical data cable, published in IEC 61156-6
FrequencyGrade 1 — satisfied by braid plus foilGrade 2 — satisfied by a single foil layerRatio Grade 2 / Grade 1
1 MHz10 mΩ/m50 mΩ/m5×
10 MHz10 mΩ/m100 mΩ/m10×
30 MHz30 mΩ/m200 mΩ/m6.7×
100 MHz100 mΩ/m1 000 mΩ/m10×
Limits as published in IEC 61156-6 and as reproduced on manufacturer data sheets. Transfer impedance is measured by the triaxial method, IEC 62153-4-3. Two independent manufacturer data sheets for Grade 1 energy-chain cable state 10 mΩ/m at 10 MHz, 30 mΩ/m at 30 MHz and 100 mΩ/m at 100 MHz, matching those three standard limits. Two Grade 2 data sheets state the full Grade 2 row of 50 / 100 / 200 / 1 000 mΩ/m. One point does diverge: both Grade 1 data sheets we checked publish 15 mΩ/m at 1 MHz against a standard limit of 10 mΩ/m. The table states the standard value, and the divergence is recorded here rather than smoothed over.

Three conclusions follow from that table, and each one is counter-intuitive enough to be worth stating plainly.

  • A screen does not become better behaved at higher frequency; it becomes worse. Both grades climb monotonically with frequency. From roughly 1 MHz upward a braid's transfer impedance rises at approximately 20 dB per decade, because coupling becomes dominated by the inductance of the weave apertures once those apertures are no longer small compared with the wavelength.
  • The Grade 1 to Grade 2 gap is not a constant. It is about 5× at 1 MHz and about 10× at 100 MHz, and it is not a straight line in between. A specification that says “Grade 2 or better” therefore says different things at different frequencies.
  • The test method has a usable frequency range, and it is shorter than most people assume. The triaxial method measures only the magnetic component of the transfer impedance; the electrostatic, capacitive component is covered separately, in IEC 62153-4-8. It is generally suitable up to about 30 MHz on a 1 m sample and up to about 100 MHz on a 0.3 m sample, which corresponds to an electrical length below roughly one sixth of the wavelength. A figure quoted at 100 MHz on a 1 m specimen is therefore not the same measurement as a figure quoted at 100 MHz on a 0.3 m one.
TRANSFER IMPEDANCE vs FREQUENCY IEC 61156-6 limits — both axes logarithmic, and lower is better 1 10 100 1000 mΩ/m 1 MHz 10 MHz 100 MHz 5× 10× Grade 1 — braid plus foil Grade 2 — single foil layer rises at ≈20 dB per decade above 1 MHz Manufacturer data sheets commonly quote a more conservative 15 mΩ/m for Grade 1 at 1 MHz; the standard value is 10 mΩ/m. These figures come from the triaxial method, which measures the magnetic component only — the capacitive component is covered separately by IEC 62153-4-8.
Both grades climb monotonically with frequency, which is the opposite of what most people assume: a screen does not become better behaved at higher frequency, it becomes worse. The Grade 1 to Grade 2 gap is about 5× at 1 MHz and about 10× at 100 MHz, and it is not a straight line in between — so a specification that says “Grade 2 or better” says different things at different frequencies. Read the figure with the test method in mind too: the triaxial method is generally usable to about 30 MHz on a 1 m sample.

One further point is worth carrying into a purchase discussion. IEC 61156-6 notes that a screen DC resistance of 30 mΩ/m or less can be used as an indicator that the Grade 2 transfer impedance requirement is met — but it cannot substitute for the measurement. The distinction matters, because DC resistance is trivially measurable on a bench and transfer impedance is not. A supplier who offers only the resistance figure has given you an indicator, not a qualification.

04Coupling attenuation, and why a grade never travels alone

Transfer impedance is the screen's own performance. It is not the only parameter that decides whether a cable survives an EMC environment, because a screen cannot compensate for a poorly balanced pair. That is what coupling attenuation captures: the combined effect of the screen and the balance of the conductor pair, measured with an absorbing clamp under IEC 62153-4-5, or by the triaxial method. IEC 61156-6 grades it by type, using a value quoted over the 30–100 MHz band with a defined roll-off above it.

The coupling attenuation types, in order of screening performance

Type I is specified as 85 dB, Type Ib as 70 dB, Type II as 55 dB and Type III as 40 dB, each over 30–100 MHz and each following the same frequency dependence above the anchor band. For screened cables, Type II is the minimum requirement; Type III is associated with unscreened constructions, where external crosstalk control is the concern rather than shielding. In construction terms the same standard notes that Type I is met by a braid plus foil design, Type Ib by a braided cable with a lighter braid where maximum screening is not needed, and Type II by a foil screen of specified characteristics. A cable datasheet that quotes a transfer impedance grade and no coupling attenuation type has told you about half of the EMC story.

Converting transfer impedance into shielding attenuation

System budgets are usually written in decibels, and a screening attenuation can be derived from the transfer impedance for an electrically short assembly as as = 20 · log (150 Ω / ZTE), where the 150 Ω is the standardised impedance of the measuring arrangement defined in IEC 62153-4-15. The exercise is worth doing once, because it makes the cost of a poor termination obvious: the screen is only as good as the weakest element in the current path, and the weakest element is very often not the cable.

Screen stated rather than impliedSend us the installation: what carries the cable, what is beside it, whether it moves, and where each end of the screen will be bonded — we will state the screen construction, the optical coverage and the applicable standard on the quotation, and tell you which of our constructions suits the route.

05Terminating the screen: one end, both ends and the 360° rule

The screen has to carry the interfering current away, and where it is allowed to go depends on the circuit. Two rules cover most industrial cases, and they are opposite to each other for a reason.

Instrumentation and analogue signal circuits are bonded at one end, normally the control-room or panel end. The reason is not shielding theory but loop physics: any difference in earth potential between the field device and the panel drives a current along the screen, that current magnetically couples into the signal pair, and the result appears at the input as differential-mode noise that a PLC's common-mode rejection cannot remove. Bonding at one end breaks the loop. Where lightning protection is required, the far end may be terminated through a capacitor or a surge device rather than left fully open, so that the screen stays bonded at the panel and the protection is provided by a component rather than by earthing the far end.

Drive output cables are bonded at both ends, around the full circumference. This is not a preference. Drive manufacturers' engineering guidance states that screened cable is mandatory between drive and motor for compliance with emission standards such as IEC 61800-3, and that the screen must be connected at both ends — at the drive and at the motor — with 360° termination. The purpose is to give the common-mode current generated by the inverter's fast switching edges a controlled, low-impedance return path, instead of letting it discharge through motor bearings, pipework and building structure. The same guidance is specific about cable construction: a symmetrical multicore cable with low leakage capacitance, and where the cross-section exceeds roughly 10 mm², a cable with three equipotential conductors rather than one. Reinforced or screened single-core cables should not be used for this duty.

Why a pigtail defeats the screen, stated as an arithmetic

The 50 mm that undoes the screen

A pigtail — the practice of folding the screen back, twisting it into a lead and landing it under a terminal screw — is the single most common cause of radiated-emission failures in the field, and the reason is a comparison of inductances. A lead of about 50 mm has an inductance of roughly 43 nH by the standard estimate, of the same order as the 1 nH per millimetre rule of thumb. At 10 MHz that is an impedance of about 2.7 Ω. Set it against the screen it is supposed to extend: one metre of Grade 1 cable presents 10 mΩ at the same frequency. The termination is roughly two orders of magnitude worse than the screen, and no amount of additional cable can compensate for it. The bottleneck is the last 50 mm of the installation, not the cable on the drum.

This is why the connection is made around the circumference rather than at a point. The PROFINET cabling and interconnection guideline requires 360° shielding on its connectors as a specification item — M12, M8 and RJ45 variants alike — with the stated purpose of screening against EMI from rotating machines. The same geometry is achieved at a gland or a screen clamp: the braid is brought into full peripheral contact with a conductive body that is itself bonded to the enclosure.

Table 3 — Screen termination by circuit type
CircuitBondingWhereReason
Analogue instrumentation, 4–20 mA, thermocouple, RTDOne end onlyPanel or control-room end; field end isolatedBreaks the earth loop that would otherwise drive screen current into the signal pair as differential-mode noise
Digital communication, industrial Ethernet, fieldbusBoth ends, 360°At each connector shell or screen clamp on entry to the enclosureMaintains the screen as a continuous conductive path; the guideline requirement for the connectors is 360° shielding
Drive output, drive to motorBoth ends, 360°RF-bonded to the drive enclosure or gland plate, and to the motor terminal boxProvides the return path for common-mode current generated by the inverter, protecting bearings and limiting radiated emission
Intrinsically safe loop with a barrier or isolatorSafe-area end onlyAt the panel, with the hazardous-area end isolatedThe barrier earth reference is part of the protection concept; the screen follows it rather than bypassing it

Two practical notes apply across all four rows. First, the screen is not a protective conductor. It carries EMC current and may carry fault current, but the protective earth function must be provided by a dedicated conductor with the cross-section the installation standard requires — a screen must never be the only earth path. How the earthing system itself is arranged and sized is a separate design exercise, worked through for hybrid generation sites in earthing and bonding to IEC 60364 and NEC 690. Second, the value of the construction is decided by a measurement at commissioning, not by inspection: a screen-to-earth resistance reading that is unexpectedly high at either end indicates a painted bracket, a folded-back drain wire, or a clamp that is not making contact around the circumference.

06Motion changes the answer: linear travel and torsion want different screens

In a fixed panel the screen is chosen for the interference. On a moving axis, survival comes first, and the screen that survives depends on how the cable moves — which is not one thing.

The distinction is made explicitly by igus in its technical guidance on screens in moving applications. For linear travel in an energy chain, the correct screen is a braid with a deliberately flat braid angle, because a flat weave opens only minimally over the bend radius and keeps the screening window small throughout the stroke. The failure mode to avoid is a braid wound at too acute an angle, which expands over the radius and breaks apart; the broken strand ends then migrate inside the cable and can cause conductor-to-conductor faults. For torsional duty, such as a robot joint, the guidance is the opposite: use a wrapped screen, where the wires are laid in one direction rather than woven, so the screen can open and close as the cable rotates.

This is the point at which the widely repeated claim that drag chains “always use a spiral shield” falls apart. Both statements cannot be true, and the primary source is unambiguous: linear travel and torsion take different screens, and the linear case takes a braid. A cable sold for energy chain duty is normally specified as braid-screened, and the data sheets confirm it — a braid-screened industrial Ethernet cable intended for energy chains states a continuous-flex minimum bend radius of 15 × the outer diameter and a flexing temperature range of −20 °C to +50 °C, against −40 °C to +80 °C for fixed installation. The temperature band is part of the specification for the same reason the screen is: a moving cable is a different product from a static one.

Table 4 — Environment, recommended screen and the reason
EnvironmentScreen recommendationWhy
Fixed instrumentation panelFoil, or foil plus braidThe foil's complete coverage is the strongest high-frequency answer and there is no flexing to crack it
Fixed drive or motor feederBraid, or foil plus braidLow resistance at the frequencies involved, and a surface that can be bonded 360° at both ends
Energy chain, linear travelBraid with a flat braid angleA flat weave holds its screening window through the stroke; a steep weave expands over the radius and fractures
Robot joint, torsional dutyWrapped or served screenThe winding opens and closes as the cable rotates instead of work-hardening
Signal pair in a strong low-frequency magnetic fieldTwisted pair plus screen, with physical separationA screen alone does not stop a power-frequency magnetic field; pair geometry and distance are what reduce the coupling

07What an unshielded cable is actually for

Unshielded is sometimes the right answer

The comparison in the title of this article is not a choice between a good option and a bad one. Unshielded cable is the correct specification in a large share of industrial installations, and specifying a screen where it is not needed buys stiffness, diameter, cost and a new failure mode without buying performance.

A screen earns its place when the circuit is a source of interference that has to be contained, when it is a victim of interference that has to be excluded, or when both are true at once. Drive output cables are the clearest case of the first. Analogue instrumentation running near heavy power is the clearest case of the second. A control circuit inside a cabinet fed from a filtered supply, with its own separation from power wiring, is frequently neither: at that point an unshielded multicore cable with the right conductor geometry does the job, and the money and the installation hours are better spent on separation and on pair twisting than on screen coverage nobody will terminate properly.

Two caveats keep that from being a licence to drop the screen everywhere. First, separation is the alternative, not an additional option — if the screen is removed, the routing has to be reviewed against the installation standard's requirements for physical separation between power and signal circuits, with crossings at right angles where they cannot be avoided. Second, a screen that is specified but terminated badly performs worse than no screen at all in one respect: it adds a path for circulating currents into a system that was not designed to carry them. Where a screen is fitted, the termination rules in section 05 are not optional extras.

For plant wiring where a screen is required, a braided screen over a flexible control-cable construction covers the general case — CY industrial flexible PVC shielded control cable is built this way, with a tinned copper braid over the laid-up core bundle and roughly 85 % optical coverage. Where the circuit is a data channel rather than a control circuit, the construction question becomes a category question, and the balance parameters in section 04 become as important as the screen: Cat6A and Cat8 S/FTP shielded data cable is specified against IEC 61156-5 and -6; the transfer impedance grade limits in Table 2 come from Part 6 of that series.

08What belongs on a shielded-cable datasheet

The word “shielded” on its own carries almost no information. Five items turn it into a specification, and a supplier who cannot produce them has not specified the screen.

Table 5 — From “shielded” to a usable specification
ItemWhat it should sayWhy it matters
Screen construction and materialAluminium foil, tinned copper braid, served wire, or a named combination such as S/FTPIt determines which frequency range the screen addresses and whether it can survive the installation's movement
Optical coverage, if braidedA percentage, stated as a typical figure for the constructionCoverage is the usual industry measure for a braid; the figure differs markedly between a general-purpose and an optimised weave
Transfer impedance, if the cable is a data cableA grade against IEC 61156-6, or measured values at stated frequenciesIt is the parameter that actually describes screen performance, and the grade corresponds to a construction, not to a price band
Coupling attenuation type, if the cable is screenedThe type, over its anchor bandIt captures the combined effect of screen and pair balance, which transfer impedance alone does not
Flex rating, if the cable movesA cycle rating with the test conditions, or a stated continuous-flex bend radius and flexing temperature rangeA cycle figure without its test conditions is not a comparison; a bend radius of 15× the outer diameter is a different product from one rated for fixed installation

It is worth being explicit about where we stand on the last row, because it is the one where claims are least often substantiated. Optical coverage and transfer impedance are measurements; a cycle rating is a test result that depends entirely on the test conditions — travel length, bend radius, speed and acceleration all change the number that comes out. When we state a figure for a flexible construction we state the condition it was measured under, and where a cycle rating has not been run on a specific construction we say that rather than quoting a general figure.

09Six questions for the quotation

  • What is the screen, precisely? Foil, braid, served, or a named combination. If the answer is “shielded”, the next four questions are the ones that matter.
  • What is the optical coverage of the braid? A percentage, from the construction drawing rather than from a general range.
  • Is there a transfer impedance grade or a measured value? For a data cable, a grade against IEC 61156-6; for a control cable, a measured value at a stated frequency, or an honest statement that no such figure is available. A DC resistance figure is an indicator for the Grade 2 requirement, not a substitute for the measurement.
  • Where does the screen get bonded, and can the gland make peripheral contact? The construction and the termination hardware are one decision. A braid that will be landed under a terminal screw has been specified as a screen and installed as an antenna. Cable glands designed for screen contact, and the accessories that go with them, are part of the same specification — see EMC cable glands and shield termination for VFD and servo cable for the termination side in detail.
  • Does the cable move, and how? Linear travel and torsion take different screens, and a cable rated for fixed installation is not a substitute for either.
  • Has the screen been continuity-checked on the finished cable? The screen is a conductive path, and the check belongs in the release test rather than in an assumption. Batch and metre markings belong on the same question, because a screen fault found a year later has to be traceable to the drum it came from.

The screen is a small part of a cable's cost and a large part of its behaviour. Specifying it as a construction, with the numbers that describe it and the termination method that will be used, costs a handful of questions at the enquiry stage and prevents the failure mode that no one can diagnose afterwards — a plant full of cables that are nominally shielded, none of which is doing anything.

Specify the screen, not just the word

Send us the circuit, the environment and the motion, and we will come back with the screen construction, the coverage or grade that goes with it, and the termination hardware that suits the route. If the cable is a control or data construction, the balance parameters are part of the same answer.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Experienced in cable specification aligned with IEC standards.

Sources checked for this article

  • IEC 61156-6:2020, Multicore and symmetrical pair/quad cables for digital communications — Part 6: Symmetrical pair/quad cables with transmission characteristics up to 1 000 MHz — Work area wiring — Sectional specification — the source of the transfer impedance grade limits in Table 2, the coupling attenuation types in section 04, the triaxial-method reference and the screen DC resistance indicator — IEC Webstore
  • IEC 62153-4-3:2013+AMD1:2024, Metallic communication cable test methods — Part 4-3: Electromagnetic compatibility (EMC) — Surface transfer impedance — Triaxial method — the test method behind every transfer impedance figure quoted, and the source of the statement that it measures the magnetic component only, plus its usable frequency range against sample length — IEC Webstore
  • IEC 62153-4-5:2021, Metallic communication cable test methods — Part 4-5: Electromagnetic compatibility (EMC) — Screening or coupling attenuation — Absorbing clamp method — the method behind the statement in section 03 that coupling attenuation is measured with an absorbing clamp, and its 30 MHz to 1 000 MHz working range — IEC Webstore
  • IEC 62153-4-8:2018, Metallic cables and other passive components — Test methods — Part 4-8: Electromagnetic compatibility (EMC) — Capacitive coupling admittance — the separate capacitive path referred to in section 03, measured on the same triaxial set-up as transfer impedance and required where the screen is a loose single braid — IEC Webstore
  • IEC 62153-4-15:2021+AMD1:2024, Metallic cables and other passive components test methods — Part 4-15: Electromagnetic compatibility (EMC) — Test method for measuring transfer impedance and screening attenuation — or coupling attenuation with triaxial cell — the triaxial-cell method, including the standardised impedance of the measuring arrangement referred to in section 03 — IEC Webstore
  • Nidec, Guide to best practices: motor-drive systems (engineering documentation, 2018) — the requirement for screened cable between drive and motor for IEC 61800-3 compliance, 360° termination at both ends, the 10 mm² threshold for single versus three equipotential conductors, and the prohibition on screened single-core cables for this duty — Nidec, PDF
  • REO UK, Complying with IEC/EN 61800-3: good EMC engineering practices in the installation of power drive systems — RF bonding of the motor cable screen to the drive enclosure and to the motor terminal box, the definition of 360° termination, and the cable-length guidance against the highest significant switching harmonic — REO UK, PDF
  • igus technical guidance, Shielded cables in moving applications — the distinction between braided screens for linear travel and wrapped screens for torsion, the flat-braid-angle requirement, the maximum 90 % optical coverage of the chainflex braid, and the failure mechanism caused by steep braid angles — igus
  • PROFINET, Cabling and Interconnection Technology guideline — the 360° shielding requirement specified on M12, M8 and RJ45 connection hardware, with the stated purpose of screening against EMI — and, from the same guideline family, the interconnection tables used for the digital-communication row of Table 3
  • Siemens SIMATIC NET product information, article 6XV1840-2AH10, IE FC TP Standard Cable GP 2x2 (Type A) — a braid-screened SF/UTP industrial Ethernet cable whose published transfer impedance at 10 MHz is 10 mΩ/m, matching the IEC 61156-6 Grade 1 limit — Siemens product information
  • Lapp data sheets ETHERLINE P EC FD Cat. 5e (DB2170433EN), ETHERLINE FD P FC Cat. 5 (DB2170894EN), ETHERLINE FD P Cat. 5e (DB2170289EN and DB2170489EN) — energy-chain cables whose published Grade 1 and Grade 2 transfer impedance rows and Type I / Type Ib coupling attenuation values are the independent check on the Table 2 limits, plus the 15 × outer diameter continuous-flex bend radius and the flexing temperature range quoted in section 06
  • Draka (Prysmian), Screening and balance performance of data cables and related screen designs (white paper) — the four coupling attenuation types with their 30–100 MHz anchor values and the frequency roll-off above 100 MHz, restated from the IEC 61156-5 and -6 series; also the construction-to-grade correspondence quoted in section 04 — Prysmian, PDF
  • BDA Connectivity, EMC of Ready-Made Connecting Devices, 2020 IWCS conference paper — the same four coupling attenuation types tabulated with their frequency dependence, used as the second independent statement of the type values — BDA Connectivity, PDF

How this was written: every figure in this article is traced to the standard or the manufacturer document listed above. Where a value is a manufacturer's published specification rather than a standard limit, the text says so; where a widely circulated claim could not be traced to a primary source, the article says that instead of repeating it.

Related product · Screened control and data cable constructions
CY Industrial Flexible PVC Shielded Control Cable
ApplicationPVC insulated, PVC sheathed screened flexible control cable — German LiYCY equivalent; British CY designation
StandardsConductor to IEC 60228 (DIN VDE 0295 cl. 5) · flame retardance to IEC 60332-1-2 · EN 50525-1 family; non-harmonised industrial control cable type
Conductor0.14–2.5 mm², typically 2–50 cores depending on size
InsulationPVC — EN 50363-3 insulating compound · EN 50363-4-1 sheathing compound
Voltage Rating300/500 V designation · 350 V max. operating voltage
Ampacity—
Temperature—
Certifications—
Screen TypeTinned copper wire braid over the laid-up core bundle; continuity checked on the finished cable
Optical CoverageApproximately 85 %
Screen TerminationIntended for termination at the gland or screen clamp at both ends for EMC purposes
Cat6A / Cat8 S/FTP Shielded Data Cable — LSZH, CPR Eca/Dca
Application—
StandardsISO/IEC 11801-1 · EN 50173 · IEC 61156-5 and IEC 61156-6 · EN 50288-10-1 · ANSI/TIA-568.2-D
Conductor23 AWG solid bare copper; 22 AWG on some Cat8.2 constructions
Insulation—
Voltage Rating—
Ampacity—
Temperature—
Certifications—
CategoriesCat6A (500 MHz) · Cat8.1 (2 000 MHz) · Cat8.2 (2 000 MHz)
Screen StructureS/FTP or F/UTP on Cat6A; U/FTP or F/UTP minimum on Cat8.1; F/FTP or S/FTP on Cat8.2
Impedance100 Ω nominal
JacketLSZH, with CPR reaction-to-fire classification
Both are supplied against the circuit and the environment rather than against the word “shielded”. Send us the route and the termination arrangement and the construction is confirmed against it, including the gland or clamp that will make the screen connection.
Q1What is the difference between foil and braid shielding?

A foil screen has complete coverage because it is a continuous metal layer, which makes it effective against high-frequency and electrostatic interference, but the metal is thin so its resistance is comparatively high and it cracks under repeated bending. A braid screen is woven tinned copper, typically around 85 % optical coverage, with much lower resistance and far better mechanical toughness, but its weave apertures leak as frequency rises. Data cable standards capture the difference in grades: under IEC 61156-6 a braid plus foil construction meets Grade 1 transfer impedance, while a single foil layer can only meet Grade 2.

Q2Should the cable shield be grounded at one end or both ends?

It depends on the circuit. Analogue instrumentation and 4–20 mA signal circuits are bonded at one end, normally the panel end, to break the earth loop that would otherwise drive screen current into the signal pair as differential-mode noise. Drive output cables are bonded at both ends with 360° termination, because the screen has to carry the inverter's common-mode current back to its source; drive manufacturers' engineering guidance states this as a requirement for compliance with emission standards such as IEC 61800-3. Digital communication circuits follow the both-ends rule.

Q3Why is a pigtail shield connection a problem?

Because a short lead has inductance that swamps the screen it is supposed to extend. A 50 mm lead is roughly 43 nH, which at 10 MHz is an impedance of about 2.7 Ω, while one metre of Grade 1 screened cable presents 10 mΩ at the same frequency. The termination is about two orders of magnitude worse than the cable, so the screen's performance is set by the last few centimetres rather than by the cable construction. Above roughly 1 MHz the connection must be made around the full circumference.

Q4Does shielding get better or worse as frequency rises?

Worse, which is the opposite of what most people assume. Both transfer impedance grades in IEC 61156-6 rise monotonically with frequency: Grade 1 goes from 10 mΩ/m at 1 MHz to 100 mΩ/m at 100 MHz, and Grade 2 from 50 to 1 000 mΩ/m. From roughly 1 MHz upward a braid's transfer impedance climbs at about 20 dB per decade, because coupling becomes dominated by the inductance of the weave apertures once they are no longer small compared with the wavelength.

Q5Can a shield be used as the protective earth conductor?

No. A screen carries EMC current and may be called upon to carry fault current, but the protective earth function has to be provided by a dedicated conductor sized to the installation standard. Treating a screen as the only earth path is a safety error as well as an EMC one, and it is prohibited by the installation requirements for the circuits concerned. The screen and the protective conductor are two functions that may share a route, but not a cross-section.

Q6Does Sorivo supply screened control and data cable?

Yes. The CY industrial flexible shielded control cable uses a tinned copper braid over the laid-up core bundle with approximately 85 % optical coverage, built to IEC 60228 conductors with flame retardance to IEC 60332-1-2, and is intended for screen termination at the gland or screen clamp at both ends for EMC purposes. For data circuits, the Cat6A and Cat8 S/FTP range is specified against ISO/IEC 11801-1, EN 50173 and IEC 61156-5 and -6; the transfer impedance grades quoted above come from Part 6 of that series.