A Chinese control cable is designated KVV, KVVR or KVVP and made to GB/T 9330.2-2008 at 450/750 V. Datasheets in this market routinely cite IEC 60227 or BS 6004 instead — standards whose scope contains no control cable of this type at all. This page decodes each field of the Chinese code and maps the family against the IEC and British systems, so a specification written in one set of letters can be quoted in another.
A GB control cable is made to GB/T 9330 — general requirements in GB/T 9330.1-2008, PVC insulated types in GB/T 9330.2-2008 and XLPE insulated types in GB/T 9330.3-2008 — and its code is built from a series letter plus material and construction letters: K (control series) + V or YJ (insulation) + V or Y (sheath) + an optional construction field (P braid screen, P2 copper-tape screen, P3 aluminium/plastic-laminate screen, R flexible, 22 steel-tape armour, 33 steel-wire armour). So KVV is PVC-insulated, PVC-sheathed, rigid; KVVR adds a flexible Class 5 conductor; KVVP adds a copper braid screen; KVVP2 uses copper tape; KVV22 adds steel-tape armour. Its rated voltage is 450/750 V and only that — a single class for the whole family. IEC 60227 is the closest international standard by voltage, but it covers PVC insulated fixed wiring cables and flexible cords (60227 IEC 01 to 60227 IEC 75), and its type list contains no control cable. BS 6004 is the British PVC insulated non-armoured standard for electric power, lighting and internal wiring, and since its 2012 revision it has narrowed further. GB/T 9330 is a Chinese product standard with no one-for-one IEC or BS equivalent: the correct move is to quote GB/T 9330, not to relabel the cable with a standard that does not describe it.
A control cable does not carry power to a load. It carries the signals that decide what the power does: close and trip commands, status and interlock signals, relay and contactor coil circuits, analogue and digital I/O between a PLC and the field. The conductor cross-sections are small — 0.5 to 10 mm² in the Chinese family — and the circuit is a low-current one, but the cable still runs through the same trays, ducts and trenches as the power cable next to it, and it has to keep its signal clean while it does so.
That combination — low current, small cross-section, many cores, installed alongside power — is what the standards below are written around. It is also why a control cable is one of the most mis-cited products in the market: because the voltage is 450/750 V, the same as some PVC wiring cable, a datasheet will often reach for the wiring standard and stop there.
China's control cable standard is a three-part document:
The scope of Part 1 states the object plainly: it specifies the product code, marking, technical requirements and inspection rules for extruded-insulated and sheathed control cables of rated voltage U0/U 450/750 V and below, and applies to cables used in control, monitoring and protection circuits at that voltage.
The rated voltage of this family is 450/750 V, and it is the only class. A datasheet that lists “300/500 V and 450/750 V” together is describing two different products: 300/500 V belongs to the GB/T 5023 family of PVC insulated cables and cords, not to GB/T 9330. There is no second voltage option to select.
The Chinese control cable code is positional. Read it left to right and each letter or digit names one physical layer or one construction feature.
Two fields do the work that catches people out. The first is the screen field: P is a copper wire braid, P2 is a copper tape and P3 is an aluminium/plastic laminate. The second is the armour field, written with the classic two-digit convention: 22 is double steel-tape armour with a PVC oversheath, 33 is steel-wire armour with a PE oversheath. A designation like KVVP2-22 therefore means braid-free tape screen and steel-tape armour in one cable, and its minimum bending radius is set by the tape, not by the plain construction.
These fields combine. The standard itself gives five worked examples in clause 4.2.5, and they cover most of the family:
| Designation | Insulation | Sheath | Screen / armour |
|---|---|---|---|
| KVV-450/750 23×1.5+1×1.5 | PVC | PVC | — (rigid, 23 cores + 1 green/yellow) |
| KYJVP2-450/750 24×1.5 | XLPE | PVC | Copper tape (P2) |
| KVV22-450/750 24×1.5 | PVC | PVC | Steel-tape armour (22) |
| ZB-KVVRP-450/750 24×1.5 | PVC | PVC | Braid (P) + flexible (R), flame-retardant class ZB |
| KYJY33-450/750 24×1.5 | XLPE | PE | Steel-wire armour (33) |
IEC 60227 is the international standard for PVC insulated cables of rated voltage up to and including 450/750 V. The voltage matches, which is exactly why the mistake happens. But the standard's own scope names what it covers: rigid and flexible cables with PVC insulation used in power installations of nominal voltage not exceeding 450/750 V AC, with the particular types set out in Parts 3, 4, 5, 6 and 7 of the series.
Those parts divide the product up like this:
Fixed wiring cable, sheathed wiring cable, flexible cord. There is a type list and a code for each — 60227 IEC 01, 60227 IEC 10, 60227 IEC 52/53, and so on — and none of those codes describes a many-core control cable with a braid or tape screen. The family that IEC 60227 produces is a wiring and cord family, not a control cable family.
A GB control cable is not “IEC 60227 under another name”. If a quotation or a datasheet cites IEC 60227 for a KVV-type control cable, it is citing a standard that does not contain that construction. The international standard that is related to GB/T 9330 by lineage is GB/T 5023 — and even that is the wiring family, not the control family.
China's PVC wiring standard, GB/T 5023, is the one that corresponds to IEC 60227: GB/T 5023.1-2008 is identical to IEC 60227-1:2007 — its cover states IDT, unlike the power cable standard GB/T 12706.1, which is only MOD from IEC 60502-1. GB/T 5023 is split the same way as IEC 60227 is: Part 1 general requirements, Part 2 test methods, Part 3 non-sheathed cable for fixed wiring, Part 4 sheathed cable for fixed wiring, Part 5 flexible cords, Part 6 lift cable, Part 7 screened and unscreened flexible multicore.
So the wiring family maps cleanly across the two systems — but a control cable is still not in it. GB/T 9330 and GB/T 5023 are two different Chinese standards for two different products, and neither is the control cable in the other's clothing.
GB/T 5023.1-2008's current type code is a two-digit number after 60227 IEC — 01, 02, 05, 10, 52, 53 and so on. The familiar BV, RV, BVV, RVV and TVV labels come from the 1985/1986 edition of GB 5023, and the current standard carries them only as an informative cross-reference in its Annex B. Quoting a modern GB wiring cable by its old BV/RVV name is a separate, common slip.
Send us the datasheet or the cable schedule and the text you were given. Our engineers will tell you which Chinese standard the cable answers to and quote it — request a quote or email us.
The British standard most often cited in place of GB/T 9330 is BS 6004. It is the standard for PVC insulated, non-armoured cables for voltages up to and including 450/750 V, for electric power, lighting and internal wiring — again a wiring standard, again not a control cable standard.
What matters for cross-referencing is that BS 6004 has narrowed. In its current edition, BS 6004:2012+A1:2020, the scope is specifically 300/500 V PVC insulated and PVC sheathed cable for electric power and lighting, covering the British national types 6181Y, 6192Y, 6241Y, 6242Y, 6243Y and the low-temperature arctic flexes. The harmonised single-core wiring cables — 6491X, 6491B and the H05V/H07V family — were moved out of BS 6004 and BS 7211 in September 2012 and now sit in the BS EN 50525 series. A British datasheet that cites BS 6004 for a flexible or a 450/750 V single-core cable may be using the citation loosely.
BS 6500 was the British standard for flexible cords rated up to 300/500 V for domestic and office appliances — the flexible-cord family. It has been withdrawn. It was superseded by BS EN 50525-1:2011 together with BS EN 50525-2-11, -2-12, -2-21 and -2-71:2011. The BS 6500 cord names are still used in the trade alongside the harmonised codes, but BS 6500 itself is not a current British Standard.
| Product family | China | IEC | British |
|---|---|---|---|
| PVC wiring, non-sheathed, fixed | GB/T 5023.3-2008 | IEC 60227-3 | BS 6004 / BS EN 50525-2-31 |
| PVC wiring, sheathed, fixed | GB/T 5023.4-2008 | IEC 60227-4 | BS 6004:2012+A1:2020 (300/500 V) |
| PVC flexible cords | GB/T 5023.5-2008 | IEC 60227-5 | BS 6500 (withdrawn) → BS EN 50525-2-11 |
| PVC control cable, multicore | GB/T 9330.2-2008 | No equivalent | No equivalent |
| XLPE control cable, multicore | GB/T 9330.3-2008 | No equivalent | No equivalent |
Cross-reference index
Control cable is where the cross-reference runs out fastest: IEC publishes no parent document, so five of the six columns can be empty for a single build. That empty column is the answer, not a gap in the index — it tells you there is no international code to check your KVV against, and that the comparison has to be made on construction and test values instead. Enter your type in the index to see which columns fill and which stay blank.
Three screen types appear in the GB/T 9330 code, and they are not interchangeable.
The braid and the tape do different jobs for different frequencies, and the choice changes the mechanical behaviour of the cable as well: a taped or armoured construction raises the minimum bending radius, so a screened type cannot be pulled round the same bend as a plain one without crushing the screen.
KVVP is a control-cable screen, not a bus-cable screen. Where the circuit has a defined characteristic impedance — PROFIBUS, PROFINET, EtherCAT, encoder feedback — a braid-screened control cable is not a substitute for the specified bus cable. For those installations, see our servo motor cable selection guide and EMC cable gland and shield termination guide.
Four points where the cross-reference is not a simple letter swap.
GB/T 9330 is a Chinese product standard for a product family — plastic insulated control cable — that the IEC and British systems do not carry under that name. IEC 60227 covers PVC wiring cable by voltage; BS 6004 covers PVC non-armoured wiring cable; the closest European product names, such as CY or SY flexible screened control cable, are trade families rather than the scope of a single numbered standard. The honest cross-reference is: quote GB/T 9330 where the product is a GB control cable, and do not relabel it with a foreign standard whose scope excludes it.
Because both the GB control cable and some GB wiring cable are rated 450/750 V, it is tempting to treat them as the same class. They are not the same product. The control family has one rating, 450/750 V; the 300/500 V figure belongs to the wiring and cord family. A datasheet that lists both is describing two products.
In the GB code, P, P2 and P3 are the screen types. In other conventions a “P” or “S” can mean the screen is present without saying which kind. Never assume a foreign product with an “S” or a “shielded” label has the same screen construction as a KVVP; check the screen type in the construction drawing.
A standard KVV is not a flame-retardant product. It passes the single-core vertical flame test to IEC 60332-1, which is a different test from the bunched-flame classes in GB/T 19666. Flame-retardant versions are ordered by adding the class to the code — ZA-, ZB- or ZC- — with the matching compound. Fire-resistant types carry an N- prefix and low-smoke halogen-free types WDZ-.
Write the standard the cable actually answers to: GB/T 9330.2-2008 for a PVC insulated and sheathed control cable, with the general requirements in GB/T 9330.1-2008 and the XLPE types in GB/T 9330.3-2008. State the conductor class (Class 1, 2 or 5 to GB/T 3956), the core count and cross-section, and the screen or armour, because those change the construction even when the type code is identical.
This page gives the standard relationships, the code decode and the construction facts. It does not decide whether a specific product complies with a specific project specification, and it does not state certification outcomes — those are confirmed against the certificate for the exact construction, and by the receiving authority for your project. Where a figure is a published product parameter rather than a clause of a standard, it is presented as such; where a standard's table value is not in our library, the page points to the table and does not invent the number.
GB/T 9330.2-2008 — Plastic insulated control cables, Part 2: PVC insulated and PVC sheathed control cables — with the general requirements in GB/T 9330.1-2008. Two numbers that appear on a lot of datasheets for this product do not belong here: IEC 60227 covers PVC insulated cables up to 450/750 V, meaning fixed wiring cables and flexible cords, and its type list has no KVV-type control cable; BS 6004 is the British standard for PVC insulated non-armoured power, lighting and internal wiring cable. The XLPE insulated control cables are in GB/T 9330.3-2008.
450/750 V, and only that. The GB/T 9330 control cable family has a single voltage class. Where a datasheet lists 300/500 V and 450/750 V together it is describing two different products, because 300/500 V belongs to the GB/T 5023 family of PVC insulated cables and cords. Design and test against 450/750 V.
KVV is the basic rigid type with a Class 1 solid or Class 2 stranded conductor, for fixed installation. KVVR uses a Class 5 flexible conductor, so it can be formed by hand and bent repeatedly during maintenance — the “R” is the flexible-structure field. KVVP adds a copper wire braid screen over the laid-up cores, and KVVP2 uses a copper tape screen instead of a braid. KVV22 is steel-tape armoured for mechanical protection. The fields combine: KVVRP is flexible and braid screened, KVVP2-22 is copper-tape screened and steel-tape armoured.
No. CY and SY are trade product names for European-style flexible screened control cable, not the scope of a single numbered standard, and they are built to different constructions. A KVV is made to GB/T 9330.2-2008 with GB/T 3956 conductors and a 450/750 V single class; a CY or SY cable answers to a different specification and is commonly a different voltage class. If a project names CY or SY, quote against that name and confirm the construction drawing rather than substituting a KVV.
From 2 to 61 cores, with the range narrowing as the cross-section grows — 61 cores at 0.5 to 1.0 mm², 37 at 1.5 mm², 24 at 2.5 mm² and around 10 at 10 mm². The limit is set by the finished diameter and by how buildable the core bundle is, not by the conductor standard. A construction drawing is issued for approval before production so the core count, screen and outer diameter are agreed in advance.
The minimum working ambient temperature is −15 °C and the cable should not be installed below 0 °C — PVC becomes brittle when cold and a bend made at −10 °C leaves damage that only appears later in service. This is an indoor cable: PVC sheath is not UV-stabilised for permanent outdoor exposure and the construction is not rated for direct burial. For outdoor or buried routes, tell us the installation and we will quote an armoured or XLPE insulated alternative.
Yes. Flame-retardant versions are ordered by adding the class to the code — ZA-, ZB- or ZC-class per GB/T 19666-2019 — and they use a flame-retardant PVC compound, which is why the class has to be specified rather than assumed. A standard KVV is not a flame-retardant product: it passes the single-core vertical flame test to IEC 60332-1, and that is a different test from the bunched-flame classes in GB/T 19666. Fire-resistant types carry an N- prefix and low-smoke halogen-free types WDZ-.
Yes to both. A construction drawing stating core count, cross-section, conductor class, screen or armour, outer diameter, sheath colour and marking is issued for approval before the first production run, and conductor resistance, insulation resistance and the 3000 V AC withstand test result are recorded per production length. Because a 4-core 1.5 mm² and a 61-core 0.5 mm² can share a type code and almost nothing else, the documentation is always matched to the exact construction quoted.
Tell us the type code, the core count and cross-section, the conductor class and the screen or armour. If your specification is written in IEC or BS letters, send that instead — our engineers will confirm the GB/T 9330 construction that meets it, or tell you honestly if a GB control cable is not the right family for the job.

How this was written: every figure in this article is checked against the standard or datasheet listed in Sources before publication. Where a value is our own measurement, it is labelled as such.