German cable standards · Type designation code · 2026

DIN VDE 0250 vs DIN VDE 0276: Reading German Cable Type Codes Correctly

Two DIN VDE numbers sit next to each other on more German cable data sheets than any others, and they do not govern the same object. DIN VDE 0250 is the wire, cord and flexible-cable series. DIN VDE 0276 is the power-cable series, and most of it is the German face of a CENELEC document. Both use the same letter code, both begin with N, and a line item that names one when the project means the other is answered with the wrong construction. This page decodes the letters position by position, maps every live part of both series, and shows where the German code meets IEC, GB and BS naming.

Published 2026-10-18 Updated 2026-10-18 Level: reference Reading time ~19 min
The short answer

DIN VDE 0250 and DIN VDE 0276 share one letter code but govern different objects. DIN VDE 0250 covers insulated power Leitungen — installation wires, cords and heavy-duty flexible cables, from NYM in Part 204 to the rubber-sheathed NSSHÖU and NSHTÖU in Parts 812 and 814. DIN VDE 0276 covers Starkstromkabel — power cables, and most of its published parts are German versions of a CENELEC HD document: Part 603 is HD 603 S1 for 0,6/1 kV distribution cable and Part 620 is HD 620 S1 for 3,6/6 kV to 20,8/36 kV.

The code itself is defined separately in DIN VDE 0292, the German version of HD 361 S3. Read it left to right from the conductor outward: N = cable to a German standard, A = aluminium conductor (absent = copper), Y = PVC, 2X = XLPE, then any concentric conductor or screen, then the armour, then the outer sheath.

01One code, two standard families

German cable names are construction descriptions, not product names. NYCWY 3 × 120 SM/70 0,6/1 kV is a complete specification in twelve characters: it tells you the conductor material, the insulation compound, the presence of a concentric copper screen in wave form, the conductor shape, the core count, the cross-sections and the voltage basis. That density is why the German code survives in tenders written outside Germany, and it is also why it goes wrong so often: the letters are read as a brand or a family, and the two standards that actually contain the requirements are never opened.

Those two standards are the ones in the title of this page. DIN VDE 0250 is titled Isolierte Starkstromleitungen — insulated power wires and cords — and it is a national series. DIN VDE 0276 is titled Starkstromkabel — power cables — and most of its parts are German adoptions of a CENELEC harmonization document, so the requirements originated in Brussels and the German part is one national edition of them. A third family sits alongside both: DIN VDE 0281, the German version of HD 21, and DIN VDE 0282, the German version of HD 22, for the harmonised wires and cords that carry H designations such as H05VV-F and H07RN-F.

The practical consequence is a rule that is worth writing down before reading a data sheet: find out which series the part number belongs to, then read the letters. An installation cable and a power cable can carry codes that look as though they belong to the same family — NYM and NYY differ by one letter — while sitting at different voltages, in different standards and under different duties. The wider mapping against IEC, BS, UL and Chinese GB designations is in the cross-reference hub for this series; this page is the German-specific decoder inside it.

Table 1 — Which German standard series governs which object
Object being boughtGoverning seriesPart that usually appearsWhat the code describes
Fixed installation wiring inside a buildingDIN VDE 0250 (Leitungen)0250-204 (NYM), 0250-214 (NHXMH), 0250-215 (NHMH)The insulation and sheath compounds of a wire, plus its fire behaviour
Heavy-duty flexible cable: reeling, mining, stageDIN VDE 0250 (Leitungen)0250-802, 0250-812, 0250-813, 0250-814The rubber sheath compound and the mechanical duty it is built for
LV power cable for distribution, 0,6/1 kVDIN VDE 0276-603 (= HD 603 S1)NYY, NAYY, NYCY, NYCWY, NA2XYThe complete cable build: conductor, insulation, bedding, armour, outer sheath
MV power cable, 3,6/6 kV to 20,8/36 kVDIN VDE 0276-620 (= HD 620 S1)N2XSY, N2XS2Y, NA2XS(F)2Y classThe same layers, plus conductor and insulation screens and their metallic screen
Fire-performance LV power cableDIN VDE 0266Quoted by construction, not by a short codeBehaviour in fire for LV power cable
XLPE-insulated installation cable, 0,6/1 kVDIN VDE 0262Quoted by constructionXLPE insulation with a thermoplastic PVC sheath
PVC wires and cords to 450/750 V, harmonisedDIN VDE 0281 (= HD 21)H05VV-F, H05V-K, H07V-U, H07V-RThe harmonised designation letters themselves
Cross-linked and rubber wires to 450/750 VDIN VDE 0282 (= HD 22)H07RN-F, H05SJ-K, H07G-UThe same, for rubber and silicone compounds
The type code itselfDIN VDE 0292 (= HD 361 S3)—How the letters are to be built and in what order
Current rating and unit conversionDIN VDE 0276-1000—Not a construction: the current-carrying tables and conversion factors
The type names in column three are the ones suppliers publish against each part. A standard fixes the requirements for a construction; it does not publish a closed list of trade names, so the same letters are occasionally quoted against a neighbouring part. When that happens, the part number on the data sheet wins over the type name in the tender.

02The letter decoder, position by position

The letters are read from the conductor outward, following the build order of the cable. The first letter is almost always N, which does not describe a material at all: it means the cable is made to a German standard. A bracketed (N) is the opposite claim — the cable is in alignment with the standard rather than made to it, which is a real distinction when a submittal has to demonstrate conformance.

After the conductor and insulation letters come the metallic layers, then the armour, then the outer sheath. The conductor form is appended to the cross-section rather than sitting in the letter string: RE is a round solid conductor, RM round stranded, SE sector solid and SM sector stranded, with V for a compacted conductor and H for a hollow one.

Table 2 — The Kurzzeichen: what each letter means, and where position changes it
LetterMeaningWhere it appears
NCable made to a German standardFirst position
(N)Cable in alignment with a German standard — not a claim of conformanceFirst position
AAluminium conductor; its absence means copperImmediately after N
YPVC insulationInsulation position
2YThermoplastic PE insulationInsulation position
XCross-linked PVC insulationInsulation position
2XXLPE — cross-linked polyethylene insulationInsulation position
HXCross-linked halogen-free polymer compoundInsulation position and outer-sheath position — same letters, two layers
HField-limiting conductive layers over the conductor and over the insulationMV cables; a field control, not a screen
CConcentric copper conductorAfter the insulation
CWConcentric copper conductor applied in wave form (Wellmantel)After the insulation
CEConcentric copper conductor over each individual coreAfter the insulation, on multicore cable
SCopper screenMV cables, after the insulation
SEField-limiting layers plus a copper screen over each individual coreMV, on multicore cable
(F)Screen is longitudinally watertightAttached to the screen
BArmour of steel tapeArmour position
RArmour of galvanised round steel wires — the German cable's SWAArmour position
FArmour of galvanised flat steel wiresArmour position
GCounter-helix or retaining helix of galvanised steel tapeWith the armour
FOverhead line bundleEarly position, and against DIN VDE 0276-626 — a different cable entirely
FECircuit integrity — the build retains its insulation under fireAfter the armour
YPVC outer sheath — or a PVC protective sheath between screen and armourSheath position
2YPE outer sheathSheath position
11YPUR outer sheathSheath position
Compiled from a German cable manufacturer's designation reference and a second manufacturer's harmonised-designation handbook. Both list the same letters; the German-language source is the one that publishes the conductor-form letters and the worked examples.
Read the position, not the letter Four letters appear twice with unrelated meanings, and each one has caused a wrong submittal somewhere: F is an overhead line bundle in one position and galvanised flat-steel-wire armour in another; Y is PVC insulation inside the cable and a PVC sheath outside it; HX is a cross-linked halogen-free compound whether it is the insulation or the outer sheath; and SE inside an MV cable's screen description has nothing to do with SE as a sector-shaped solid conductor at the end of a cross-section. A decoder that works letter by letter without positions will read some German codes exactly backwards.

03Reading a power-cable line item

Take the worked example the German reference itself uses: NYCWY 3 × 120 SM/70 0,6/1 kV. Six blocks, in build order.

READ FROM THE CONDUCTOR OUTWARD NYCWY 3 × 120 SM/70 0,6/1 kV N Cable made to a German standard Kabel nach Norm Y PVC insulation Isolierung aus Polyvinylchlorid (PVC) CW Concentric copper conductor, wave-formed Konzentrischer Leiter aus Kupfer, wellenförmig Y PVC outer sheath Außenmantel aus Polyvinylchlorid (PVC) 3 × 120 SM/70 Three 120 mm² sector-shaped stranded cores, plus a 70 mm² concentric 3 Adern 120 mm² sektorförmig mehrdrähtig + 70 mm² konzentrisch 0,6/1 kV Rated voltage U0/U Nennspannung The trailing SM is the conductor form: sektorförmig mehrdrähtig — a sector-shaped stranded conductor. The same reading gives NA2YSEY 3 × 70 SE/16 5,8/10 kV, an aluminium cable quoted at 5,8/10 kV.
The six blocks of NYCWY 3 × 120 SM/70 0,6/1 kV, from the worked example in a German manufacturer's designation reference. Nothing in the code says which standard it is made to — that is the part the data sheet has to tell you.

Two things about that example are easy to miss. The first is that the concentric copper conductor is written into the middle of the letters, between the insulation and the sheath, because that is where it physically sits; a code that puts it at the end is describing a different build. The second is the trailing /70 on the cross-section: the concentric conductor has its own cross-section, and it is sized for the earth-fault duty rather than for the load, which is why it does not simply repeat the phase size.

Table 3 — The 0,6/1 kV codes that fill German and European quotes
CodeConductorInsulationConcentric / screenArmourOuter sheath
NYYCopperPVC——PVC
NAYYAluminiumPVC——PVC
N2XYCopperXLPE——PVC
NA2XYAluminiumXLPE——PVC
NA2X2YAluminiumXLPE——PE
NYCYCopperPVCConcentric Cu, over each core—PVC
NYCWYCopperPVCConcentric Cu, wave-formed—PVC
N2XRYCopperXLPE—Steel wirePVC
N2XSYCopperXLPECopper screen—PVC
N2XS2YCopperXLPECopper screen—PE
The last four rows are the medium-voltage family, where the code adds S for the copper screen and a final Y or 2Y to say whether the outer sheath is PVC or PE. Nothing in the naming marks the voltage; that always comes from the rating written at the end of the line, and the two must agree.

The same construction travels under different names depending on the naming tradition the supplier was brought up in. A copper conductor with XLPE insulation, steel wire armour and a PVC sheath is N2XRY in German, YJV22 or YJV32 in Chinese GB/T usage and simply “SWA armoured XLPE cable” in British construction language. That is expanded on the cross-reference page for the British armoured pair, BS 5467 vs BS 6724, where the same layer stack is described under two sheath compounds.

04DIN VDE 0276 and the European spine behind it

DIN VDE 0276 is a family of power-cable standards in which almost every part is the German edition of a CENELEC HD document. The part number is German; the requirements were agreed in Brussels. That matters commercially, because it means a German part number and its HD source can be quoted interchangeably in a tender as long as the edition is the same — and it matters for the decoder, because the HD number tells you which document a manufacturer's type test is actually being run against.

Part 603 is the one that appears on almost every German low-voltage data sheet. Its published German edition is the 2010-03 version, 112 pages, carrying the title Starkstromkabel — Teil 603: Energieverteilungskabel mit Nennspannung 0,6/1 kV; Deutsche Fassung HD 603 S1:1994/A3:2007, Teile 0, 1, 3-G und 5-G, and it replaced DIN VDE 0272. Its scope sentence describes cables used in underground power distribution networks, mainly for public distribution. The full HV 603 S1 story, and the corresponding HD 620 S1 story for medium voltage, is on the HD 603 / HD 620 cross-reference page; what matters here is that the German part number is a pointer to it.

Table 4 — The published parts of DIN VDE 0276 and the CENELEC document behind each
PartGerman title (short form)German version ofObject
0276-603Energieverteilungskabel mit Nennspannung 0,6/1 kVHD 603 S1LV distribution cable
0276-604Starkstromkabel mit verbessertem Verhalten im Brandfall für KraftwerkeHD 604 S1LV power-station cable, fire behaviour
0276-605Ergänzende PrüfverfahrenHD 605 S1Supplementary test methods
0276-620Energieverteilungskabel mit extrudierter Isolierung, 3,6/6 kV bis 20,8/36 kVHD 620 S1MV distribution cable
0276-621Energieverteilungskabel mit getränkter PapierisolierungHD 621 S1Paper-insulated MV cable
0276-622Starkstromkabel mit verbessertem Verhalten im Brandfall, 3,6/6 kV bis 20,8/36 kVHD 622 S1MV cable, fire behaviour
0276-626Isolierte Freileitungsseile für oberirdische VerteilungsnetzeHD 626 S1Insulated overhead bundles
0276-627Vieladrige und vielpaarige Kabel für die Verlegung in Luft und in ErdeHD 627 S1Multicore and multipair cable
0276-632Kabel mit extrudierter Isolierung über 36 kV bis 150 kVHD 632 S1HV extruded cable
0276-633Prüfungen an Ölkabeln mit PapierisolierungHD 633 S1HV oil-filled cable
0276-634Prüfungen an GasinnendruckkabelnHD 634 S1HV internal gas pressure
0276-635Prüfungen an GasaußendruckkabelnHD 635 S1HV external gas pressure
0276-1000Strombelastbarkeit, Allgemeines Umrechnungsfaktoren— no HD sourceCurrent rating and conversion factors
Titles and editions taken from the published German standards index and cross-checked against the commercial publication records for Parts 603 and 604. Several parts carry an amendment appended to the title, which is how the edition has to be quoted when a submittal asks for conformance.
Check before quoting The safest way to quote a 0276 cable is to write both numbers: the German part and the HD document it is the German version of, each with its edition year. A line that says only “to VDE 0276” leaves roughly a dozen parts open, and a manufacturer who builds to a different part can still sign it.

05DIN VDE 0250: what is actually in the wire series

DIN VDE 0250 is the German national series for insulated power wires, cords and flexible cables. It is not a harmonised series: it never became an HD document, and the types in it are German products rather than European ones. Part 1 carries the general requirements for the whole series; the numbered parts below it each describe one product family.

Two of them carry most of the traffic. Part 204 is the PVC installation cable NYM — the standard German in-wall and in-conduit cable, in the J version with a green-yellow protective conductor and the O version without one. Part 214 is NHXMH, the halogen-free installation cable with improved behaviour in fire, which is what a German project asks for when the specification says “halogen-free” rather than “PVC”. Part 215 covers NHMH, a second halogen-free installation type with special fire properties.

The rest of the series is where the German preference for special-purpose flexible cable shows. Parts 802, 812, 813 and 814 describe rubber-sheathed heavy-duty cables — stage cable, mine and plant cable, hose-type multicore and reeling or trailing cable — and it is this group that made DIN VDE 0250 known outside Germany, because Germany is unusual in publishing detailed design rules for flexible reeling and material-handling cable.

Table 5 — DIN VDE 0250, part by part
PartGerman titleWhat it is
0250-1Isolierte Starkstromleitungen — Allgemeine FestlegungenGeneral requirements for the whole series
0250-102Wärmebeständige PVC-Verdrahtungsleitung in ZwillingsausführungHeat-resistant PVC twin wiring
0250-106ETFE-AderleitungETFE single-core wire
0250-201StegleitungFlat “staircase” wiring for surface runs
0250-204PVC-Installationsleitung NYMThe German installation cable: NYM-J and NYM-O
0250-206PVC-Mantelleitung mit TragseilPVC sheathed cable on a supporting wire
0250-210BleimantelleitungLead-sheathed wire
0250-212Geschirmte PVC-Leitung, U0/U 3,6/6 kVScreened PVC wire at medium voltage
0250-213Dachständer-EinführungsleitungRoof-stand service entry wire
0250-214Installationsleitung NHXMH mit verbessertem Verhalten im BrandfallHalogen-free installation cable
0250-215Installationsleitung NHMH mit speziellen Eigenschaften im BrandfallHalogen-free installation cable, special fire properties
0250-502Wärmebeständige Silikon-FassungsaderHeat-resistant silicone core
0250-602Sonder-GummiaderleitungSpecial rubber single-core
0250-603Gummi-PendelschnurRubber pendant cord
0250-802TheaterleitungStage and theatre cable
0250-806Gummischlauchleitung NMHVÖURubber hose-type cable
0250-809Gummi-FlachleitungFlat rubber cable
0250-811Gummischlauchleitung NSHCÖURubber hose-type cable, heavy duty
0250-812Gummischlauchleitung NSSHÖUHeavy rubber-sheathed cable for plant and mining duty
0250-813LeitungstrosseMulticore rubber hose-type cable
0250-814Gummischlauchleitung NSHTÖUReeling and trailing cable for drum duty
Titles as published, with the series' own part numbering. Parts outside 204 and 214 are rarely quoted in a building tender, which is exactly why a line that says “to DIN VDE 0250” without a part number is close to meaningless.
The bracketed prefix (N)YM-J is not a typographical variant of NYM-J. German data sheets use the bracketed (N) to mean a cable built in alignment with the standard rather than to it, and the layout that appears alongside is usually sold as such. A submittal offering (N)YM-J where the specification said NYM-J is offering a cable whose maker is not claiming conformance to DIN VDE 0250-204 — which is a decision for the person who signed the specification, not for the supplier.

06NYM, NHXMH and (N)YM side by side

All three are 300/500 V installation cables for fixed wiring inside a building, and all three appear in the same tender. They are not interchangeable, and the difference is in the compounds.

NYM is PVC insulated and PVC sheathed, black outside, built to DIN VDE 0250-204. Its conductor is Class 1 solid to IEC 60228 at the smaller sections and Class 2 stranded at the larger ones; the cores are identified to DIN VDE 0293-308; the flame test is the single-wire vertical test to DIN VDE 0482-332-1-2, the German face of EN 60332-1-2; the fixed temperature range runs from −40 °C to +70 °C. NHXMH is the halogen-free answer: XLPE insulation, a halogen-free flame-retardant outer sheath in light grey, built to DIN VDE 0250-214, with the same core identification. Because it is halogen-free it can carry a CPR declaration, and a manufacturer's brochure for its own NHXMH quotes class Dca-s1b,d2,a1.

The distinction that catches people is not the material but the test. The flame test on NYM proves that a single wire does not propagate flame along its own length. The halogen-free claims on NHXMH are separately tested — halogen content, smoke density and acidity — and they are properties of the smoke, not of the circuit. Neither cable promises that the circuit keeps working during a fire; that is a circuit-integrity duty and it belongs to a different family of standards entirely, which is the subject of the fire-test cross-reference page.

Table 6 — Three installation cables a German tender can ask for
AttributeNYM-J / NYM-ONHXMH-J / NHXMH-O(N)YM-J
Standard quotedDIN VDE 0250-204DIN VDE 0250-214In alignment with DIN VDE 0250-204
Rated voltage300/500 V300/500 V300/500 V
Core insulationPVCXLPEPVC
Outer sheathPVC, blackHalogen-free flame-retardant compound, light greyPVC
ConductorClass 1 to IEC 60228; Class 2 stranded at the larger sectionsRound solid or round stranded to DIN VDE 0250Quoted by construction
Core identificationDIN VDE 0293-308DIN VDE 0293-308DIN VDE 0293-308
Vertical flame testDIN VDE 0482-332-1-2 / EN 60332-1-2VDE 0472-804 method C / IEC 332-1Stated by the maker
Halogen-freeNoYes, to VDE 0472-815No
Smoke densityNot claimedVDE 0472-816Not claimed
Fixed temperature range−40 °C to +70 °CQuoted on the maker's data sheetQuoted on the maker's data sheet
Circuit integrity under fireNot claimedNot claimed by the installation-cable standardNot claimed
The CPR class is deliberately absent from the table. It is declared per construction rather than per type name, so it has to be read from the Declaration of Performance for the cable actually ordered. The halogen-free and smoke-density tests are quoted with their VDE 0472 part numbers because that is how the German data sheets present them; the equivalent EN and IEC methods are published separately.

07Where the harmonised H designations fit

The H designations — H05VV-F, H07V-R, H07RN-F — come from a different system, agreed across CENELEC rather than nationally. Germany adopted them twice over: first as DIN VDE 0281 for the PVC wires and DIN VDE 0282 for the cross-linked and rubber wires, and today as the DIN EN 50525 series, adopted in German practice as DIN VDE 0285-525-2-xx. A German data sheet for a harmonised wire therefore carries three identities at once: the H designation, the EN 50525 part, and the DIN VDE number.

Germany also kept its own short designations for the same products, and they are still printed. A manufacturer's handbook of the harmonised code lists the pairs directly: NYA and NYAF against H07V-U and H07V-K, NYMHY against H05VV-F, NMHöuNSHöu against H07RN-F, N4GA against H07G-U, and N2GAFU against H05SJ-K. Seeing one of those older codes on a drawing is not evidence of an obsolete cable, but it does mean the drawing and the current standard have to be reconciled before the order goes out.

The important gap is the one the harmonised system never covered. NYM, NHXMH, NSSHÖU and NSHTÖU are German types with no H designation. They are national products, they are specified by their German part number, and there is no H-code substitute that a buyer can simply swap in. The wider harmonised-wire picture, including how the H designations map onto IEC 60227 and IEC 60245, is on the building-wiring cross-reference page.

08The German code against IEC, EN and GB

The type code is German; the cable usually is not. Most 0,6/1 kV cable sold into Europe and Asia is built to the IEC 60502-1 basis and then labelled with whichever national code the customer reads — NYY or N2XY in German terms, VV or YJV in Chinese GB/T terms, or a plain construction phrase such as “XLPE/SWA/PVC” in British usage. The naming traditions were built independently by three national standards bodies, and the shorthand was never agreed internationally even where the underlying construction requirements overlap.

The consequence for procurement is that matching by name fails and matching by standard works. Two cables built to IEC 60502-1 and GB/T 12706 are generally interchangeable even when one is labelled N2XY and the other YJV. The conductor classes line up across IEC 60228 and its Chinese counterpart, and the flame-propagation tests line up across the IEC 60332 series and its Chinese counterpart. What does not line up is the code, so the useful question on any line item is not “which name is this” but “which standard and which construction is this”.

Table 7 — One construction, four naming traditions
ConstructionGerman (VDE)IEC / EN basisChinese (GB/T)British style
Copper, PVC insulated, PVC sheathedNYYIEC 60502-1VVPVC/PVC
Copper, XLPE insulated, PVC sheathedN2XYIEC 60502-1YJVXLPE/PVC
Aluminium, XLPE insulated, PVC sheathedNA2XYIEC 60502-1YJLVAl XLPE/PVC
Copper, XLPE insulated, steel wire armoured, PVC sheathedN2XRYIEC 60502-1YJV22 / YJV32XLPE/SWA/PVC
Copper, XLPE insulated, copper screen, PE sheathed, MVN2XS2YIEC 60502-2MV equivalent quoted by constructionMV screened
The Chinese column is the GB/T naming tradition, not a claim that a GB/T standard is identical to the German one. The German code describes the layers; the Chinese code describes the layer materials in its own abbreviation set; the British entry describes the same layers in words. The page for the Chinese naming system itself is YJV and the Chinese power-cable names.
Where this costs money The failure mode is not a wrong temperature. It is a line item answered with the wrong family — an installation cable priced against a power cable because both begin with N and Y, or a PVC cable delivered against a halogen-free specification because the buyer recognised the letters NYM and stopped reading. Send the type code, the voltage basis, the cross-section and the route, and we will answer against the construction the code actually describes rather than the family it looks like. Check a type code with us.

09Writing a line item that cannot be misread

Almost every dispute described on this page starts as a short line in a bill of quantities. The fix is to make the line name four things: the part number, its edition, the object, and the construction. If any one of the four is missing, a supplier who reads the line differently can still be right.

Table 8 — German lines as written, and what is still missing
Line as writtenWhat it points atWhat is still missing
“To DIN VDE 0250”One of roughly twenty parts, from NYM to reeling cableThe part number, the edition, and which of the wire or flexible families is meant
“To VDE 0276”Thirteen published parts, from LV distribution to 150 kVThe part, and therefore the voltage band and the construction
“NYY 4 × 120 mm²”Copper, PVC insulated, PVC sheathed LV cableThe standard and edition, the conductor class, and whether the route needs armour
“N2XY 0,6/1 kV”Copper, XLPE insulated, PVC sheathed, unarmouredThe conductor class, the sheath compound where fire performance matters, and the current-rating basis
“NYM-J 5 × 2,5”German installation cable to DIN VDE 0250-204Whether a halogen-free build was intended; NYM is PVC and stays PVC
“NHXMH 3 × 1,5”Halogen-free installation cable to DIN VDE 0250-214The CPR class from the Declaration of Performance, and whether that class is accepted where the cable is being installed
“N2XRY 4 × 95 SE”Armoured LV cable with a sector-shaped solid conductorWhether the concentric or screen layer is required as well, and the armour's fault-duty basis
The right-hand column is the part worth putting in the quotation request. It is usually answered in one round when it is asked before the order, and it is almost never answered at all when the cable has already been manufactured.

A wording that survives review

  • Name the part, not the series. “DIN VDE 0250-204” and “DIN VDE 0276-603” identify one document each. “To VDE” identifies neither.
  • Add the edition where conformance has to be demonstrated. A part number without a year is a moving target, and the amendments appended to a title change the requirement.
  • Say which object the cable is. A wire to 0250 and a power cable to 0276 sit at different voltages and serve different duties, and no letter code bridges them.
  • Write the construction alongside the code. “Cu/XLPE/PVC, 0,6/1 kV, Class 2” survives translation into any naming tradition; N2XY alone does not.
  • Ask for the document, not the claim. A test report names the construction, the core count and the section that were tested. Anything broader than that is a type name, and type names travel.

Send the code and the construction, and we will answer against both

Give us the type code as it appears in the tender, the voltage basis, the cross-section and the route — buried, ducted, on tray, or inside plant. We will come back with the construction we build for that requirement, the standard basis it is made to, and the documentation that applies to it. Where a name is ambiguous, we will say so rather than pick the cheaper reading.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Experienced in cable specification aligned with IEC standards.

Sources checked

  • DIN VDE 0250-204:2000-12 — the publication record for the PVC installation cable NYM: title, status, page count and the note that it replaced DIN 57250-204. VDE publication record
  • DIN VDE 0276-603:2010-03 — the German edition of HD 603 S1:1994/A3:2007 for 0,6/1 kV distribution cable; edition, page count and replacement history. DIN Media record
  • DIN VDE 0276-603:2010-03 — second record, used for the German scope sentence, the supersession of DIN VDE 0272 and the table of contents. Publication record
  • German standards index (Part 2) — German-language index carrying the part lists and titles of the DIN VDE 0250, 0276, 0281 and 0282 series with their edition dates. Standards index (PDF)
  • Bayka — Kabelkurzzeichen reference: the German designation code letter by letter, including the conductor-form letters and the worked examples used in Figure 1. Kabelkurzzeichen
  • HELUKABEL — harmonised designation code handbook: the H-designation letters, the comparison table against the DIN VDE numbers and the old-to-new national short designations. HAR code handbook (PDF)
  • HELUKABEL — NYM-J / NYM-O datasheet to DIN VDE 0250-204, used for the voltage, test voltage, temperature range, conductor classes and the standard reference list. NYM datasheet (PDF)
  • Batt Cables — NYM-J / NYM-O product page, used as an independent check on the installation duty and the standards line of the NYM family. NYM product page
  • Prysmian — NHXMH technical brochure to DIN VDE 0250-214: insulation compound, halogen-free sheath, core identification, CPR class and minimum bending radius. NHXMH brochure (PDF)
  • ELMAT — NHXMH datasheet to DIN VDE 0250, used for the VDE 0472 test list (flame method C, halogen-free to Part 815, smoke density to Part 816, ozone to Part 805). NHXMH datasheet (PDF)
  • Hardy Schmitz — NYY-J / NYY-O datasheet to VDE 0276-603: rated and test voltage, bending radii, temperature range, conductor forms, core identification and flame test. NYY datasheet (PDF)
  • TT Cables — the 0,6/1 kV type range published against VDE 0276-603, used to check the low-voltage code list. VDE 0276-603 range
  • Hywire — third independent product page for a VDE 0276-603 NYY, used to confirm the construction description of the all-PVC type. VDE 0276-603 NYY
  • Jianyun Cable — NYY / YJV / VV decoding page, used for the German, Chinese and British construction comparison and the statement that matching is done by standard rather than by name. Cable code comparison
  • Source by Spec — independent power-cable reference: the VDE 0276 code table, the PVC and XLPE temperature and short-circuit limits, and the medium-voltage screen conventions. Power cable encyclopedia

How this was written: every part number, title and figure in this article is checked against the standard index, publication record or manufacturer datasheet listed in Sources before publication. Where a figure comes from a supplier or a manufacturer's own document rather than from the standard itself, it is labelled as such in the text and not presented as a standard value.

Related product · the LV constructions these codes describe
Cu/XLPE/SWA/PVC 0,6/1 kV Armoured Power Cable
ApplicationFixed low-voltage distribution and utility-style routes where the cable is buried, ducted or pulled — the duty a German 0,6/1 kV line describes
StandardsBS 5467 for the 0,6/1 kV armoured arrangement; IEC 60502 for the extruded-insulation construction at this voltage; conductor to IEC 60228 Class 2; flame retardance to IEC 60332-1-2. A German line quoting 0276-603 is describing the same PVC-sheathed distribution layer
ConductorPlain annealed copper, stranded, IEC 60228 Class 2
InsulationExtruded XLPE rated +90 °C continuous; galvanised steel wire armour over a PVC bedding; PVC over-sheath
Voltage Rating0,6/1 kV Uo/U
AmpacityBy cross-section, core count and installation method; 246 A in air at 30 °C for 4 × 70 mm², derated for grouping and ambient
TemperatureConductor +90 °C continuous; +250 °C short-circuit condition limited to 5 s, taken as a calculated duty rather than a working temperature
CertificationsQuoted as made to the standards above, not as certified; any third-party approval is confirmed against the certificate for the exact construction ordered
Cu/XLPE/LSZH/SWA/LSZH 0,6/1 kV Armoured Power Cable
ApplicationThe same low-voltage distribution duty where the bedding and oversheath must be halogen-free and low-smoke — plant rooms, tunnels, stations and basements
StandardsBS 6724 for the 0,6/1 kV halogen-free armoured arrangement; IEC 60502 for the construction at this voltage; conductor to IEC 60228 Class 2; bunched flame propagation to IEC 60332-3 Cat. C
ConductorAnnealed copper, Class 2 stranded to IEC 60228
InsulationExtruded XLPE; halogen-free bedding; galvanised steel wire armour; halogen-free low-smoke oversheath
Voltage Rating0,6/1 kV Uo/U
AmpacitySame current family as the PVC-sheathed version of the build; 246 A in air at 30 °C for 4 × 70 mm², derated for route, grouping and ambient
TemperatureConductor +90 °C continuous; +250 °C short circuit, 5 s maximum
CertificationsHalogen-free and smoke-density performance declared for the construction ordered, not for the type name; no blanket approval claim
Which family does your line name? Send the type code, the voltage basis, the cross-section and the route, and we will answer against the construction the code describes — request a quote.
Q1What is the difference between DIN VDE 0250 and DIN VDE 0276?

They govern different objects. DIN VDE 0250 is the insulated-power-Leitung series — installation wires, cords and heavy-duty flexible cables such as NYM, NHXMH, NSSHÖU and NSHTÖU. DIN VDE 0276 is the power-cable series, and most of its published parts are German versions of a CENELEC HD document: Part 603 is HD 603 S1 for 0,6/1 kV distribution cable and Part 620 is HD 620 S1 for medium voltage. Both series draw their letters from DIN VDE 0292, the German version of HD 361 S3, which is why a wire and a power cable can carry codes that look as though they belong to one family.

Q2What do the letters in NYY actually mean?

Read left to right from the conductor outward. N means the cable is made to a German standard; A would mean an aluminium conductor and its absence means copper; Y means PVC insulation; and the second Y means a PVC outer sheath. So NYY is copper, PVC insulated and PVC sheathed. N2XY swaps the insulation to XLPE, marked 2X. A trailing J means a green-yellow protective conductor is present and O means it is not, which is the only difference between NYM-J and NYM-O.

Q3Is NYM the same as NYY?

No. They belong to different series and different duties. NYM is an installation cable to DIN VDE 0250-204 rated 300/500 V, with PVC insulation and a PVC sheath, intended for fixed wiring in buildings in dry, damp or wet locations and for embedding in concrete. NYY is a power cable to DIN VDE 0276-603 rated 0,6/1 kV, intended for fixed installation outdoors, in the ground, indoors and in ducts and cable trenches. The voltage basis and the standard differ, so one does not substitute for the other.

Q4What does the 2X in N2XY mean?

It marks a cross-linked polyethylene insulation, known outside Germany as XLPE. PVC is quoted at +70 °C continuous and +160 °C short circuit where XLPE is quoted at +90 °C and +250 °C, which is the whole reason N2XY now appears in place of the older all-PVC NYY on new work. The letters that follow the 2X describe the layers after the insulation: S for a copper screen, and a final Y or 2Y for a PVC or PE outer sheath.

Q5Does a German cable type have an IEC equivalent?

The type code is German but the cable is often not. Most 0,6/1 kV cable sold into Europe and Asia is built to the IEC 60502-1 basis and then labelled with whichever national code the customer reads: NYY or N2XY in German terms, VV or YJV in Chinese GB/T terms, or a construction phrase such as XLPE/SWA/PVC in British usage. Two cables built to IEC 60502-1 and GB/T 12706 are generally interchangeable. What is not interchangeable is the code itself, so the reliable approach is to specify by construction and standard rather than by name.

Q6Why does NHXMH carry a CPR class and NYM does not?

CPR, the Construction Products Regulation, classifies cables for reaction to fire and has applied to construction cables in the EU since 2017, with a Declaration of Performance and a Euroclass rather than a certificate. A halogen-free installation cable such as NHXMH is routinely declared, and one manufacturer's NHXMH brochure quotes class Dca-s1b,d2,a1. Because the class belongs to the construction that was tested rather than to the type name, it has to be read from the Declaration of Performance for the cable actually ordered, and the class accepted in the destination country can differ from the German one.