BS 5467 vs BS 6724: What Is the Difference?

📅 Published: 2026-06-12 | 📁 Category: Armoured Cable Guide | ⏱ 12 min read

BS 5467 vs BS 6724 armoured cable comparison for external street and landscape lighting

1. Why the Right Cable Standard Matters for External Lighting

Specifying the wrong cable for an outdoor lighting installation is not just a paperwork error — it can mean early sheath degradation, fire safety non-compliance, unnecessary cost overruns, or failing a building control inspection. In the UK, the two dominant British Standards for low-voltage armoured power cables — BS 5467 and BS 6724 — are often treated as interchangeable. They are not.

Both standards describe cables with XLPE insulation, steel wire armour (SWA), and a 600/1000V rating. Both are suitable for direct burial. For equivalent conductor size and installation method they generally have comparable electrical performance, although actual dimensions and weight can differ between manufacturers. The critical difference is the outer sheath material: PVC under BS 5467, and LSZH (Low Smoke Zero Halogen) under BS 6724.

For an external lighting contractor or consultant, the choice depends less on whether the installation is outdoors and more on the cable route, the fire environment and the project specification. If the cable stays entirely outdoors in open, ventilated locations, BS 5467 is cost-effective and field-proven. If the route passes through a fire compartment, an enclosed public space, a tunnel, or another area with specific low-smoke / halogen-free requirements, BS 6724 may be specified instead — always confirm the project fire strategy and applicable specifications.

This guide provides a side-by-side comparison of BS 5467 and BS 6724 for external lighting applications, including construction differences, fire performance, cost impact, installation requirements under BS 7671, and practical decision criteria for UK electrical contractors and specifiers.

BS 5467 XLPE/SWA/PVC BS 6724 XLPE/SWA/LSZH 600/1000V rated 90°C conductor SWA direct burial BS 7671 compliant
Related reading: For a broader comparison of armoured cable types, see our guide on SWA vs AWA vs STA Armoured Cable | BS 5467/BS 6724. For cable laying best practices, see Cable Laying Methods & Requirements.

2. Construction: Same Core, Different Sheath

BS 5467 and BS 6724 cables share the same conductor, insulation, and armour construction. Every difference is in the bedding and outer sheath materials.

2.1 Common Construction — Copper Conductor & XLPE Insulation

Both standards specify plain annealed stranded copper conductors to BS EN 60228 (Class 2), with XLPE (cross-linked polyethylene) insulation to BS 7655 Type GP8. XLPE provides a 90°C maximum conductor operating temperature and 250°C short-circuit capability — significantly higher than PVC-insulated cables (70°C).

2.2 Armour — Steel Wire Armour (SWA)

Both use a single layer of galvanised steel wire armour for mechanical protection. For single-core cables, aluminium wire armour (AWA) is required instead to avoid inductive heating. The armour also serves as a Circuit Protective Conductor (CPC) under BS 7671 when correctly terminated at both ends.

2.3 The Critical Difference: Bedding & Outer Sheath

LayerBS 5467 — XLPE/SWA/PVCBS 6724 — XLPE/SWA/LSZH
ConductorCopper, Class 2 stranded (BS EN 60228)Copper, Class 2 stranded (BS EN 60228)
InsulationXLPE, Type GP8 (BS 7655) — 90°CXLPE, Type GP8 (BS 7655) — 90°C
Bedding (inner sheath)PVC (Type 9)LSZH, Type LTS1 (BS 7655)
ArmourGalvanised steel wire (SWA) or aluminium wire (AWA for single-core)Galvanised steel wire (SWA) or aluminium wire (AWA for single-core)
Outer SheathPVC, carbon-black loadedLSZH, Type LTS1, black
Flame retardancyIEC 60332-1-2 (single vertical)IEC 60332-1-2 + IEC 60332-3-24 Cat C (bunched)
Halogen contentPVC compounds can release hydrogen chloride and dense smoke when exposed to fireZero halogen (IEC 60754-1/2 — HCl < 0.5%)
Smoke emissionDense black smoke (IEC 61034 ≤ 20% transmittance)Low smoke (IEC 61034 ≥ 60% transmittance)
UV resistanceYes (carbon black in PVC)Yes (carbon-loaded LSZH formulation)

2.4 Identical Electrical Performance

Because the conductor, insulation thickness, and armour are identical, both cable types share the same:

  • Current-carrying capacity (ampacity) — per BS 7671 Table 4E4A
  • Voltage drop (mV/A/m) — identical per core size
  • Short-circuit rating — 250°C for 5 seconds
  • Overall dimensions — generally similar for equivalent construction, but verify against the manufacturer’s datasheet
  • Minimum bending radius — 6× OD for ≤16 mm², 8× OD for ≥25 mm²
Key point: For equivalent cable construction and the same installation conditions, BS 5467 and BS 6724 generally provide similar current-carrying and voltage-drop characteristics. The final selection should still be verified against BS 7671 and the manufacturer’s datasheet — the difference between the standards is the outer sheath fire performance.

2.5 Pricing: BS 5467 vs BS 6724 at SORIVO

FactorStandard Market Cable (PVC Sheath)SORIVO BS 6724 (LSZH Sheath)
Sheath materialPVC (can release hydrogen chloride and dense smoke in a fire)LSZH Type LTS1 (zero halogen, low smoke)
Fire toxicityProduces HCl gas and dense smoke in fireIEC 60754-1/2 — HCl < 0.5%, IEC 61034 — ≥60% transmittance
Bunched flame testNot required (single vertical only)IEC 60332-3-24 Cat C — test report available on request
Typical price premiumBaseline+10–15% over equivalent BS 5467
TraceabilityMay lack metre markingMetre-marked, batch-traceable, certificate on request
Design lifeVaries by manufacturer25 years (matching building lifecycle); warranty terms on request

3. Standards & Certification: What BS 5467 and BS 6724 Actually Require

Both standards are published by the British Standards Institution (BSI) and are harmonised with European and international standards. Here is what each standard actually specifies and tests.

3.1 BS 5467:2016 — XLPE/SWA/PVC

Full title: Specification for cables with thermosetting insulation for rated voltages up to and including 600/1000V.

  • XLPE insulation to BS 7655 Type GP8 — 90°C continuous, 250°C short-circuit
  • PVC bedding and outer sheath to BS 7655 Type 9
  • SWA or AWA armour per conductor size configuration
  • Flame retardancy to IEC 60332-1-2 (single cable vertical flame propagation)
  • Voltage rating: U₀/U = 0.6/1 kV (also available in 1.9/3.3 kV)

3.2 BS 6724:2016 — XLPE/SWA/LSZH

Full title: Specification for cables with thermosetting insulation for rated voltages up to and including 600/1000V, having low emission of smoke and corrosive gases when affected by fire.

  • Same XLPE insulation as BS 5467 (BS 7655 Type GP8)
  • LSZH bedding and sheath to BS 7655 Type LTS1 — zero halogen, low smoke
  • Flame retardancy to IEC 60332-1-2 plus IEC 60332-3-24 Cat C (bunched cables)
  • Halogen-free to IEC 60754-1/2 — HCl content < 0.5%
  • Low smoke to IEC 61034-2 — light transmittance ≥ 60%
  • Voltage rating: U₀/U = 0.6/1 kV (also available in 1.9/3.3 kV)

3.3 BS 7671 (IET Wiring Regulations) — External Lighting Requirements

The 18th Edition of BS 7671 sets the following requirements relevant to external lighting cable selection:

RequirementValueBS 7671 Reference
Burial depth (general ground)~600 mm commonly usedRegulation 522.8.10 — verify against site conditions
Burial depth (under hard standing)~300 mm commonly usedGood practice / 522.8.10
Warning tape above buried cable150 mmRegulation 522.8.10
Socket-outlet RCD protection30 mA (mandatory)Regulation 411.3.3
Fixed lighting RCD protection30 mA (recommended)Section 714 guidance
Voltage drop (lighting circuits)3% max (5% for other uses)Appendix 4, Section 6.4
Compliance note: For external lighting circuits in public spaces — schools, hospitals, transport hubs, commercial car parks — the local authority or project specification may mandate BS 6724 for any cable that enters a building or fire compartment. Always check the project's fire strategy document before specifying.

4. Which Standard for Which External Lighting Scenario?

The decision between BS 5467 and BS 6724 depends on the cable route and the building types it serves. The following table gives scenario-based recommendations.

4.1 Application Decision Table

ApplicationCable RouteRecommended StandardReason
Street lighting (public highway)Buried in ground, terminates in lighting column baseBS 5467 (PVC) ✓No building entry. Lighting column base is ventilated. PVC is sufficient and cost-effective.
Car park lightingBuried + clipped to columns, terminates in columnBS 5467 (PVC) ✓Same as street lighting. Open air, low fire risk.
School / hospital external lightingBuried → enters building plant room or distribution boardBS 6724 (LSZH) ✓Where cable enters a public building, LSZH may be specified by the fire strategy or project specification.
Tunnel lightingClipped to tunnel wall or ceilingBS 6724 (LSZH) ✓Confined space — dense smoke would be lethal. LSZH is commonly specified for tunnel installations.
Retail / shopping centre perimeter lightingBuried → enters centre electrical roomBS 6724 (LSZH) ✓Public building + fire compartment penetration. LSZH may be specified.
Residential garden lightingBuried or surface clipped to fence/wallBS 5467 (PVC) ✓Low risk, small scale. PVC is standard for domestic work.
Sports floodlighting (stadium)Buried → floodlight column baseBS 5467 (PVC) ✓Open air, ventilated column base. PVC is sufficient unless project spec requires otherwise.
Emergency escape route lightingSurface or buried along escape routeBS 6724 (LSZH) ✓Low smoke supports evacuation, but confirm whether the project specifies a fire-resisting cable (e.g. BS 7846) for circuit integrity.
Important: BS 6724 is a low-smoke, low-halogen armoured cable standard. It should not be treated as a fire-resistant cable standard. Where an emergency lighting or other life-safety circuit must maintain circuit integrity during a fire, a fire-resisting cable such as BS 7846 (or another project-specified fire-resisting construction) may be required.

Quick Decision: BS 5467 or BS 6724 for Your Project?

If the cable...Use
...never enters a building or enclosed spaceBS 5467 (PVC) — most cost-effective
...enters a public building (school, hospital, shopping centre, transport hub)BS 6724 (LSZH) — may be specified by fire strategy
...runs through a tunnel or underground walkwayBS 6724 (LSZH) — confined space safety
...serves emergency escape lightingBS 6724 (LSZH) is often used for low smoke — but confirm whether a fire-resisting cable is required for circuit integrity
...is in a plant room, riser, or basement car parkBS 6724 (LSZH) — fire compartment rules apply
...is in a domestic garden, open car park, or sports fieldBS 5467 (PVC) — sufficient and economical

Note: Always verify with the project's fire risk assessment and BS 7671 wiring regulations.

4.2 BS 5467 vs BS 6724 — Equivalent Cable Sizes & Ampacity

Illustrative values for 3-core XLPE armoured cable under the stated reference conditions (clipped direct, 90°C conductor, 30°C ambient). Actual current capacity must be selected using the applicable BS 7671 installation method and correction factors.

Conductor SizeBS 5467 (PVC) — Clipped Direct (A)BS 6724 (LSZH) — Clipped Direct (A)Voltage Drop (mV/A/m)
1.5 mm²232327
2.5 mm²313116
4 mm²424210
6 mm²53536.8
10 mm²72724.1
16 mm²96962.6
25 mm²1301301.7

Ampacity per BS 7671 Table 4E4A; voltage drop per Table 4E4B. 3-core cable at 90°C conductor temperature, 30°C ambient. Current ratings are identical between BS 5467 and BS 6724 for the same conductor size.

Design tip (example only): For a 3-phase lighting circuit carrying approximately 10 A per phase, a 6 mm² 3-core SWA cable may provide adequate voltage-drop performance over a typical 100 m run. The final size should be confirmed using the actual load distribution, power factor, source voltage and installation conditions.

5. The 25-Year Cost: BS 5467 vs BS 6724 in External Lighting

The upfront cost difference between BS 5467 and BS 6724 is typically 10–15%. But the total cost of ownership tells a different story — especially when fire risk, replacement cycles, and compliance penalties are factored in.

5.1 When BS 5467 (PVC) Costs More Over Time

If PVC-sheathed cable is installed where LSZH is now required by Code or local regulation — for example, in a school extension where the cable enters a fire compartment — the eventual remediation cost far exceeds the upfront saving.

ScenarioInitial Saving (BS 5467 over BS 6724)Remediation CostNet Impact
Correct specification£0Optimal
BS 5467 installed where BS 6724 was specified~15% cable cost savedFull re-pull + re-termination + inspectionNet loss: ~3–5× the initial "saving"
PVC aged in wet ground (30+ years)Potential plasticiser leaching in wet ground → sheath cracking → earlier replacement possibleBS 6724 likely still in service

5.2 Typical Cable Cost Comparison (per metre, 4-core 6 mm² SWA)

Cable TypeApprox. Cost per Metre25-Year Lifecycle
BS 5467 XLPE/SWA/PVCBaseline1 installation (replace PVC if plasticiser migration occurs in wet soil)
BS 6724 XLPE/SWA/LSZH+10–15%1 installation expected; service life depends on environment — LSZH compounds are generally more stable in wet ground

5.3 The Compliance Cost of Getting It Wrong

A Building Control inspection that finds PVC-sheathed cable in a fire compartment where LSZH is specified can result in:

  • Rejection of the electrical installation — delaying project handover
  • Cost of replacement — excavation, re-cabling, making good surfaces
  • Reputational risk — for the contractor and consultant
  • Potential insurance implications — non-compliant installation may affect coverage
Bottom line: If the cable route is entirely outdoors with no building penetration, BS 5467 is the clear economic choice. If there is any risk that the cable enters a fire-sensitive zone, specify BS 6724 — the 10–15% upfront premium is negligible compared to the cost of retrofitting LSZH after installation.

6. How to Verify BS 5467 / BS 6724 Cable Quality Before Purchase

When sourcing armoured cable for an external lighting project, use these practical checks to confirm you are getting the standard you specified.

  1. Read the cable marking: Every metre of compliant BS 5467 or BS 6724 cable must be marked with the standard number, conductor size, voltage rating, and manufacturer (or BASEC licence number). Example: "BS 5467 6mm² 3-Core 0.6/1kV SORIVO". Rub the marking — if it smudges or wipes off, the ink quality is poor.
  2. Check the BASEC certificate: BASEC is the UK's leading cable certification body. Every BASEC-certified cable has a unique licence number searchable at www.basec.org.uk. Never rely solely on printed labels — verify the licence is active.
  3. Burn test (simple field check): Take a small offcut of the outer sheath. Heat it with a lighter in a ventilated area. PVC produces black smoke and a sharp chlorine smell (like bleach). LSZH produces minimal white/grey smoke, no chlorine smell, and the material leaves a chalky residue rather than dripping.
  4. Measure outer diameter: Compare against the manufacturer's datasheet. A cable that is significantly thinner than specified may have reduced XLPE insulation thickness or fewer armour wires — both safety-critical issues.
  5. Check conductor stranding: For a 6 mm² cable, expect Class 2 stranded copper — typically 7 wires (1+6 construction). If the conductor has fewer or visibly thinner strands, the cable may not meet BS EN 60228.
  6. Sheath flexibility: PVC stiffens noticeably at low temperatures (below 0°C). LSZH Type LTS1 maintains flexibility across a wider temperature range. If the cable feels unusually stiff in cold weather, compare against a known compliant sample.

For a complete walkthrough, see our dedicated guide: How to Verify Cable Certification (methodology applies equally to BS standards).

7. Conclusion: A Practical Framework for Specifying External Lighting Cable

When specifying armoured cable for external lighting, follow this three-step process:

  1. Map the cable route — does it enter any building, fire compartment, tunnel, or enclosed public space? If so, check whether the project specification or fire strategy requires LSZH, and whether a circuit-integrity (fire-resisting) cable is also needed. If the route is entirely outdoors in open, ventilated areas, BS 5467 (PVC) is usually sufficient.
  2. Size the cable — use the ampacity values in BS 7671 Table 4E4A. Remember: BS 5467 and BS 6724 have identical current ratings for the same conductor size. Verify voltage drop for long runs (over 80 metres).
  3. Specify the standard clearly — write "BS 6724 4-core 6 mm² XLPE/SWA/LSZH" in your bill of quantities. Do not write "or equivalent" unless you verify the proposed substitute carries the same fire performance certification.

For the majority of external lighting applications — street lighting, car parks, sports floodlighting — BS 5467 XLPE/SWA/PVC remains the industry standard: reliable, cost-effective, and fully compliant with BS 7671 for outdoor use.

For any installation where the project specification or fire strategy requires low-smoke, halogen-free performance, BS 6724 XLPE/SWA/LSZH is the appropriate choice — confirm the exact requirement from the fire strategy rather than assuming it from the building type. At SORIVO, both standards are available with batch traceability and certification documents available on request.

Further reading:

Need help selecting BS 5467 or BS 6724 for your project?

Send us your cable size, core configuration, voltage, installation method and required length. Our engineering team can confirm the appropriate construction and provide a quotation for your external lighting project.

Request a Specification Review & Quote

📧 sale@sorivocable.com | 📞 +86 192 8290 5529

8. Frequently Asked Questions

Q1: Can I use BS 5467 PVC-sheathed cable for direct burial in all soil types?

BS 5467 PVC-sheathed cable is suitable for direct burial in most well-draining soils. However, in waterlogged ground, clay soils with high moisture content, or chemically contaminated ground (e.g., former industrial sites), PVC plasticisers can leach over time, causing the sheath to become brittle. In these conditions, specify BS 6724 (LSZH) or request an MDPE (medium-density polyethylene) outer sheath variant. For standard street lighting in typical UK ground conditions, BS 5467 is proven over 25+ year design life.

Q2: Does BS 7671 require RCD protection on all external lighting circuits?

BS 7671 (18th Edition) requires 30 mA RCD protection for socket-outlets that may supply outdoor equipment (Regulation 411.3.3). For fixed external lighting (hard-wired, no socket), RCD protection is not mandatory in all cases — particularly if the circuit uses SWA cable with the armour earthed as a CPC. However, industry good practice recommends 30 mA RCD for all outdoor circuits. If in doubt, install the RCD — the cost is negligible compared to the risk. For TT earthing systems, RCD protection is mandatory.

Q3: Is BS 6724 always required when the cable enters a building?

Not automatically — it depends on the project specification and fire strategy. A cable that passes through a fire compartment or serves a life-safety circuit (emergency lighting, fire alarms) may require LSZH, and may also need circuit-integrity (fire-resisting) performance that LSZH alone does not provide. For a simple meter cabinet or external distribution board mounted on the outside wall, a short PVC-sheathed tail entering the building through a sealed gland may be acceptable. Many local authorities and project specifications specify BS 6724 for building penetration as a conservative measure. Always check the project fire strategy document.

Q4: What is the typical lead time for BS 6724 (LSZH) cable compared to BS 5467?

BS 5467 PVC-sheathed cable is more widely stocked by UK wholesalers due to its higher volume. BS 6724 LSZH cable typically requires manufacturer stock or factory lead time. At SORIVO, we maintain stock of both standards for common sizes (4 mm² to 16 mm², 3-core and 4-core). For non-standard sizes or lengths, allow 2–3 weeks for BS 6724 production. Our CU/XLPE/LSZH/SWA/LSZH cable is available with batch traceability and certification documents on request.

Q5: Can I use single-core AWA cable instead of multi-core SWA for a three-phase lighting supply?

Yes — for three-phase external lighting, single-core AWA (aluminium wire armour) cables are sometimes used for large floodlighting installations or long runs where installing multiple single cores in trefoil formation reduces eddy current losses. However, the standard for most external lighting is multi-core SWA (3-core or 4-core), which is simpler to install, requires fewer terminations, and is more cost-effective for runs under 100 metres. For more detail, see our SWA vs AWA comparison guide.

Technical References

BS 5467:2016 — Electric cables: thermosetting insulated, armoured cables up to 600/1000 V for fixed installations
BS 6724:2016 — As BS 5467, with low emission of smoke and corrosive gases when affected by fire
BS 7671 — IET Wiring Regulations (installation requirements)
BS 7655 — Specification for insulation and sheath compounds
IEC 60332 / IEC 60754 / IEC 61034 — Flame propagation, halogen and smoke emission tests
BS 7846 — Fire-resisting armoured cable with enhanced circuit integrity (where applicable)
Standards are subject to revision — verify the current edition before specifying.