Standard cross-reference · Low-voltage power cable · 2026

YJV Cable Cross-Reference: GB/T 12706 vs IEC 60502 and BS 5467

A low-voltage XLPE power cable is designated YJV in China, CU/XLPE/PVC or N2XY under IEC 60502-1, Cu/XLPE/SWA/PVC under BS 5467, and a UL-listed type code in North America. This page decodes each field of the Chinese code and maps the family across the four systems, so a specification written in one can be quoted in another.

Published 2026-10-15 Updated 2026-10-15 Level: reference Reading time ~15 min
The short answer

For a low-voltage XLPE-insulated power cable at 0.6/1 kV, the four systems describe the same product family in different letters. GB/T 12706.1-2020 is China's national standard and writes the type as YJV for copper and YJLV for aluminium; it is modified from IEC 60502-1:2004 — its cover states MOD, not IDT, so it is not the same document. IEC 60502-1 is the international counterpart and names the same construction by its layers — CU/XLPE/PVC, with STA (steel tape) or SWA (steel wire) armour added where the cable must take mechanical load. BS 5467 is the British low-voltage armoured family, Cu/XLPE/SWA/PVC at 0.6/1 kV, with the low-smoke BS 6724 alongside it. North America is a separate case: LV power cable is covered by the UL 44 / UL 854 and ICEA families, not by a harmonised European or Chinese code. The four agree on the physical recipe — annealed copper or aluminium conductor, XLPE insulation at 90 °C, a 0.6/1 kV class — and differ in type code, in the standard relationship, and in the armour and sheath conventions each one assumes.

01What a low-voltage power cable is, before the code letters

A low-voltage power cable carries the main supply from a transformer or a distribution board to the loads downstream of it. The job it has to do is narrower than a building wire's: it is fixed for its whole life, it carries a defined load current that decides its cross-section, and it may have to survive being pulled into a trench, buried, or hung in a shaft. That combination is what the standards below are written around.

All four systems land on the same physical recipe for the common product:

  • Conductor: annealed copper or aluminium, solid or stranded — the cross-section is set by the load current and the volt-drop allowance, not by the type code.
  • Insulation: cross-linked polyethylene (XLPE), rated 90 °C continuous with a short-circuit allowance of 250 °C, so the cable can carry more current per square millimetre than an older PVC-insulated cable of the same size.
  • Sheath: a PVC (or, where fire emission matters, a low-smoke halogen-free) oversheath. In the Chinese code the sheath is a separate letter from the insulation; in the IEC and BS codes it is the last layer in the layer string.
  • Voltage: a 0.6/1 kV class as the standard low-voltage rating — 0.6 kV phase-to-earth, 1 kV phase-to-phase.
  • Armour (optional): steel tape or steel wire, added when the cable is buried or pulled. In the IEC and BS codes it appears in the layer string; in the Chinese code it is the two-digit suffix.

Where they diverge is exactly what a buyer trips over: whether the standard named on the certificate is the one the project specified, what the armour digits mean, and whether the cable you were quoted is the halogen-free construction or the PVC one. The rest of this page works through those one system at a time.

Scope of this page

This is a cross-reference for a product and its designations, not a compliance decision. Whether a specific cable satisfies a specific project is settled by the certificate scope and the accepting authority. For the medium-voltage side of the same family, see our MV collector-circuit cable selection page; this page is the low-voltage map.

02GB/T 12706.1: the Chinese reference, and the MOD that matters

China's standard for this cable is GB/T 12706.1-2020, Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 35 kV (Um = 40.5 kV) — Part 1: Cables for rated voltage of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV). It was published on 2020-03-31, took effect on 2020-10-01, and replaced the 2008 edition; it is a 53-page document under ICS 29.060.20, committee SAC/TC 213.

The scope fixes the limits: it covers the construction, dimensions and test requirements of extruded-insulation power cables for rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV), for fixed installation in distribution networks or industrial installations, and it explicitly excludes cables for special conditions — overhead networks, the mining industry, nuclear power plants (inside and around the containment area), and underwater or shipboard use.

The single most misquoted fact on a YJV datasheet

The cover of GB/T 12706.1-2020 states its relationship to the international standard directly: it is IEC 60502-1:2004 modified from — the adoption code is MOD, not IDT. The two numbers are not interchangeable and the standards are not identical; a Chinese cable made and tested to GB/T 12706.1-2020 is not automatically to IEC 60502-1:2004, and the reverse is also true. That distinction matters the moment a specification asks which edition the cable is tested to, or a tender lists the two numbers side by side as if one proved the other.

MOD is not IDT, and neither is a certificate

Stating "GB/T 12706.1-2020 (equivalent to IEC 60502-1)" is wrong on two counts: the adoption is MOD, and a national standard number does not evidence a test result. Ask for the standard the cable is actually made and tested to, and the certificate scope that names it.

03The YJV code, decoded field by field

The Chinese designation is a product-code string rather than a compact position code. Its logic is a sequence of attribute letters followed, where applicable, by two armour digits, and the worked example in the standard's own product-designation annex is the thing to read against. The rule for the letters is simple to state and easy to get wrong: YJ is the insulation, and the sheath letter that follows it is a different material.

THE CODE IS A LAYER STRING — INSULATION, SHEATH, THEN ARMOUR YJ V Y L 22 Cross-linkedpolyethyleneinsulation (XLPE) PVCoversheath Polyethyleneoversheath (PE) Aluminiumconductor Double steeltape armour V = PVC sheath, Y = PE sheath — the sheath letter is not the insulation letter. Copper is the default and carries no letter; L marks the aluminium variant (YJLV). Armour digits: 22 = double steel tape, 32 = fine round steel wire, 42 = coarse round steel wire.
Fig 1 — The YJV designation. YJ is the cross-linked polyethylene insulation; the following letter is the oversheath (V for PVC, Y for polyethylene); L marks an aluminium conductor and is omitted for copper; and the two-digit suffix gives the armour type. So YJV22 is the steel-tape armoured version for direct burial.

Reading the common members of the family

Once the letters are fixed, the variants in everyday use fall out of them directly. YJV is the plain copper XLPE/PVC cable for trays, ducts and conduits, with no armour. YJLV is the same construction on an aluminium conductor — cheaper and lighter, so it is common on longer runs where the load allows the larger cross-section aluminium needs. YJV22 adds double steel-tape armour for direct burial and crush resistance; YJV32 and YJV42 add fine and coarse round steel wire armour respectively, for shafts and risers where the cable carries its own weight. YJY swaps the PVC oversheath for polyethylene — useful where moisture rather than fire emission is the constraint. A flame-retardant prefix (ZR-), a low-smoke halogen-free prefix (WDZ-) and a fire-resistant prefix (NH-) go in front of the type and point to the flame and smoke performance, which is governed by a different standard family than the base cable type.

Table 1 — Field-by-field decoding of the GB/T 12706.1 YJV designation
FieldCodeMeaningNotes
Function prefix (optional)ZR- / WDZ- / NH-Flame-retardant / low-smoke halogen-free / fire-resistantSets the flame and smoke performance, which is governed by the flame-test standard family, not the base type
InsulationYJCross-linked polyethylene (XLPE) insulationYJ always comes first; it is the insulation, never the sheath
SheathVPolyvinyl chloride (PVC) oversheathYJV and YJLV are PVC-sheathed; PVC contains halogen, so they are not halogen-free products
Sheath (alternative)YPolyethylene (PE) oversheathGives YJY / YJLY, for moisture rather than fire emission
Conductor(none)Copper conductorCopper is the default; a bare "T" for copper is normally omitted
Conductor (alternative)LAluminium conductorGives YJLV; aluminium needs a larger cross-section for the same current
Armour22Double steel-tape armourFor direct burial and crush resistance
Armour32 / 42Fine round steel-wire / coarse round steel-wire armourFor shafts and risers where the cable carries its own weight

Decoded from the GB/T 12706.1 product-designation annex (Annex E gives the model-designation table and the arrangement order), corroborated by the published type descriptions on our own YJV product page. The library holds the standard's cover, contents and scope but not its numeric tables, so no table value or clause number is quoted here.

What the code does and does not prove

The letters fix the materials and the armour. They do not fix the conductor class, the cross-section, the standard edition the cable was tested to, or whether the certificate covers the exact construction you are buying. Those come from the standard number and the certificate scope — which is why the sheath print carries the type, the standard, the voltage class and the cross-section together.

04IEC 60502-1: the international counterpart

The international standard for this product family is IEC 60502-1, Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) — Part 1: Cables for rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV). Where the Chinese standard uses a type code, IEC names the cable by its layers, and that layer string is the thing a buyer has to read on an international datasheet.

The construction string is built outward from the conductor. CU/XLPE/PVC is the plain copper, XLPE-insulated, PVC-sheathed cable for indoor and trench installation where it does not have to take external mechanical force. Add steel tape and it becomes CU/XLPE/PVC/STA/PVC — the STA (steel tape armour) between two PVC layers, for indoor or direct-burial routes that do have to take mechanical force. Add steel wire instead and it becomes CU/XLPE/PVC/SWA/PVC, for routes that also have to take a pulling tension. Swap CU for AL and the same three strings describe the aluminium versions. This layer-string convention is the reason an English-language datasheet for the same physical cable as a Chinese YJV reads completely differently: nothing about the product changed except the naming system.

Conductors, temperature and the 0.6/1 kV class

Across the IEC family the conductor is specified to IEC 60228 — Class 1 solid, Class 2 stranded, or Class 5 flexible — and the insulation is XLPE, rated 90 °C continuous with a 250 °C short-circuit allowance for up to five seconds. The standard low-voltage rating is 0.6/1 kV. These three facts are the same in the Chinese standard, which is exactly why the two families map so cleanly at the product level even though their documents differ.

Where the CHINESE AND IEC stand

GB/T 12706.1-2020 and IEC 60502-1:2004 describe the same product on the same conductor, insulation and temperature basis, and the Chinese standard is modified from the IEC one — the cover says MOD. What that means in practice: the products map one to one, but the documents do not, and a claim against one is not a claim against the other. Treat the pairing as "same family, different adoption code", not "the same standard".

05BS 5467 and BS 6724: the British armoured family

The British low-voltage armoured cable standard is BS 5467, Electric cables — Thermosetting insulated, armoured cables of rated voltages of 600/1000 V and 1900/3300 V for fixed installations, and the low-smoke counterpart is BS 6724, which carries the same construction with a low-smoke halogen-free sheath in place of PVC. Both editions in current use are the 2016 revisions, and the older BS 5467:1997+A3:2008 was withdrawn on 2016-04-30 — a date worth knowing when a datasheet cites the superseded edition.

The type is written as a layer string of the same kind IEC uses. Cu/XLPE/SWA/PVC at 0.6/1 kV is the multicore steel-wire-armoured cable for LV distribution where PVC is acceptable. BS 6724 versions swap both the bedding and the oversheath to LSZH. One rule runs through both standards and catches people out: single-core AC cables use aluminium wire armour (AWA), not steel, because a ferromagnetic steel enclosure around a single AC conductor produces induced eddy and hysteresis heating and derates the cable. That is why the single-core string is Cu/XLPE/PVC/AWA/PVC and not SWA.

Table 2 — The British low-voltage family and its neighbours
StandardConstructionVoltageWhere it fitsCaution
BS 5467Cu/XLPE/SWA/PVC (multicore)0.6/1 kV; 1.9/3.3 kVFixed LV distribution where a PVC sheath is acceptableNot a flexible or reeling qualification
BS 5467 (single-core)Cu/XLPE/PVC/AWA/PVC0.6/1 kVSingle-core AC routes using non-magnetic armourAWA is not interchangeable with SWA by name
BS 6724Cu/XLPE/SWA/LSZH0.6/1 kV; 1.9/3.3 kVWhere smoke and corrosive-gas emission are constrainedA fire-performance choice, not a plain material swap
IEC 60502-1CU/XLPE/PVC + STA or SWA0.6/1 kV; 1.8/3 kVProjects specified to IEC rather than to the British standardIEC compliance does not establish BS 5467 approval

Compiled from published BS 5467 / BS 6724 / IEC 60502-1 comparison material; the library holds no BS or IEC 60502-1 text, so only scope-level and construction-level facts are stated, with no clause numbers or table values.

One more naming layer in Europe

In some European harmonised documentation the same CU/XLPE/PVC construction appears as the code N2XY. The layer string is the version to trust: it names every layer in order, whereas the harmonised letter code has to be read against the relevant national table. Where a specification shows only the letter code, ask for the layer string behind it.

06The cross-reference table

The table below maps the designations for the common 0.6/1 kV XLPE low-voltage power cable across the four systems. Read it as a mapping of product to product, not as a statement that any one certificate satisfies another jurisdiction.

Table 3 — Low-voltage XLPE power-cable designation cross-reference
AttributeGB/T 12706.1 (China)IEC 60502-1BS 5467 / BS 6724 (UK)North America
Type designationYJV / YJLVCU/XLPE/PVC (N2XY)Cu/XLPE/SWA/PVCUL 44 / UL 854 / ICEA type codes
Armoured variantYJV22 (tape) / YJV32 (wire)…/STA/PVC or …/SWA/PVCSWA multicore; AWA single-corePer the listing
Rated voltage0.6/1 (1.2) kV0.6/1 kV0.6/1 kV; 1.9/3.3 kV600 V / 1 kV class per the listing
ConductorCu or Al; Class 1/2 to GB/T 3956Cu or Al; Class 1/2 to IEC 60228Cu (multicore); Class 1/2 to BS EN 60228Per the listing
InsulationXLPE (+90 °C / +250 °C)XLPE (+90 °C / +250 °C)XLPE or EPRPer the listing
SheathPVC (YJY = PE; WDZ-YJY = LSZH)PVC (Type ST2); PE or LSZH on requestPVC (5467); LSZH (6724)Per the listing
Standard relationshipMOD from IEC 60502-1:2004(reference)(separate national standard)(separate regime)

The North American column is deliberately not filled with a type-code mapping: LV power cable in that system is covered by the UL 44 / UL 854 and ICEA families, which the library does not hold, so no letter-level correspondence is asserted. Cells that defer to "the listing" mean the value lives in the individual product listing, not in the standard's scope.

Map your specification to a build

If you have the table above and still need to know which construction a project actually requires, send us the standard, the voltage class, the load current and the installation route — we will answer against a power-cable build we manufacture. Ask a quote for the corresponding YJV or CU/XLPE/SWA/PVC construction.

Cross-reference index

YJV is the designation most enquiries arrive with, and the one most often quoted back in the wrong system. If the enquiry names something else — N2XY, NYY, BS 5467, IEC 60502-1, or a construction written out in full rather than as a code — enter it in the cross-reference index. It accepts a type code, a standard number, or a whole schedule line such as 3Cx95 mm² PVC/SWA/PVC 0.6/1 kV, and returns the Chinese type each one maps to.

Open the cross-reference index →

07What does not translate

Four misreadings cause most of the trouble when a low-voltage power-cable specification crosses a system boundary.

1. "Equivalent" is not the relationship GB/T 12706.1 has to IEC 60502-1

The adoption is MOD — modified from — and the covers say so. Writing the two numbers as if they were the same document overstates the relationship and can mislead a specification that asks which edition the cable is tested to. Say "modified from", and ask for the certificate scope if the question matters.

2. The sheath letter is not the insulation letter

YJV is YJ insulation plus V sheath. YJY is YJ insulation plus Y (polyethylene) sheath. The two letters after YJ in a longer code name two different layers, and reading YJY as "XLPE insulation twice" is a common error that hides a real change — PE sheath instead of PVC, which is a different fire and moisture behaviour.

3. Steel armour on a single-core AC cable is a design error, not a variant

Single-core AC circuits use aluminium wire armour because a ferromagnetic steel enclosure around a single AC conductor produces induced heating. A datasheet that offers a single-core "SWA" construction without addressing that is describing a cable that will derate or overheat in service.

4. Certification attaches to the construction, not the family

A certificate for one construction — one conductor material, one sheath compound, one armour type, one cross-section range — does not extend to another. Changing PVC to LSZH, or copper to aluminium, or adding armour where there was none, moves the product outside the tested scope. This is why the sheath print and the certificate scope are read together, and why the type code alone settles nothing.

08What this page publishes, and what it will not

The tables above are built from standard records, published scope text and manufacturer datasheets, and every voltage, temperature and adoption code in them is taken from a document listed in Sources rather than inferred from a letter string. Where a document was not available, the page says so and stops at the standard name: the GB/T 12706.1 layer-by-layer table comparison is not published here because the numeric tables were not obtained, the YJV designation is decoded without a clause number because the standard text was not fully held, and the North American column is left at the standard-family level rather than given a type-code translation that would not be sourced.

What this page does not do is decide a project. It will not tell you that a particular YJV cable satisfies a particular BS 5467 or IEC 60502-1 requirement on your job, because that depends on the build, the certificate scope and the accepting authority. Bring us the two specifications and the installation conditions, and we will work the comparison against a construction we actually build.

Send us the designation and the standard, and we will work the cross-reference

Give us the standard the enquiry is written to, the type code, the conductor material and class, the cross-section range, the voltage class and the installation route. We will come back with the corresponding construction and the points where the two standards diverge.

Senior cable application engineer at Sorivo
Reviewed by Luo Qiang — Senior Cable Application Engineer, Sorivo
15+ years in industrial and renewable energy cable specification. Experienced in cable specification aligned with IEC standards.

How this was written: every figure in this article is checked against the standard or datasheet listed in Sources before publication. Where a value is our own measurement, it is labelled as such.

Sources checked for this article

  • GB/T 12706.1-2020 — Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 35 kV (Um = 40.5 kV) — Part 1; cover states IEC 60502-1:2004 … MOD; scope 1 kV and 3 kV fixed installation, excluding overhead, mining, nuclear and submarine. Standard record — 准行天下 standard record.
  • GB/T 3956-2008 — Conductors of insulated cables; current edition (replaced GB/T 3956-1997); conductor classes 1, 2 and 5. Listed among the GB/T 12706.1 referenced standards — 准行天下.
  • IEC 60502-1 — Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) — Part 1: Cables for rated voltages of 1 kV and 3 kV; the international counterpart named on the GB/T 12706.1 cover.
  • 0.6/1 kV CU/XLPE/PVC construction and colour codes — conductor to IEC 60228, XLPE insulation, PVC Type ST2 sheath, STA / SWA armour strings. Supplier reference — Renhui 0.6/1 kV power cable and Cu/XLPE/PVC 0.6/1 kV (IEC 60502-1).
  • BS 5467 / BS 6724 — BS 5467:2016 thermosetting insulated armoured cables 600/1000 V and 1900/3300 V (superseded BS 5467:1997+A3:2008 withdrawn 2016-04-30); BS 6724 the low-smoke halogen-free counterpart; single-core uses AWA. Reference — BS 5467 / 6724 / 6622 comparison and SWA / AWA single-core rule.
  • Sorivo product page, YJV/YJLV 0.6/1 kV — GB/T 12706.1-2020 with the MOD relationship to IEC 60502-1:2004 stated on the cover; 0.6/1 (1.2) kV; conductors Class 1/2 to GB/T 3956; +90 °C continuous and +250 °C short circuit; four bending-radius values (20D / 15D plain, 15D / 12D armoured) — sorivocable.com.
  • Sorivo product page, Cu/XLPE/SWA/PVC 0.6/1 kV — the BS 5467-equivalent armoured construction — sorivocable.com; and the Cu/XLPE/LSZH/SWA/LSZH BS 6724 construction.
Related product · the power-cable constructions this page maps
YJV / YJLV 0.6/1 kV XLPE Insulated Power Cable
ApplicationFixed LV distribution — transformer-to-board and board-to-board feeders, plant power, building services
StandardsGB/T 12706.1-2020 (MOD from IEC 60502-1:2004); conductor to GB/T 3956-2008
ConductorCopper (YJV) or aluminium (YJLV), Class 1 or 2 to GB/T 3956; 1.5–800 mm²
InsulationXLPE, with a PVC oversheath; YJY for PE, WDZ-YJY for LSZH
Voltage Rating0.6/1 kV U₀/U, with Um = 1.2 kV
AmpacityBy cross-section and installation method — set with the current rating table for the route
TemperatureConductor +90 °C continuous; +250 °C short circuit ≤5 s
CertificationsConfirmed against the certificate for the exact construction and cross-section
Cu/XLPE/SWA/PVC 0.6/1 kV Armoured Cable
ApplicationLV distribution needing mechanical protection — direct burial, ducts and routes subject to crush or pull
StandardsBS 5467 (multicore steel-wire armoured LV family); conductor to BS EN 60228
ConductorCopper, stranded
InsulationXLPE, with a PVC bedding and PVC oversheath around a steel-wire armour
Voltage Rating0.6/1 kV
AmpacityBy cross-section and installation method — set with the current rating table for the route
TemperatureConductor +90 °C continuous; +250 °C short circuit ≤5 s
CertificationsConfirmed against the certificate for the exact construction and cross-section
Which designation does your specification map to? Send the standard, the type code, the voltage class and the cross-section range and we will answer against them — request a quote.
Q1What does YJV stand for?

It is the Chinese designation for a copper-conductor, XLPE-insulated, PVC-sheathed power cable under GB/T 12706.1. read the fields left to right: YJ is the cross-linked polyethylene insulation, V is the PVC oversheath, and a copper conductor carries no letter, so YJV is copper / XLPE / PVC. Add L and it becomes YJLV, the aluminium-conductor version.

Q2Is GB/T 12706.1 the same as IEC 60502-1?

No. GB/T 12706.1-2020 is modified from IEC 60502-1:2004, and its cover states the adoption code MOD, not IDT. The two describe the same product family on the same conductor, insulation and temperature basis, so the cables map one to one, but the documents are not the same and a claim against one is not a claim against the other.

Q3What is the difference between YJV, YJV22 and YJV32?

The base YJV has no armour, for trays, ducts and conduits. YJV22 adds double steel-tape armour for direct burial and crush resistance. YJV32 and YJV42 add fine and coarse round steel-wire armour for shafts and risers where the cable carries its own weight. The letters before the digits name the materials; the digits name the armour.

Q4What is the BS 5467 equivalent of a YJV cable?

The plain CU/XLPE/PVC construction under IEC 60502-1, or the British Cu/XLPE/SWA/PVC once steel-wire armour is added under BS 5467. They are technically comparable constructions, not interchangeable approvals: an IEC or Chinese certificate does not establish BS 5467 approval, and a project specified to BS 5467 needs evidence against that standard.

Q5Is a YJV cable halogen-free?

No. YJV and YJLV have a PVC oversheath, and PVC contains halogen, so they are not low-smoke halogen-free products. If the project requires LSZH, the model changes — WDZ-YJY for a halogen-free low-smoke sheath, or YJY for a plain polyethylene sheath — and that should be stated at enquiry stage so the right construction is quoted.

Q6Why does a single-core cable use aluminium armour?

Because a ferromagnetic steel enclosure around a single AC conductor produces induced eddy and hysteresis heating and derates the cable. Single-core AC routes therefore use aluminium wire armour (AWA), which is non-magnetic, while multicore routes use steel wire armour (SWA). A single-core "SWA" construction offered without addressing that is a design error rather than a variant.